DAIKIN IM 1316 Outside Airflow Sensor Kit Instruction Manual
- June 6, 2024
- Daikin
Table of Contents
DAIKIN IM 1316 Outside Airflow Sensor Kit Instruction Manual
Included Parts
- Outside Airflow Monitor/Transmitter
- (2) Sensor Probes
- (4) Probe Brackets
- (1) Top and (1) Bottom Panel
- (1) Left-Side Panel and (1) Right-Side Panel
- Conduit Bushing
- 5-pin Male Molex plug with (1 each) 12” Red, Black, Green wires (not shown)
- 3″ long black wire (not shown)
- (38) 3/8″ #10 self-tapping screws
- (6) Cable Ties (not shown)
- (6) Wire Ties (not shown)
Figure 1: Kit Parts Assembly
Installation
All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run any of this device’s wiring in the same conduit as other AC power wiring. Tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. If you are experiencing any of these difficulties, please contact your Daikin representative.
-
Remove all components from the packaging and confirm all pieces have been received.
-
Assemble the sensor enclosure as show in Figure 1.
Note: Use field-supplied screws to attach sensor probe brackets to sensor probes. -
Attach sensor assembly to filter inlet frame as shown in Figure 2.
Figure 2 : Attach Assembled Outside Airflow Kit to Filter Inlet Frame
-
Attach sensor wires from Monitor/Transmitter to sensor probe tubes as shown in Figure 3.
Figure 3 : Attach and Route Wires from Sensor Probes Brackets to Monitor/Transmitter -
Route wiring harness from mating CFM/IHS molex plug to the monitor/transmitter, (Figure 4).
Figure 4 : Route Male Plug Wire Harness Wires to Monitor/Transmitter
-
Connect the wires from the wire harness to the monitor/transmitter terminals as follows: Refer to Figure 5
- Green wire (CFM11-GN) to the POWER 24VAC IN : L1 connection
- Black wire (CFM12-BK) to the POWER 24VAC IN : L2 connection
- Red wire (CFM13-RD) to the OUTPUT : 1 connection
- Install the 3″ black wire (CFMJP) between the POWER 24VAC IN: L2 and OUTPUT: COM connections
Figure 5: Connect Wire Harness Wires to Monitor/Transmitter Terminals
Outside Airflow Monitor/Transmitter Configuration
- Set the power switch to ON.
- Set transmitter SW1 to VDC
- Set transmitter to display in ACFM by selecting SETUP > ANALOG OUT > *AO1 UM=AFPM Change to AO1 UM = ACFM
Figure 6: Monitor/Transmitter Board
Programming
To enable use of this sensor the following configuration point must be changed. Changes can be made through the local user interface or through the Service Tools software for Microtech® Unit Controllers program on a connected PC. For information on how to use the ServiceTools software, refer to OM 732. The local user interface menu path is shown below.
- To enable Outdoor Air Flow measuring go to Service > Serv-AnaIn > Serv-AnaIn-Config > CFgAnIn16 and change the value from None to OAFLOW. Then go to SET > Set-SensorInstall > OAFlowSens and confirm that it is set to ‘Inst’.
If using the ServiceTools software, change the unit configuration as follows:
- To enable Space Temperature sensing, go to the ‘Configuration’ menu and under the ‘Inputs’ drop down change ‘Analog Input 16’ to ‘Outside Air Flow’. Confirm that under the ‘Sensor Installation’ drop down, ‘Outside Air Flow’ is ‘Installed’.
Click the Save button after making changes so they take effect. ServiceTools prompts you to save if you are switching to another screen without saving
DAIKIN
Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin equipment,
its care should be a high priority. For training information on all Daikin
HVAC products, please visit us at www.DaikinApplied.com and click on Training,
or call 540-248-9646 and ask for the
Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of
sale, including Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800 37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432 1342.
This document contains the most current product information as of this
printing. For the most up-to-date product information, please go to
www.DaikinApplied.com.