Miele PDR 928/528 SI Steam Heated Stainless Steel Professional Vented Dryer Installation Guide
- June 6, 2024
- Miele
Table of Contents
Miele PDR 928/528 SI Steam Heated Stainless Steel Professional Vented Dryer
Installation requirements
The tumble dryer must only be installed and commissioned by Miele Customer Service Department or an authorised dealer
- The tumble dryer must be installed in accordance with all relevant regulations and standards.
- The dryer must only be operated in a room that has sufficient ventilation and which is frost-free.
Electrical connection
The electrical connection must be established by a qualified electrician.
- The electrical connection may only be made to an electrical system provided in accordance with all appropriate local and national legislation, regulations and guidelines. Please also observe the regulations set out by your insurance provider and energy supplier, accident prevention regulations, as well as recognised codes of practice.
- Reliable and safe operation of this tumble dryer is only ensured if it has been connected to the mains electricity supply.
The required supply voltage, power rating and fuse rating can be found on the
data plate on the tumble dryer. Ensure that the supply voltage matches the
voltage quoted on the data plate before establishing the electrical connection
to the tumble dryer.
Connection to a supply voltage other than the one quoted on the data plate can
damage the tumble dryer if the voltage is too high.
- If more than one voltage is specified on the data plate, the tumble dryer can be converted for connection to the relevant input voltage. This conversion must be performed by the Miele Customer Service Department or by an authorised dealer. During the conversion, the wiring instructions given on the wiring diagram must be followed.
The tumble dryer can either be hard-wired or connected using a plug-and socket connection in accordance with IEC 60309-1. For a hard-wired connection, an all-pole isolation device must be available at the installation site.
An isolation device is a switch which ensures a contact opening of more than 3 mm. These include circuit breakers, fuses and contactors (IEC/EN 60947).
If the mains supply cannot be permanently disconnected, the isolation device
(including plug and socket) must be safeguarded against being switched on
either unintentionally or without authorisation.
Tip: We recommend connecting the tumble dryer to the power supply via a plug
and socket so that it is easier to conduct electrical safety checks (e.g.
during maintenance or repair work).
- The tumble dryer must not be connected to devices such as timers which would switch it off automatically.
If local regulations require that a residual current device (RCD) is installed, a type B residual current device (sensitive to universal current) must be used.
Steam connection
The steam connection must only be carried out by a registered installation technician. The information from the data plate, the wiring diagram and the documentation accompanying the appliance must be noted and complied with when connecting steam-heated Miele appliances.
Condensate connection
The condensate separator must be installed so that when the system is not operating, the heater bank is completely emptied. This means that no condensate may remain in the heater bank. The installation of an inverted bucket condensate trap is recommended.
Air intake/exhaust air
The tumble dryer may only be operated when the ducting has been connected properly and the room is sufficiently ventilated.
- Accessory parts may only be fitted when expressly approved by Miele. If other parts are used, warranty, performance and product liability claims will be invalidated
Dimensions
Dimensions quoted in millimetres
Installation
Dimensions quoted in millimetres
EL Electrical connection
D Steam connection
K Condensate connection
AL Exhaust duct
ZL Air intake
PA Connection for equipotential bonding (optional)
XCI XCI Box/Connector Box (optional)
Installation (standard/on concrete plinth)
Dimensions quoted in millimetres
B Drill hole/anchor point
BS Concrete plinth
Technical data
Voltage variants/electrical data
Standard connection
Supply voltage| 1N AC 230 V
Frequency| 50/60 Hz
Power rating| 1.2 kW
Fuse rating (on site)| 10 A
Minimum cross-section for connection cable| 3×1.5 mm²
Cable gland| M20
Steam connection
Steam overpressure | 600–1000 kPa |
---|---|
Boiling point | 165–184 °C |
Mass flow, peak capacity | 60 kg/h |
On-site threaded union for steam (internal thread) | ½” mm |
Length of steam valve connection cable | 500 mm |
Steam valve, dirt filter and steam shut-off valve must be fitted by the
customer on site.
The steam valve must be fitted in the direct vicinity of the steam connection.
Condensate connection
On-site threaded union (internal thread) | ½” mm |
---|
Shut-off equipment and condensate trap must be fitted by the customer on site.
Exhaust air
Maximum nominal volume flow rate in extraction mode (PDR 9xx only) | 1000 m³/h |
---|---|
Maximum nominal volume flow rate (PDR 5xx only) | 1100 m³/h |
Maximum permitted pressure loss | 510 Pa |
Connector on machine side (external diameter) | 150 mm |
Connection pipe provided on site (internal diameter) | 150 mm |
Maximum exhaust air temperature | 80 °C |
As relative humidity inside the exhaust ducting can be as high as 100 %, suitable measures must be taken to prevent a backflow of condensate into the machine.
Air intake
Standard connection: air intake from installation site
Recommended free air intake cross-section into the room:
(equivalent to 3 times the exhaust air cross-section of a machine). 531 cm²
There must be sufficient air intake to the installation site to match the air
outlet volume.
Alternative connection: air intake connection directly from outdoors
Connection sleeve on machine side (internal diameter)| 161 mm
Connection pipe provided on site (external diameter)| 160 mm
Removing the protective cover exposes live parts. For safety reasons, a pipe must be installed from the tumble dryer’s central fresh air intake (over a minimum length of 900 mm) and secured with 2 screws.
Machine data
Machine width, total | 1206 mm |
---|---|
Machine height, total | 1640 mm |
Machine depth, total | 1019 mm |
Niche width | 1550 mm |
Recommended wall spacing (up to the front edge of the machine) | 1600 mm |
Minimum wall spacing (up to the back edge of the lid) | 500 mm |
Packaging width | 1390 mm |
Packaging height | 1766 mm |
Packaging depth | 1108 mm |
Maximum gross volume | 2719.9 l |
Maximum gross weight | 295.9 kg |
Maximum net weight | 281.3 kg |
Max. floor load in operation | 3171 N |
Diameter of exhaust duct | 150 mm |
Drum diameter | 1100 mm |
Diameter of drum opening | 520 mm |
Drum depth | 561 mm |
Drum volume | 500 l |
Diameter of door opening | 520 mm |
Maximum door opening angle | 180° |
Emission sound pressure level | 60 dB(A) re 20 µPa |
Sound power level | 70 |
Average heat dissipation rate into the room | 6.1 MJ/h |
Permissible ambient temperature range | 2–40 °C |
Fixing options
Fixing without plinth
Quantity | Screw size | |
---|---|---|
Tensioning strips | 2 | |
Wood screws DIN 571 (Ø × length) | 2 | 6×40 mm |
Plugs (Ø × length) | 2 | 10×50 mm |
Fixing the appliance in place is absolutely essential.
Fastenings for floating screed must be supplied by the customer on site.
Fixing to concrete plinth
Quantity | Screw size | |
---|---|---|
Tensioning strips | 2 | |
Wood screws DIN 571 (Ø × length) | 2 | 6×40 mm |
Plugs (Ø × length) | 2 | 10×50 mm |
If the tumble dryer is being fixed to a concrete plinth on site, fixing in
place is absolutely essential.
Fastenings for floating screed must be supplied by the customer on site.
Options/Accessories
Concrete base (on site)
Minimum width | 1200 mm |
---|---|
Recommended height | 100 mm |
Minimum height | 50 mm |
Minimum depth | 1100 mm |
The quality of the concrete and its strength must be assessed according to the machine load. The on-site concrete plinth must be fixed adequately to the floor.
Miele & Cie. KG
Carl-Miele-Straße 29
33332 Gütersloh
Germany
Telefon: 05241 89-0
Telefax: 05241 89-2090
Internet: www.miele.com/professional
Documents / Resources
|
Miele PDR 928/528 SI Steam Heated Stainless Steel Professional Vented
Dryer
[pdf] Installation Guide
PDR 928 528 SI Plan Commercial Tumble Dryers, PDR 928 528 SI Steam Heated
Stainless Steel Professional Vented Dryer, PDR 928 528 SI, Steam Heated
Stainless Steel Professional Vented Dryer
---|---