TTK FG-ALS4 Four-Zone Alarm and Location System Unit Installation Guide
- June 6, 2024
- TTk
Table of Contents
TTK FG-ALS4 Four-Zone Alarm and Location System Unit
Panel Mounting
- Fix the panel to the wall using 4 screws (not included).
- Five push-through holes are provided for installing the PG11 glands.
- Power supply
- Relays
- Outputs 1&2
- Outputs 3&4
- JBUS/MODBUS
- Knock out the push-through holes from the outside.
- Connect all plug-in terminals (refer to step 2).
- Plug the terminals.
- Close the box, starting by inserting the top side, and then push the bottom down. Lock, using the two available screws.
- Power up from the circuit breaker
Electrical Connections
-
Connect the sense cables following this color code:
A: Green
B: White
C: Black
D: Red
Terminate unused outputs with two loops between connectors A & B and C & D.
The wiring diagram is on the back page. -
Connect the relays:
COM: Common
NC: Normally Closed
NO: Normally Open -
Five relays are available on FG-ALS4:
Relay 1 = leak zone 1
Relay 2 = leak zone 2
Relay 3 = leak zone 3
Relay 4 = leak zone 4
Relay 5 = cable-break all zones -
Connect the power supply following the signs:
Ground sign: Ground
N: Neutral
L: Live
Power supply : 100-240 V AC 50/60 Hz 0.25 A
Capacity
The FG-ALS4 panel is designed to receive up to 45m (147 ft) of sense cable (FG-ECS, FG-ACS, FG-ECX, FG-ACX) per zone.
Powering-on the System
Power on from the circuit breaker:
The panel will sound and show ‘‘SYSTEM TEST’’ for 20 seconds on the display,
and will then show the ‘‘home’’ screen:
Settings
-
Touch the second button (arrows), the touch screen shows the lengths installed on each of the four zones:
-
Alarm screen:
If a fault occurs (leak or cable-break), the leak alarms are represented by a drop of liquid;
Cable-break alarms are represented by scissors and the ‘‘sensor’’ label.
The system will return to the ‘‘home’’ screen after 30 seconds of inactivity.
MODBUS
The MODBUS protocol implemented on FG-ALS4 allows the current status of the
system to be supervised. The two types of alarm (leak and cable-break) are
coded using different Modbus registers for each individual zone.
The physical support of the MODBUS is two-wire RS485.
Serial port configuration | 9600 B, 8 data bits, 1 stop bit, no parity |
---|---|
Communication protocol | MODBUS or JBUS, functions 3 or 4 |
Maximum number of FG-ALS connected to the same controller | 31 |
Slave number | 1 to 255 |
Maximum number of reading registers | 16 |
MODBUS addresses in the memory | Register 1 = length zone 1 |
Register 2 = leak zone 1
Register 3 = cable-break zone 1 Register 4 = leak location zone 1
Register 5 = length zone 2
Register 6 = leak zone 2
Register 7 = cable-break zone 2 Register 8 = leak location zone 2
Register 9 = length zone 3
Register 10 = leak zone 3
Register 11 = cable-break zone 3 Register 12 = leak location zone 3
Register 13 = length zone 4
Register 14 = leak zone 4
Register 15 = cable-break zone 4 Register 16 = leak location zone 4
Format of the solution:
Slave number
| Function| No. of bytes read| Byte 1| Byte 2| …| Byte N| CRC 16
---|---|---|---|---|---|---|---
1, 2, …, 255| 3 or 4| up to 32| XXh| XXh| …| XXh|
XXXXh
- Remarks:
– The last panel on the serial link should be terminated with a 120 Ohms / 1W resistor between points RT- and RT+. The shielding of the data transmission cable should be connected to the controller’s earth and to the terminal COM of each FG-ALS panel.
– Slave number 0 inhibits the MODBUS operation.
– It is advisable to leave at least 200 ms between the successive requests.
Although carefully prepared to ensure technical accuracy, this brochure is intended for promotional use only. TTK cannot guarantee that the information contained herein is free of errors or omissions, and hence does not accept liability related to the use of its equipment. TTK maintains its obligations set out in the Standard Terms and Conditions of Sale and will not, under any circumstances, assume liability for any incidental damages, indirect or consequential, arising from the sale, resale, use or misuse of this product. All purchasers accept their responsibility as sole judge of the suitability of the product for the intended use. FG-NET, FG-SYS and TOPSurveillance are trademarks of TTK S.A.S. © TTK 2021
- TTK Headquarters / 19 Rue du Général Foy, 75008 Paris, France / T: +33.1.56.76.90.10 / F: +33.1.55.90.62.15 / www.ttk.fr / ventes@ttk.fr
- TTK UK Ltd. / 3 Luke Street London EC2A 4PX / United Kingdom / T : +44 20 7729 6002 / F : +44 20 7729 6003 / www.ttkuk.com / sales@ttkuk.com
- TTK Pte Ltd. / #10-08, Shenton House, 3 Shenton Way / Singapore 068805 / T: +65 6220.2068 / M: +65 9271.6191 / F: +65 6220.2026 / www.ttk.sg / sales@ttk.sg
- TTK Asia Ltd. / 2107-2108 Kai Tak Commercial Building / 317 Des Voeux Road Central / Hong Kong / T: +852 2858.7128 / F: +852 2858.8428 / www.ttkasia.com / info@ttkasia.com
- TTK Middle East FZCO / Building 6EA, Office 510 PO Box 54925 / Dubai Airport Free Zone /UAE / T: +971 4 70 17 553 / M: +971 50 259 66 29 / www.ttkuk.com / cgalmiche@ttk.fr
- TTK Deutschland GmbH / Berner Strasse 34, 60437 Frankfurt / Germany / T : +49 (0)69-95005630 / F : +49(0)69-95005640 / www.ttk-gmbh.de / vertrieb@ttk-gmbh.de
- TTK North America Inc / 1730 St Laurent Boulevard Suite 800 / Ottawa, ON, K1G 5L1 / Canada / T: +1 613 566 5968 / www.ttkcanada.com / info@ttkcanada.com
- Thomas Sales & Marketing Inc. TTK Master Distributor For USA / 7200 W 66th St / Bedford Park, IL 60638 / USA / T: +1 630-518-4724 / www.ttkusa.com /dmolk@ttkusa.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>