DAIKIN P1P2 Aux Heater Wiring Installation Guide

June 6, 2024
Daikin

DAIKIN logo

DAIKIN P1P2 Aux Heater Wiring

Introduction

DAIKIN P1P2 Aux Heater Wiring fig8

  • Aux heat is supported in P1P2 (VRV, SkyAir) and S21 (single/multi-split) systems
  • The aux heat source cannot require the indoor unit fan, just controlled from the thermostat.
  • The thermostats Aux outputs are dry contacts that close the connection to turn on the aux equipment.
  • A 24V AC control signal must be routed through the aux contacts.

Aux Heat Setup on Daikin One+

  • An aux heat source can be added in the “Equipment Setup” menu using “add equipment”.
  • The Aux heat can be setup as primary or the secondary source of heat. Once added, Emergency heat mode will also be added to the system mode menu.
  • Setup Aux heat source
  • Click on Add equipment / aux Heat source
  • Select Connection: select aux1 or aux 2 based on Wiring connection to AUX heater
  • Default: heat pump is primary heat source.
  • Select control to adjust parameters

DAIKIN P1P2 Aux Heater Wiring fig2

Set-up of Heat Pump as Primary Heat Source

Note: the heat pump lockout and the AUX heat lockout are based on the ambient temperature data. The Ambient temperature data is communicating to the ONE+ through the weather service, therefore the Wi-Fi connection is necessary for AUX heat logic to execute.
DAIKIN P1P2 Aux Heater Wiring fig3

Operation with Heat Pump as Primary Heat Source

  • Heat pump is primary heat source
  • Heat pump lockout adjustable from -20°F to 65°F in 5°F increments. (default 15°F)
  • Aux heat lockout adjustable from -10°F to 75°F in 5°F increments. (default 50°F)
  • Aux heat demand
  • Ton differential -7°F to -3°F in 1°F increments (default -3°F)
  • Toff differential -4°F to 1°F in 1°F increments (default 1°F)

DAIKIN P1P2 Aux Heater Wiring fig4

Set-up of Aux Heat as Primary Heat Source

DAIKIN P1P2 Aux Heater Wiring fig5

Operation with Aux Heat as Primary Heat Source

  • Aux. is primary heat source
  • Heat pump lockout adjustable from -20°F to 65°F in 5°F increments. (default 15°F)
  • Setpoint differential -9°F, -7°F, -4°F, and -2°F (default -2°F)
  • Aux heat demand
  • Ton differential -1°F to -2°F (default -1°F)
  • Toff differential 1°F fixed

DAIKIN P1P2 Aux Heater Wiring fig6

Independent Aux Heater Operation

The aux heater operates independently from the master’s mode.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals