DAIKIN P1P2 Aux Heater Wiring Installation Guide

June 6, 2024
Daikin

DAIKIN logo

DAIKIN P1P2 Aux Heater Wiring

Introduction

DAIKIN P1P2 Aux Heater Wiring fig8

  • Aux heat is supported in P1P2 (VRV, SkyAir) and S21 (single/multi-split) systems
  • The aux heat source cannot require the indoor unit fan, just controlled from the thermostat.
  • The thermostats Aux outputs are dry contacts that close the connection to turn on the aux equipment.
  • A 24V AC control signal must be routed through the aux contacts.

Aux Heat Setup on Daikin One+

  • An aux heat source can be added in the “Equipment Setup” menu using “add equipment”.
  • The Aux heat can be setup as primary or the secondary source of heat. Once added, Emergency heat mode will also be added to the system mode menu.
  • Setup Aux heat source
  • Click on Add equipment / aux Heat source
  • Select Connection: select aux1 or aux 2 based on Wiring connection to AUX heater
  • Default: heat pump is primary heat source.
  • Select control to adjust parameters

DAIKIN P1P2 Aux Heater Wiring fig2

Set-up of Heat Pump as Primary Heat Source

Note: the heat pump lockout and the AUX heat lockout are based on the ambient temperature data. The Ambient temperature data is communicating to the ONE+ through the weather service, therefore the Wi-Fi connection is necessary for AUX heat logic to execute.
DAIKIN P1P2 Aux Heater Wiring fig3

Operation with Heat Pump as Primary Heat Source

  • Heat pump is primary heat source
  • Heat pump lockout adjustable from -20°F to 65°F in 5°F increments. (default 15°F)
  • Aux heat lockout adjustable from -10°F to 75°F in 5°F increments. (default 50°F)
  • Aux heat demand
  • Ton differential -7°F to -3°F in 1°F increments (default -3°F)
  • Toff differential -4°F to 1°F in 1°F increments (default 1°F)

DAIKIN P1P2 Aux Heater Wiring fig4

Set-up of Aux Heat as Primary Heat Source

DAIKIN P1P2 Aux Heater Wiring fig5

Operation with Aux Heat as Primary Heat Source

  • Aux. is primary heat source
  • Heat pump lockout adjustable from -20°F to 65°F in 5°F increments. (default 15°F)
  • Setpoint differential -9°F, -7°F, -4°F, and -2°F (default -2°F)
  • Aux heat demand
  • Ton differential -1°F to -2°F (default -1°F)
  • Toff differential 1°F fixed

DAIKIN P1P2 Aux Heater Wiring fig6

Independent Aux Heater Operation

The aux heater operates independently from the master’s mode.