EM3500FM 280kg Electromagnetic Lock
Installation Manual
Introduction
The EM3500FM is a 280kg flush mount single magnetic lock. .
The Lock Status Switch (LSS) indicates if the lock is powered and the magnetic bond is active using a Hall Effect crystal. The output is an onboard relay, the output requires the lock to be powered.
Installation Tips
Armature Plate must remain flexible – the armature plate must be remained
movable to allow surface alignment with the magnet face. The magnetic lock
will lose holding force without this floating alignment. Do not trim the
rubber washer mounted on the head of the armature center bolt. Trimming rubber
washers will adversely affect the release of the armature plate from the
magnetic lock.
Important Safety Requirements
Apply thread-locker glue (e.g. Loctite) to the thread of the Armature-Plate-
Fixing Screw (Allen-Screw) to prevent from becoming loose. Locks should be
inspected at regular intervals to ascertain the safety functionality. The
supplied Allen screws cater for maximum door thickness of 45mm.
Wiring and Power input requirements:
12 VDC 0.42 A max
24 VDC 0.21 A max
The (+) lead of the Power Source is connected to RED lead of the PCB and the
(-) lead is connected to BLACK lead of the PCB. The operating switch or
controlling contacts must be installed between the power source and the
Magnetic Lock to reduce operating time of the magnetic lock to a minimum.
Dip switch settings:
Switch positions 1 and 2 to ON and switch position 3 to OFF for 12 VDC
operation.
Switch position 3 to ON and switch positions 1 and 2 to OFF for 24 VDC
operation
Default operating voltage factory set to 24 volts.
Trouble Shooting
Problem | Possible Cause | Solution |
---|---|---|
Door will not lock | No DC voltage to lock. Loose wire on terminal strip. |
Check power supply and wiring to magnetic lock.
Reduced holding force| Bad physical contact between armature plate and face of
magnet.
Incorrect voltage jumper setting.| Ensure mating surfaces are clean and in
proper alignment and the armature plate floats freely.
Check magnetic lock for low voltage or wrong voltage setting.
Delay in door release| Circuit switch is not between magnetic lock and power
source. Secondary diode installed across magnetic lock.| Re-wire circuit
switch between magnetic lock and power source.
Remove any installed diode. Voltage spike protection is on the PCB.
Maintenance
Contacting surfaces of the electromagnet and armature plate must be kept free of contaminating materials. Surfaces should be cleaned periodically with a non-abrasive cleaner. Do not spray the electromagnet or armature plate surface with any lacquer chemical, this will create problems with the release of the magnetic lock and armature plates.