HITACHI WJ200 Drives 150HF User Guide
- June 6, 2024
- Hitachi
Table of Contents
- Quick Start Essential
- To Unlock All the Parameters
- To Set the Motor Current
- To Set the Motor Poles
- To Set the Speed Reference
- To Set the Run Command Source
- To Set the Frequency or Speed
- To Set the Acceleration Time
- To Set the Deceleration Time
- **To Set the Stop Mode
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
0Inspire the Next
WJ200
Quick Start
Quick Start Essential
Parameters
b037 – Unlocks parameters (default 04)
A001 – Frequency (Speed) Source (default 02)
A002 – Run Command Source (default 02)
b012 – Motor nameplate current (default varies)
b091 – Stop Mode (default 00)
H004 – Motor nameplate poles (default 4 poles)
F001 – Keypad Speed setting (default 00.00)
F002 – Acceleration time (default 10 seconds)
F003 – Deceleration time (default 10 seconds)
To Unlock All the Parameters
- Press ESC to enter programming mode
- Press ESC until parameter b001 is on the display of your drive
- Press the UP key until b037 is reached
- Then press the SET key to enter the b037 parameter
- Now you can change the 04 to 00 using the down key
- Press the SET key to save the data Now you have unleashed your WJ200 drive!
To Set the Motor Current
- Press ESC to enter programming mode
- Press ESC until parameter b001 is on the display of your drive
- Press the UP key until b012 is reached
- Then press the SET key to enter the b012 parameter
- Now you can set your motor nameplate current using the Up and Down keys
- Press the SET key to save the data
To Set the Motor Poles
- Press ESC to enter programming mode
- Press ESC until parameter H001 is on the display of your drive
- Press the UP key until H004 is reached
- Then press the SET key to enter the H004 parameter
- Now you can set the motor poles based on the speed of your motor
- Press the SET key to save the data
Motor poles = 120*60/synchronous speed (1200, 1800, 3600 RPM)
To Set the Speed Reference
-
Press ESC to enter programming mode
-
Press ESC until parameter A001 is on the display of your drive
-
Then press the SET key to enter the A001 parameter
-
Select the speed reference from the options below
00- To use the Keypad Potentiometer
01- Analog input (0- 10Vdc, or 4-20mA) from the terminals
02- When using the Keypad set the speed with parameter F001
03- When setting the speed via Modbus communication network
04- Option card used for speed
06- If your application is using a pulse train input
07- When setting the speed via the Easy Sequence programming
10- When the speed is a result of an operation used in your drive programming -
Press the SET key to save the data
To Set the Run Command Source
-
Press ESC to enter programming mode
-
Press ESC until parameter A001 is on the display of your drive
-
Press the UP key until A002 is reached
-
Then press the SET key to enter the A002 parameter
-
Now you can select the run command source from the options below
01- To use the digital input via the terminals
02- When your application calls for using the Keypad to run command
03- Use this option when commanding your drive to run via your Modbus communication network
04- Option card used for run -
Press the SET key to save the data
To Set the Frequency or Speed
- Press ESC to enter programming mode
- Press ESC until parameter F001 is on the display of your drive
- Then press the SET key to enter the F001 parameter
- Now you can adjust the speed of your drive based on your application
- Press the SET key to save the data
F001 parameter can be adjusted with your driver stopped or running.
To Set the Acceleration Time
- Press ESC to enter programming mode
- Press ESC until parameter F001 is on the display of your drive
- Press the UP key until F002 is reached
- Then press the SET key to enter the F002 parameter
- Now you can adjust the acceleration time of your drive based on your application. The time is adjusted using the Up and Down keys
- Finally, press the SET key to save the data
To Set the Deceleration Time
- Press ESC to enter programming mode
- Press ESC until parameter F001 is on the display of your drive
- Press the Up key until F003 is reached
- Then press the SET key to enter the F003 parameter
- Now you can adjust the deceleration time of your drive based on your application. The time is adjusted using the UP and Down keys
- Press the SET key to save the data
**To Set the Stop Mode
**
-
Press ESC to enter programming mode
-
Press ESC until parameter b001 is on the display of your drive
-
Press and hold the UP key until b091 is reached
-
Then press the SET key to enter the b091 parameter
-
Now you can select the Stop Mode from the options below
00- decelerate to stop (controlled stop)
01- free run stop (coast) -
Press the SET key to save the data
TECH SUPPORT
980-500-7141
WEBSITE
https://www.hitachi-iesa.com/ac-drivesinverters
EMAIL
Inverter.Info@hitachi-iesa.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>