MITSUBISHI ELECTRIC PUD-SHWM80VAA Air-To-Water Heat Pump Systems Heat Only Bibloc Instruction Manual
- June 6, 2024
- Mitsubishi Electric
Table of Contents
PUD-SHWM80VAA Air-To-Water Heat Pump Systems Heat Only Bibloc
Ensuring efficient operation of your Ecodan heating and hot water system
ecodan.co.uk
Commissioning Checklist
This Commissioning Checklist is to be completed in full by the installer who
commissioned the Ecodan and associated equipment as a means of demonstrating
compliance with the appropriate Building Regulations and then handed to the
customer to keep for future reference.
For further information, please refer to Mitsubishi Electric training
literature and installation manual. Failure to install and commission this
equipment to the manufacturer’s instructions may invalidate the warranty but
does not affect statutory rights.
Customer Information Name: Telephone: Email:
Address:
Installer Information Name: Company: Telephone: Email: MCS Installer Reg No. G3 Certification No.
Address:
ME Installer No. F-Gas Certification No. Certified Operative Reg. No.
Building Information Heating System Peak Heat Loss (kW): Peak Hot Water Volume (L): Building Regulations Notification No. DNO Notification:
(Tick appropriate boxes if applicable)
Connect & Notify
Apply to Connect
Commissioning Checklist
Heat Pump Information
Heat Pump Technology:
Air Source Ground Source
(Tick appropriate boxes if applicable)
Water Source
Other
Model No.
Qty:
Serial No.
Type:
Monobloc
Split
Other
Application:
Heating & Hot Water
Heating Only
Hybrid
Cascade
Hot Water System Information Manufacturer:
Model No.
Qty:
Serial No.
Type:
Vented
Un-Vented
Thermal Store
Other
Application:
Direct
In-Direct
Electrical & Hydronic Control Information Manufacturer:
Model No.
Qty:
Serial No.
Type:
Wired
Wireless
Wi-Fi Adapter Information Manufacturer:
Model No.
Qty:
Serial No.
MAC ID Address:
Supplementary Hybrid System Information Manufacturer:
Model No.
Qty:
Serial No.
Type:
Vented
Gas Boiler
Oil Boiler
Other
Application:
Heating & Hot Water
Heating Only
Hybrid
Cascade
Commissioning Checklist
Electrical & Hydronic Controls – System & Heat Pump
1 Time & Temperature Control to Heating
2 Time & Temperature Control to Hot Water
3 Hybrid System – synchronised control of boiler and heat pump fitted
Room Thermostat & Programmer/Timer
Programmable Room Thermostat
Cylinder Thermostat & Programmer/Timer
Yes If Yes – boiler model switching point (Quote Tariff or Temperature Level)
4 Heating Zone Valves (including underfloor loops)
Pre-existing
5 Hot Water Zone Valves
Pre-existing
6 Thermostatic Radiator Valves 7 Outdoor Sensor
Pre-existing Pre-existing
8 Heat Pump Safety Interlock (3)
Pre-existing
9 Flow & Cylinder temperature sensors correctly positioned?
10 Automatic Bypass System
Pre-existing
11 Buffer Vessel Fitted
No
Yes If Yes, Volume:
(Tick appropriate boxes if applicable)
Load/Weather Compensation
Optimum Start Control
Combined with Heat Pump main controls
Fitted Fitted Fitted Built In Built In No Fitted
Litres:
Not Required Not Required Not Required Provided Provided Yes Not Required
12 Plate Heat Exchanger fitted to give hydronic separation 13 Expansion vessel for heating is sized, fitted & charged in accordance with manufacturers instructions? 14 Legionella protection for stored hot water provided by timed temperature co l?
15 Weather Compensation Settings
ºC flow at
ºC outdoor &
ºC flow at
16 Control System
FTC2 FTC3 FTC4
No
Yes
Yes
Yes
ºC outdoor
FTC5 FTC6
17 Third Party Controls?
No Yes Manufacturer Name & Mode:
18 Are third party controls correctly interlocked?
No
Yes
All Systems
(Tick appropriate boxes if applicable)
1 The heating system has been filled and pressure tested
Yes
2 Expansion vessel for heating is sized, fitted & charged in accordance with manufacturer’s instructions
Yes
3 The system has been flushed and cleaned in accordance with BS7593: 2019 and heat pump manufacturer’s instructions Yes
4 What system cleaner was used?
Brand:
Product:
5 What heating system inhibitor was used?
Brand:
Product:
6 What heat pump anti-freeze has been used?
Brand:
7 What is the heat pump anti-freeze concentration level?
Product: %
Commissioning Checklist
All Systems
8 System filter fitted in accordance with BS 7593: 2019?
(Tick appropriate boxes if applicable)
Yes
9 Outdoor fuse rating
10 Cylinder coil surface area or Plate heat exchanger
11 Legionella protection
A M² ºC every
Type Plate Heat Exchanger Fitted
Days
Not Available Heating Only
12 Circulating pump(s) speed settings?
13 Measured flowrate
Domestic Hot Water
Litres/Min
Heating
Litres/Min
14 Measured steady state delta T (Flow and Return)
ºC
Flow Temperature
ºC
Return Temperature
ºC
Outdoor Unit
1 Is the heating system adequately frost protected and pipes insulated to prevent heat loss?
2 Split only: The refrigerant circuit has been evacuated and charged in accordance with manufacturer’s instructions
Yes
3 The heat pump is fitted on a solid/stable surface capable of taking its weight
Yes
4 The necessary heat pump defrost provision been put in place
Yes
5 The heat pump fan free from obstacles and operational
Yes
6 Is all external pipework insulated?
No
Yes
7 ASHP only: Does the outdoor unit have adequate airflow as per the manufacturers guidelines?
No
Yes
8 Has suitable consideration been made for condensate discharge?
No
Yes
9 Flow and return isolation valves fitted?
No
Yes
10 Anti-Vibration mounting pads fitted?
No
Yes
11 Refrigerant type:
Weight (kG):
12 Has the condensate drain been installed to the manufacturers instructions?
Heating Mode
1 The heating system has been filled and pressure tested
No
Yes
Yes
2 Heating Temperatures
Heating Flow Temperature
ºC Heating Return Temperature
ºC
3 Emitter type 4 Emitters balanced? 5 Air removed from system? 6 System correctly balance/rebalanced
Underfloor Heating
Radiators
Towel Rail
Yes
Not Required
Yes
Yes
Commissioning Checklist
Domestic Hot Water Mode – Measure & Record
1 Is the heat pump connected to a hot water cylinder? Unvented 2 Hot water
cylinder size
3 Domestic hot water target temperature 4 Hot water has been checked at all
outlets 5 Have Thermostatic blending valves been fitted?
Vented
(Tick appropriate boxes if applicable)
Thermal store Not Connected Litres
ºC Cylinder heat up Not Required
Minutes Yes Yes
Additional System Information
1 Water Flow rate setting of the heat pump at commissioning (I/min):
2 Additional heat sources connected
Gas Boiler Other
3 Remove & clean line strainer if present
4 The operation of the heat pump and system controls have been demonstrated to
the end-user
Oil Boiler
No No
Electric Heater Solar Thermal
Yes
Not Applicable
Yes
Not Applicable
All installations
1 All electrical work complies with the appropriate Regulations
Yes
2 The heat pump and associated products have been installed and commissioned in accordance with the manufacturer’s instructions
Yes
3 The operation of the heat pump and system controls have been demonstrated to and understood by the customer
Yes
4 The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained
and left with the customer
Yes
Mains Pressure Hot Water Storage System Commissioning Checklist
Domestic Hot Water Mode – Measure & Record
1 Is the primary circuit a sealed or open vented system? 2 What is the maximum
primary flow temperature?
(Tick appropriate boxes if applicable)
Sealed
Open
ºC
All Systems
1 What is the incoming static cold water pressure at the inlet to the system?
2 Has a strainer been cleaned on installation debris (if fitted) ?
No
3 Is the installation in a hard water area (above 200ppm) ?
No
4 If Yes, has a water scale reducer been fitted ?
No
5 What type of scale reducer has been fitted ?
6 What is the hot water thermostat set temperature ?
7 What is the maximum hot water flow rate at set thermostat temperature
(measured at high flow outlet) ?
8 Time and temperature controls have been fitted in compliance with Part L of
the Building Regulations?
9 Type of control system (if applicable)
Y Plan
S Plan
10 Is the cylinder solar (or other renewable) compatible ?
No
11 What is the hot water temperature at the nearest outlet ?
12 All appropriate pipes have been insulated up to 1 metre or the point where they become concealed
Bar Yes Yes Yes
ºC l/min Yes Other Yes ºC Yes
Unvented Systems
1 Where is the pressure reducing valve situated (if fitted) ?
2 What is the pressure reducing valve setting ?
Bar
3 Has a combined temperature and pressure relief valve and expansion valve been fitted and discharge tested ?
No
Yes
4 The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations
Yes
5 Are all energy sources fitted with a cut out device ?
No
Yes
6 Has the expansion vessel or internal air space been checked ?
No
Yes
Mains Pressure Hot Water Storage System Commissioning Checklist
Thermal Stores Only
1 What store temperature is achievable ? 2 What is the maximum hot water
temperature ?
(Tick appropriate boxes if applicable)
ºC ºC
All Installations
1 The hot water system complies with the appropriate Building Regulations
Yes
2 The system has been installed and commissioned in accordance with the manufacturer’s instructions
Yes
3 The system controls have been demonstrated to and understood by the customer
Yes
4 The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained
Yes
and left with the customer
Commissioning Engineer’s Signature
Customer’s Signature*
Date
- (To confirm satisfactory demonstration and receipt of manufacturers’ literature)
All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer. © Heating and Hot Water Industry Council (HHIC)
Annual Service Tasks
Mechanical Tasks
(Tick appropriate boxes if applicable)
1 Inspect and clean evaporator fins. Repair damaged fins using a fin comb if required
2 Check visually for signs of oil leaks which may indicate a refrigerant leak (check for leaks if necessary)
3 Check integrity of refrigerant / water pipe work and lagging, repair lagging if required
4 Check system operation
5 Check the antifreeze and if necessary top up the concentration as per manufacturer’s recommendations
6 Check and clean the magnetic particle filter
7 Check system pressure
8 Release any air from the primary/heating systems
Controller Tasks 9 Check for the correct operation and temperature setting of
the thermostats 10 Check the operation of the zone valves 11 Check the
operation and the timing of the immersion heater
On Completion Check that the whole system is working satisfactorily Mitsubishi
Electric recommends that the frequency of maintenance visits to be a maximum
of 12 months between inspections. Frequency of maintenance may increase
dependent upon the equipment and local water conditions e.g. hard water, scale
forming, water containing a high proportion of solids. Failure to maintain the
system to the above minimum recommendations could result in the warranty
becoming null and void. Please fill in the Service Record sheet to confirm the
above tasks have been carried out on the Ecodan outdoor unit.
Service Record
It is recommended that your Ecodan is serviced regularly and that the
appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Services Interval Record below, please
ensure you have carried out the service as described in the manufacturer’s
instructions. Always use the manufacturer’s specified spare part when
replacing components.
Service 1
Engineer Name:
Date:
Company Name:
Telephone No:
Operative ID No:
System inhibitor concentration has been checked and appropriate action taken,
in accordance with BS 7593 and heat pump manufacturers’ instructions.
Comments:
Yes N/A
Service 2
Engineer Name:
Date:
Company Name:
Telephone No:
Operative ID No:
System inhibitor concentration has been checked and appropriate action taken,
in accordance with BS 7593 and heat pump manufacturers’ instructions.
Comments:
Yes N/A
Service 3
Engineer Name:
Date:
Company Name:
Telephone No:
Operative ID No:
System inhibitor concentration has been checked and appropriate action taken,
in accordance with BS 7593 and heat pump manufacturers’ instructions.
Comments:
Yes N/A
Service 4
Engineer Name:
Date:
Company Name:
Telephone No:
Operative ID No:
System inhibitor concentration has been checked and appropriate action taken,
in accordance with BS 7593 and heat pump manufacturers’ instructions.
Comments:
Yes N/A
Service 5
Engineer Name:
Date:
Company Name:
Telephone No:
Operative ID No:
System inhibitor concentration has been checked and appropriate action taken,
in accordance with BS 7593 and heat pump manufacturers’ instructions.
Comments:
Yes N/A
Telephone: 01707 282880
MELSmart Customer Services & Support: 0161 866 6089
Option 1 – Air Conditioning Technical Option 2 – Spares Option 3 – Warranty
Option 4 – Heating Technical Option 5 – Returns Option 6 – Product Training & Site Services
email: livingenvironmentalsystems@meuk.mee.com website: les.mitsubishielectric.co.uk
UNITED KINGDOM Mitsubishi Electric Europe Living Environment Systems Division
Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England General Enquiries
Telephone: 01707 282880 Fax: 01707 278881
IRELAND Mitsubishi Electric Europe, Westgate Business Park, Ballymount, Dublin
24, Ireland
Telephone: (01) 419 8800 Fax: (01) 419 8890 International code: (003531)
Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi
Electric Europe 2020. Mitsubishi and Mitsubishi Electric are trademarks of
Mitsubishi Electric Europe B.V. The company reserves the right to make any
variation in technical specification to the equipment described, or to
withdraw or replace products without prior notification or public
announcement. Mitsubishi Electric is constantly developing and improving its
products. All descriptions, illustrations, drawings and specifications in this
publication present only general particulars and shall not form part of any
contract. All goods are supplied subject to the Company’s General Conditions
of Sale, a copy of which is available on request. Third-party product and
brand names may be trademarks or registered trademarks of their respective
owners.
Note: The fuse rating is for guidance only. Please refer to the relevant
databook for detailed specification. It is the responsibility of a qualified
electrician/electrical engineer to select the correct cable size and fuse
rating based on current regulation and site specific conditions. Mitsubishi
Electric’s air conditioning equipment and heat pump systems contain a
fluorinated greenhouse gas, R410A (GWP:2088), R32 (GWP:675), R407C (GWP:1774),
R134a (GWP:1430), R513A (GWP:631), R454B (GWP:466), R1234ze (GWP:7) or R1234yf
(GWP:4). *These GWP values are based on Regulation (EU) No 517/2014 from IPCC
4th edition. In case of Regulation (EU) No.626/2011 from IPCC 3rd edition,
these are as follows. R410A (GWP:1975), R32 (GWP:550), R407C (GWP:1650) or
R134a (GWP:1300).
015
015
Follow us @meuk_les Follow us @green_gateway
Mitsubishi Electric Cooling and Heating UK
Mitsubishi Electric Living Environmental Systems UK
SAP NO. 574311
Mitsubishi Electric Living Environmental Systems UK
mitsubishielectricuk_les
thehub.mitsubishielectric.co.uk
Designed by Square Bear Limited 01604 899099
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>