EMERSON Wall-Mounted CO2 Sensor Installation Guide

June 6, 2024
Emerson

EMERSON Wall-Mounted CO2 Sensor Installation Guide
EMERSON Wall-Mounted CO2 Sensor

Emerson specs a CO2 Sensor (P/N 210-2000) to be used in building control and anti-sweat control applications using the Emerson input boards. The CO2 sensor measures CO2, room temperature, and provides analog outputs.

The 210-2000 CO2 sensor is a non-dispersive infrared analyzer designed for measuring environmental CO2 concentration in ventilation systems and indoor spaces. Its measurement range of 0-2000 or 0-5000 ppm covers the range required to monitor compliance with ASHRAE and other ventilation efficiency standards.

The LCD display is available to provide local indication of CO2 concentration and facilitate the setup and calibration process. An adjustable setpoint relay is available for direct control and alarm applications. The microprocessor- based digital electronics and unique self-calibration algorithm improves long- term stability and accuracy.

Specifications

OPERATING ENVIRONMENT

Input Power| Class 2 (20 to 30Vdc), 24Vac 50 to 60 Hz
Analog Output| 0 to 5V, Selectable 4 to 20mA, 0 to 10V
Operating Temp. Range| (32°F to 122°F) 0°C to 50°C
Operating Humidity Range| 0 to 95% (non-condensing)
Housing Material| High-impact ABS plastic
Terminal Block Torque| 0.5 to 0.6 N-m (0.37 to 0.44 in-lbf )
IP Rating| IP 30
CO2 TRANSMITTER
Sensor Type| Non-dispersive infrared (NDIR), diffusion sampling
Output Range| 0 to 2000/5000 ppm (selectable)
Accuracy| ±30 ppm ±3% of measured value
Repeatability| ±20 ppm ±1% of measured value
Response Time| <60 seconds for 90% step change
DISPLAY MODELS


LCD

| 52mm (2.05 in), segmented with 3 buttons

Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable Timeout override: Display timeout**

Lockout override: Touchscreen/button lockout**

OVERRIDE
Override Button| Display models feature momentary-to-ground override button
WIRING TERMINALS
Terminal Blocks| Screw terminals, 18-24 AWG
Screw Terminal Torque| 0.2 N-m (2.0 in-lbF) max.
COMPLICANCE INFORMATION
UL 916, European conformance CE: EN61000-6-2,

Agency Approvals                          EN61000-6-3, EN61000 Series – industrial immunity, EN 61326-1

FCC Part 15 Class B, REACH, RoHS, RCM (Australia), ICES-003 (Canada)

****Icons

Installation

  1. Remove the cover by pressing the tab on the bottom of the sensor while pulling outward on the bottom edge of the cover.

  2. Position the sensor vertically on the wall, 4 feet (1.5 m) above the floor. Place so that the “Install This End Up” statement on the board is in the upper right corner.
    Installation Instruction

  3. Mount the backplate onto the wall using the screws provided.

  4. Wire the backplate. Connect the wires to the screw terminals. Do not over-tighten the screws.
    Installation Instruction

  5. With the sensor base fully installed, align the top cover to mounting tabs on top of the sensor base. Swing the cover downward until it latches at the bottom.

  6. Installed the locking screw to secure cover in a closed position.

  7. The 400 ppm baseline calibration allows the sensor to be set at 400 ppm. Push and hold the calibrator button for 3 to 5 seconds. The LED will flash green. Once the push button is released, the calibration is complete and the LED is switched off.
    Installation Instruction

Mounting

  1. Mount the backplate on the wall in an appropriate location with the “Install This End Up” label positioned in the upper right corner.
  2. Wire the unit as shown (see the Wiring section on page 5).
  3. Attach the front plate.

Wiring

  1. Use Belden #8771 shielded three-conductor cable or equivalent.
  2. Connect the RED, BLACK, and WHITE wires to the screw terminals of the CO2 sensor’s connector as shown in the image below.
  3. For TEMP OUTPUT wiring connect the BLACK wires to the 0V terminal of the input board. Connect the WHITE wire to the SIG terminal of the input board. RED wire not used for TEMP OUTPUT; clip and insulate. Connect the SHIELD wire to chassis ground near the MultiFlex board.
  4. For C02 OUTPUT wiring connect the BLACK wires to the 0V terminal of the input board. Connect the WHITE wire to the SIG terminal of the input board. Connect the RED wire as described in Step 5. Connect the SHIELD wire to chassis ground near the MultiFlex board.
  5. Connect the RED wire to one side of the 24VAC power output of the P/N 640-0039 Class 2 isolated non-center tapped transformer. Connect the other side of 24VAC output from transformer to the MultiFlex 0V input terminal used for CO2 OUTPUT signal. Do not use the MultiFlex or 16AI power transformer to power the C02 sensor.
  6. Locate the input dip switch for the sensor point, and set to the OFF position (LEFT for MultiFlex, DOWN for 16AI). Refer to the input board’s user manual for locations of the input dip switches.

Wiring Diagram

Table

Operations

Emerson wall-mounted humidity sensors measure the levels of RH and temperature (if equipped) in the air inside of a room. To maintain accurate functionality, keep all pickup vents clear and free of dust, debris, etc.

Dimensions

Dimensions

LCD Display

Button functions:

LCD Display

Display Icons:

The main screen displays a sensor values for CO2, temperature and Celsius/Fahrenheit.

Display Icons

Document Part # 026-4858 Rev 0 Page 6 of 7
©
2021 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates

This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
Join Emerson Technical Support on Facebook.http://on.fb.me/WUQRnt
For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com

The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user. ©2021 Emerson is a trademark of Emerson Electric Co.