testifire 1000-001 Smoke and Heat Detector Tester User Guide

June 6, 2024
testifire

1000-001 Smoke and Heat Detector Tester

heat detector

www.acornfiresecurity.com
testifire®
MULTI-STIMULUS DETECTOR TESTER
Quick Start Guide

SIGNALING
Multi-Detector Test Apparatus as to Verification of Detector Functional Operation Only 77TL
www.acornfiresecurity.com

1. Charging the Battery Baton

○ The charger can be connected to
a mains power outlet or a 12 volt
vehicle socket (1). When connected,
the red Power LED will illuminate.
○ Connect the Battery Baton to the
charger and turn the locking ring
( 2 & 3 ).
○ The yellow Fast Charge LED will
illuminate (4).
○ Charge times vary but can be 75-90 minutes when charging a
fully discharged Battery Baton. When fully charged, the charger
will switch to Trickle Charge and the green LED will illuminate (4).
Note: Use only NiMH Battery Batons with Testifier.

2. Inserting the Battery Baton

○ To insert the Battery Baton, hold the Testifire head unit by the
handle and depress the upper spring button on the Battery Baton.
Align the button with the location hole in the handle and push the
Battery Baton into the handle until the button springs up through the location hole (5).

○ Insert the other end of the Battery Baton into the Solo access pole and depress the lower spring button. Align it with the location hole and push the Battery Baton further into
the pole until the button springs up
through the hole (6).

3. Removal & Replacement of Smoke Capsules (Testifire 1000 & 2000

series)

Removal:
○ Release the upper access cover A (7) on the body of the Testifire by opening it from the right hand side.
Note: Testifire 1000 series units only have one access cover.
○ Squeeze the two clips B of the used capsule and gently pull the capsule out.
spring clip Replacement:

○ Remove the capsule from its outer carton and Anti-Static bag.

○ Remove the spring clip protector cap from the new capsule C (8).

○ Holding the capsule by the spring clips with the label on the underside, carefully insert the new capsule into the capsule port. Push E it into position, ensuring that the E clips spring out positively on both Spring Clips sides of the capsule.

○ Close the access cover A securely.

4. Removal & Replacement of CO Capsules (Testifire 2000 series only)

Removal:
○ Only replace the CO capsule when it is empty. Turn Testifire off for five minutes to allow the capsule to cool down before removing it.
○ Release the lower access cover D (9) by opening it from the right hand side.
○ Squeeze the spring clips E on each side and gently pull the capsule out.
○ Do not touch the tip of the CO capsule as it may be hot.

protectorReplacement:
○ Remove the capsule from its carton and Anti-Static bag.
○ Remove the tip protector F (10).
○ Hold the capsule by the spring clips with the label uppermost. Carefully insert into position, ensuring that the clips spring out positively on both sides.
○ Close the access cover D securely.

5. Using the Menus

menu key○ Using the UP’ andDOWN’ menu navigation keys (11), you can move the cursor through the MAIN’ menu. Press theENTER’ key to select stimuli from the MAIN’ menu. ○ Pressing theESCAPE’ key goes back to the MAIN’ menu, or when a test sequence has been programmed and theMAIN’ menu is displayed, the ESCAPE’ key will cancel the programmed test sequence. ○ ADOWN’ arrow on the bottom right of the MAIN’ menu indicates more options are available below. Use theDOWN’ key on the keypad smoke
testto move down through the menu. (12).
○ The UP’ arrow on theMAIN’ menu indicates more options available above. Use the UP’ key on the keypad to move up through the menu (13). ○ Press theLEFT’ key on the keypad to go back one menu level.

6. Turning the Unit On

○ To turn the unit on, press and hold the red ON-OFF key’ for 2 seconds (14). TheStatus’ LED will flash slowly green to indicate that the unit is in STANDBY’ mode. ○ The first time the unit is poweredon you will be prompted to select the operating language for your region. Use theUP’ and DOWN’ ![operating language](https://manuals.plus/wp-content/uploads/2021/12/operating-language- png-107x300.png)keys to navigate and use theENTER’ key to select your language (15).
○ This will display a confirmation screen (16). Press the MENU’ key to confirm or theSTATUS’ key to cancel. The MAIN’ menu will be displayed. ○ After long periods of non-use or when a Smoke Capsule has been replaced, the unit will self-prime at power-on. ThePreparing for use Please wait’ message will be displayed for a short period (17).

7. Adjusting the Head Angle

adjustment setting○ Correct head angle adjustment is important. The detector should touch the base of the inner clear cup (22).

○ To adjust the head unit hold the body (18) and, pulling gently against the spring, angle the head unit away from the Battery Baton (19). The head unit will lock and remain in that position for testing.

8. Testing High Profile Detectors

inner clear cup○ When testing high profile detectors, remove the inner clear cup. Place your finger in the cut-out and carefully lift out the inner cup (20). This will 20 allow the detector to touch the platform (21).

www.acornfiresecurity.com
testifire®
MULTI-STIMULUS DETECTOR TESTER

Testing a Detector

1. How to Perform a Test

○ To carry out a simple, single stimuli

○ As the detector enters Testifire, the infrared beam test, use the UP’ and DOWN’ keys on the keypad to highlight the stimulus required e.g. Smoke’ (23). is interrupted by the body of the detector and the chosen test will begin, indicated by theStatus’ LED flashing faster.

○ Raise the Testifire head unit up to the
Note: It is very important that the detector under 23 detector to be tested, and place it test is in the correct position (22). Ideally, the centrally over the detector. bellows should seal against the ceiling surface.

2. Simultaneous Testing (selected tests at the same time)

In this example, Smoke’ andHeat’ are selected as a simultaneous test (24).
○ Move the cursor to Smoke’ and press theENTER’ key
1′ will be displayed alongsideSmoke’.
○ Move the cursor to Heat’ and press theENTER’ key
2′ will be displayed alongsideHeat’. Press ENTER’ once more to display1′ alongside Heat’. l Repeat the above as required for additional stimuli. ○ To delete a test setup, use theESCAPE’ key .
1. Programme the tests: Smoke 1
2. Raise Testifire over the detector: Smoke’ andHeat’ are tested at the same time as test `1′.
3. Lower Testifire from the detector: The test is completed and ready to test another detector in the same way.

3. Sequential Testing (selected tests, one after another)

smoke cursorIn this example, Smoke’,Heat’ and CO’ are selected as a sequential test (25). ○ Move the cursor toSmoke’ and press the ENTER’ key1′ will be displayed alongside Smoke’. ○ Move the cursor toHeat’ and press the ENTER’ key 2′ will be displayed alongside Heat’. ○ Move the cursor toCO’ and press the ENTER’ key3′ will be displayed alongside CO’. ○ To delete a test setup, use theESCAPE’ key .
1. Programme the tests: Smoke 1 Heat 2 CO 3
2. Raise Testifire over the detector: Smoke’ is tested as test1′.
3. Lower for 2-10 seconds, then raise Testifire again: Heat’ is tested as test2′.
4. Lower for 2-10 seconds, then raise Testifire again: CO’ is tested as test 3′.
5. Lower Testifire: The test is completed and ready to test another detector in the same way.

4. Combined Simultaneous and Sequential Testing

smoke statusIn this example, Smoke’ andHeat’ are combined as a simultaneous test followed by CO’ (26). ○Heat’ and Smoke’ can be combined as the first operation, followed by a CO’ test. Note: you will need to lower the head unit between each test.
○ To delete a test setup, use the `ESCAPE’ key .

Using these methods, you can programme Testifire to combine tests and continue in sequence.
In this example Smoke’ andHeat’ are tested together as test 1′ and then CO’ is tested as test 2′. **Note:**Clear’ (clearing) can also be selected in any of the above operations.

www.acornfiresecurity.com

Indicating LED Reference Chart

Test Type LED

test progressprogress portion

Status LED

status ledled status

Identification of Parts

identification parts1.Inner Clear Cup
2. Platform
3. Clear Cup
4. Bellows
5. RFID Antenna*
6. Infrared Beam
7. Main Duct for Heat, Smoke and CO

8. Testifire 100 RFID Bluetooth®Module*
9. Smoke Capsule TS3
10. CO Capsule TC3

11. USB Port (on rear of unit)
12. User Interface Display (LCD)
13. Test Type’ LED 14\.Status’ LED
15. Smoke Capsule Access Cover
16. CO Capsule Access Cover*
17. Adjustable Handle
18. Battery Baton
19. Infrared Remote Control Receivers

remote control

Infrared Remote Control

Generation of test stimuli starts when A Testifire Smoke Capsule TS3 stimuli generation to start. The optional B Testifire CO Capsule TC3* infrared remote control can be used to initiate the test procedure in such situations.

  • Depending on model specification ** Future option Testifire is positioned over a detector and remote controls are not generally required. Certain detectors (such as those with virtual chambers) have no physical features to cause

Replacement Capsules

replacement capsule

keypad interfaceinterface keyboard

General Safety Information

CAUTION Please refer to your User Manual and take clearnote of all warnings and cautions before using your Testifire.
Testifire has no userserviceable parts. Do not disassemble. Refer to the manual for Service and Support information.

www.testifire.com
Powered by TCPDF (www.tcpdf.org)