EIP CD30 Industrial Dehumidifier Owner’s Manual
- June 6, 2024
- EIP
Table of Contents
EIP CD30 Industrial Dehumidifier
UNPACKING
Carefully remove the CD30 dehumidifier unit from its transit box and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing; it will be useful when transporting the dehumidifier unit in the future.
INTRODUCTION
Dehumidifiers remove moisture from the air that is circulating through the
unit. The resulting reduction of relative humidity helps prevent rust, rot,
mould, mildew and condensation within the room, or other enclosed spaces where
the dehumidifier is used.
A dehumidifier consists of a motor-compressor unit, a refrigerant condenser,
an air circulating fan, a refrigerated surface, a means of collecting and
disposing the condensed moisture and a cabinet to house these components. The
fan draws air through the refrigerated surface and cools it below its dew
point, removing moisture which is collected and led away. The cool air then
passes the hot condenser, where it is reheated. With the addition of other
radiated heat the air is discharged into the room at a higher temperature but
lower relative humidity than when the air entered the unit. Continuous
circulation of the room air through the dehumidifier unit gradually reduces
the relative humidity in the room.
The CD30 has been designed for the exacting conditions which can prevail in
offices, shops, houses, restaurants, public houses etc. It combines lightness
and compactness with high reliability and strength. The gas, which is used
inside the hermetically sealed refrigeration circuit is R134a and contains no
CFC’s and has therefore a zero ozone depletion factor.
SPECIFICATIONS
M ODEL : | CD30 | CD30E |
---|---|---|
H EIGHT : | 300mm | **** |
300mm
W IDTH :| 304mm| 350mm
L ENGTH :| 550mm| 550mm
W EIGHT :| 23 Kg| 25 Kg
A IRFLOW :| 150 M3/Hr| 150 M3/Hr
P OWER S UPPLY :| 240V, 1 ph, 50Hz| ****
240V, 1 ph, 50Hz
P OWER| 360W (max)| 460W (max)
F INISH :| grey epoxy coating| grey epoxy coating
E FFECTIVE V OLUME :| 85M3| 85M3
R EFRIGERANT T YPE /Q TY :| R134a (170g)| R134a
(170g)
“This product contains fluorinated greenhouse gases covered by the Kyoto
Protocol. The refrigeration system is hermetically sealed.
The Global Warming Potential (GWP) of refrigerants used in products
manufactured by Ebac Industrial Products Ltd is as follows
R134a – 1300
R407c – 1610
For type and weight of refrigerant contained in this unit, please refer to the
product data label”
INSTALLATION
POSITIONING:
Position the dehumidifier unit in the center of the room to be conditioned if
at all possible. However if a damp patch is particularly apparent the outlet
grille should be pointed towards it.
NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have
clear space around them and not be obstructed in anyway.
WIRING:
Connect the power mains cable to a 5 or 13 Amp power supply. As follows:- 230V
supply
- Brown: Live
- Blue: Neutral
- Green/Yellow: Earth (ground)
DRAINAGE:
Connect a 12.5mm inside diameter hose to the condensate outlet pipe
(positioned centrally, beneath the air inlet grille). Secure the hose using a
worm drive clip. The hose should at no point be raised higher than the outlet
pipe. Hose should be ran to a permanent drain. Failure to observe this
requirement will result in flooding of the dehumidifier.
OPERATION
The operation of the dehumidifier is to remove moisture from the air by having it condense on the cold tubes of the evaporator coil. The air then passes over the hot condenser coil and returns to the conditioned space slightly warmer and dryer than when it entered the dehumidifier unit.
AIR MOVING SYSTEM:
Air is drawn in through the inlet grille at the rear of the dehumidifier
(below the handle) and over the two heat exchanges (evaporator/condenser
coils) under the influence of the axial fan, which is driven by the motor. The
operation of the fan is to run continuously whenever the power is supplied to
the dehumidifier. The fan motor used in the dehumidifier unit is induction
protected i.e. the motor is able to take stalled current without burning out
the motor windings.
DEFROST OPERATION:
Should the ambient temperature fall below 15°C the ice will form on the
evaporator coil as the air is passed over it, and in turn the efficiency of
the unit will drop. To prevent the build-up of ice on the evaporator coil a
timer is incorporated to energize the hot-gas defrost valve every 55mins for a
period of 4mins. Operating the hot-gas valve causes the evaporator coil to
defrost and the water to drain down to the condensate pan and into the
drainage tube.
HIGH-TEMPERATURE CUTOUT:
The CD30 dehumidifier has been designed to work in ambient temperatures
between -5°C and +35°C. Should the temperature in the room become excessive a
thermostat within the compressor casing will open and dehumidifying will stop,
until the thermostat resets itself.
HUMIDISTAT CONTROL:
The CD30 is fitted with a control humidistat, which measures the relative
humidity of the air within the room to be conditioned. The humidistat
incorporates a pointer and scale, which can be adjusted, and set to a relative
humidity level that is acceptable to maintain the required conditions within
the room. The humidistat controls the on/off function of the dehumidifier,
when the relative humidity of the air in the room falls below the set point of
the humidistat the dehumidifier will switch off, but when the relative
humidity of the air starts to rise again and passes the set point the unit
will switch on. The humidistat is used for the on/off function as it is a
cost-effective method that ensures power is only used when needed.
WARNING:
- Due to the high pressures within the refrigeration circuit, under no circumstances must direct heat be applied to the evaporator coil in an attempt to remove the build up of ice.
- No attempt should be made to cut open any part of the refrigeration circuit due to high pressures and gas involved.
- If the unit is switched off at the mains power supply for any reason, the unit must be allowed to stand at rest for at least three minutes before restarting. Failure to do so may cause the unit to blow the fuses owing to the compressor due to there being a refrigerant imbalance.
SPECIAL FEATURES
(Where Fitted)
Temperature Controlled Defrost
The ‘CD30E’ Dehumidifier unit can be fitted with temperature sensitive devices
which will operate in conjunction with the defrost control. In normal
operation the defrost control will come into operation every 55minutes, this
is to ensure that there will be no build up of ice at lower temperatures, but
where year round conditions need to be maintained the dehumidifier will have
to operate across a wider range of temperatures. To ensure that the
dehumidifier operates most efficiently this temperature sensitive device will
restrict the operation to the times when the evaporator coil is at –2ºC.
Heated Condensate Drainage Tube
The ‘CD30E’ dehumidifier unit can be fitted with a heater tape, which will run
the length of the condensate drainage tube. The effect of this heated
condensate drainage tube will ensure that when the drainage point for the unit
is not in the same room, but is run outside the room and could fall below
freezing point, the tube will be warm enough to still allow the condensate to
flow. Ensure that the heater tape does not protrude past the condensate
drainage tube, if it does then the tape should be doubled up and fed back up
into the condensate tube.
Control Humidistat
This humidistat operates in the same way as the normal humidistat to control
the on/off function of the dehumidifier units, but is factory pre-set at 55%
RH to maintain the relative humidity air at the set point.
Alarm Humidistat
This humidistat, which has been factory pre-set at 70% RH, allows for
connection to an external warning system. This warning indicating system will
be monitored by the customer and will warn and indicate when the relative
humidity of the air within the room has risen above a warning level due to a
fault, either with the dehumidifier or due to some other circumstances and
will require a service engineer.
NOTE RATING OF ALARM HUMIDISTAT IS 3.5A @ 240V
Alarm Wiring:
- Plug L – Normally open contacts
- Plug N – Close on humidity rise
- Plug E – Earth
ROUTINE SERVICE
WARNING :
ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE
CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD
ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON.
To ensure continued full efficiency of the dehumidifier, maintenance
procedures should be performed as follows:
Removal of the cover is achieved by means of four screws at the sides of the
unit at base level. With the cover removed all maintenance can be carried out.
-
Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air. Hold the nozzle of the air hose away from the coil (approx 6”) to avoid damaging the fins. Alternatively, vacuum clean the coils.
WARNING:
DO NOT STEAM CLEAN REFRIGERATION COILS -
Check that the fan is firmly secured to the motor shaft and that the fan rotates freely.
The motor is sealed for life and does not require any lubrication -
To check the refrigerant charge, run the unit for 15 minutes and briefly remove the cover. The evaporator coil should be evenly frost coated across its surface. At temperatures above 25°C, the coil may be covered with droplets of water rather than frost. Partial frosting accompanied by frosting of the thin capillary tubes, indicates loss of refrigerant gas or low charge.
-
Check all wiring connections.
IF ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC SERVICE CENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE.
REPAIRS
-
Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part.
-
If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action.
Any competent refrigeration technician will be able to service the equipment. The following procedure must be used:
a. The source of the leak must be determined and corrected.
b. The machine should be thoroughly evacuated before recharging.
c. The unit must be recharged with refrigerant measured accurately by weight.
d. For evacuation and recharging of the machine, use the crimped and brazed charging stub attached to the side of the refrigerant compressor.
The charging stub should be crimped and rebrazed after servicing. NEVER allow permanent service valves to be fitted to any part of the circuit. Service valves may leak causing further loss of refrigerant gas. -
The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service. Compressor failure can result from the machine losing its refrigerant gas. The compressor can be replaced by a competent refrigeration technician.
Failure of the compressor can be confirmed by the following procedure:
a. Establish that power is present at the compressor terminals using a voltmeter.
b. With the power disconnected, check the continuity of the internal winding by using meter across the compressor terminals. An open circuit indicates that the compressor should be replaced.
c. Check that the compressor is not grounded by establishing that a circuit does not exist between the compressor terminals and the shell of the compressor.
TROUBLESHOOTING
S YMPTOM | C AUSE | R EMEDY |
---|
Little or no airflow
| 1. Loose fan on shaft
2. Fan motor burnt out
3. Dirty refrigeration coils
4. Loose electrical wiring
5. Control humidistat either set too high or malfunctioning
| 1. Tighten fan
2. Replace the fan motor
3. See Routine Maintenance
Section
4. Check the wiring diagram to find fault and repair
5. Adjust humidistat as required or replace
Little or no water extraction
| ****
1. Insufficient air flow
2. Compressor fault
3. Loss of refrigerant gas
| 1. Check all of the above
2. Contact the Factory Service Center
3. Contact the Factory Service Center
Little or no defrost when required
| ****
1. Faulty Timer
2. Faulty bypass timer
| 1. Contact the Factory Service Center
2. Contact the Factory Service Center
CD30
SPARE PARTS LIST
D ESCRIPTION | P ART N UMBER |
---|---|
Product Part Number | 1139500 |
Compressor | 3022132 |
Compressor OH Protector | 3021519 |
Compressor Relay | 3021520 |
By-Pass Valve | 3020811 |
Condenser Coil | 3020740 |
Evaporator Coil | 2013713 |
Filter Dryer | 3020937 |
Fan Motor | 3035752 |
Fan Blade | 3040129 |
Control Humidistat | 3035141 |
Warning Humidistat | 3035141 |
Frostat | 3031516 |
Control Defrost Device | 3031516 |
PCB Timer | 1613700 |
Solenoid Coil | 3030422 |
Humidistat Knob | 3090611 |
Control Knob | – |
Control Knob Cap (black) | 3090612 |
Warning Knob Cap (orange) | 3090645 |
Panel Mounting Plug | 3035997 |
Free Socket | 3035998 |
Feet | 3100758 |
Mains Cable | 3031225 |
Condensate Drain Tube | 3014338 |
Worm Drive Clip | 3086101 |
Cover fixing Clip Nut | 3080507 |
Spare parts available online www.EIPLDIRECT.com
CD30I STAND & CD30I INDICATOR BOX SPARE PARTS LIST
DESCRIPTION| PART
NUMBER
---|---
CD30I Stand| 1139535
Adjustable Tilt Guide| 3050305
CD30I Indicator Box| 1139530
Red Neon Lamp| 3032272
M16 Gland Type| 3032512
Resistor 180K Ohms| 3032883
Female Insert Contact Type| 3033810
Hood| 3033811
Cable Seal| 3033813
Female Contact| 3033815
Green Neon Indicator Lamp| 3034584
Sealing Washer| 3035423
6-way Terminal Block| 3036810
WARNINGS
This appliance can be used by children from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning use of
the application in a safe way and understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children without
supervision.
If the SUPPLY CORD is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified person in order to avoid hazard.
This product contains fluorinated greenhouse gases covered by the Kyoto
Protocol. The refrigeration system is hermetically sealed.
The Global Warming Potential (GWP) of refrigerants used in products
manufactured by Ebac Industrial Products Ltd is as follows
R134a – 1300
R407c – 1610
For type and weight of refrigerant contained in this unit, please refer to the
product data label
Due to the high pressures within the refrigeration circuit, under no
circumstances must direct heat be applied to the evaporator coil in an attempt
to remove the build-up of ice.
No attempt should be made to cut open any part of the refrigeration circuit
due to high pressures and gas involved.
If the unit is switched off at the mains power supply for any reason, the unit
must be allowed to stand at rest for at least three minutes before restarting.
UK Head Office
Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland
County Durham
DL14 9AD
Tel: +44 (0) 1388 664400 Fax: +44 (0) 1388 662590
www.eipl.co.uk
sales@eipl.co.uk
American Sales Office
Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News
Virginia, 23606-2575
USA
Tel: +01 757 873 6800 Fax: +01 757 873 3632
www.ebacusa.com
sales@ebacusa.com
German Sales Office
Ebac Industrial Products Ltd. Gartenfelder Str. 29-37 Gebäude 35
D-13599, Berlin
Germany