MITSUBISHI ELECTRIC PURY-P200YNW-A2 VRF Heat Recovery User Guide
- June 6, 2024
- Mitsubishi Electric
Table of Contents
City Mult VRF
Quick Reference Guide 2024
R410A R2 Series
Heat Recovery (R2) Series
The following sections provides detail on the Piping Restrictions and Pipe Selections:
RANGE | Standard Efficiency R2 Series | Comprising |
---|---|---|
8 HP | PURY-P200YNW-A2 | |
10 HP | PURY-P250YNW-A2 | |
12 HP | PURY-P300YNW-A2 | |
14 HP | PURY-P350YNW-A2 | |
16 HP | PURY-P400YNW-A2 | |
18 HP | PURY-P450YNW-A2 | |
20 HP | PURY-P500YNW-A2 | |
22 HP | PURY-P550YNW-A2 | |
16 HP | PURY-P400YSNW-A2 | PURY-P200YNW-A2 PURY-P200YNW-A2 |
18 HP | PURY-P450YSNW-A2 | PURY-P200YNW-A2 PURY-P250YNW-A2 |
20 HP | PURY-P500YSNW-A2 | PURY-P250YNW-A2 PURY-P250YNW-A2 |
22 HP | PURY-P550YSNW-A2 | PURY-P250YNW-A2 PURY-P300YNW-A2 |
24 HP | PURY-P600YSNW-A2 | PURY-P300YNW-A2 PURY-P300YNW-A2 |
26 HP | PURY-P650YSNW-A2 | PURY-P300YNW-A2 PURY-P350YNW-A2 |
28 HP | PURY-P700YSNW-A2 | PURY-P350YNW-A2 PURY-P350YNW-A2 |
30 HP | PURY-P750YSNW-A2 | PURY-P350YNW-A2 PURY-P400YNW-A2 |
32 HP | PURY-P800YSNW-A2 | PURY-P400YNW-A2 PURY-P400YNW-A2 |
34 HP | PURY-P850YSNW-A2 | PURY-P400YNW-A2 PURY-P450YNW-A2 |
36 HP | PURY-P900YSNW-A2 | PURY-P450YNW-A2 PURY-P450YNW-A2 |
38 HP | PURY-P950YSNW-A2 | PURY-P450YNW-A2 PURY-P500YNW-A2 |
40 HP | PURY-P1000YSNW-A2 | PURY-P500YNW-A2 PURY-P500YNW-A2 |
42 HP | PURY-P1050YSNW-A2 | PURY-P500YNW-A2 PURY-P550YNW-A2 |
44 HP | PURY-P1100YSNW-A2 | PURY-P550YNW-A2 PURY-P550YNW-A2 |
High Efficiency R2 Series | Comprising | |
--- | --- | |
PURY-EP200YNW-A2 | ||
PURY-EP250YNW-A2 | ||
PURY-EP300YNW-A2 | ||
PURY-EP350YNW-A2 | ||
PURY-EP400YNW-A2 | ||
PURY-EP450YNW-A2 | ||
PURY-EP500YNW-A2 | ||
PURY-EP550YNW-A2 | ||
PURY-EP400YSNW- A2 | PURY-EP200YNW-A2 PURY-EP200YNW-A2 | |
PURY-EP450YSNW- A2 | PURY-EP200YNW-A2 PURY-EP250YNW-A2 | |
PURY-EP500YSNW- A2 | PURY-EP250YNW-A2 PURY-EP250YNW-A2 | |
PURY-EP550YSNW- A2 | PURY-EP250YNW-A2 PURY-EP300YNW-A2 | |
PURY-EP600YSNW- A2 | PURY-EP300YNW-A2 PURY-EP300YNW-A2 | |
PURY-EP650YSNW- A2 | PURY-EP300YNW-A2 PURY-EP350YNW-A2 | |
PURY-EP700YSNW- A2 | PURY-EP350YNW-A2 PURY-EP350YNW-A2 | |
PURY-EP750YSNW- A2 | PURY-EP350YNW-A2 PURY-EP400YNW-A2 | |
PURY-EP800YSNW- A2 | PURY-EP400YNW-A2 PURY-EP400YNW-A2 | |
PURY-EP850YSNW- A2 | PURY-EP400YNW-A2 PURY-EP450YNW-A2 | |
PURY-EP900YSNW- A2 | PURY-EP450YNW-A2 PURY-EP450YNW-A2 | |
PURY-EP950YSNW- A2 | PURY-EP450YNW-A2 PURY-EP500YNW-A2 | |
PURY-EP1000YSNW- A2 | PURY-EP500YNW-A2 PURY-EP500YNW-A2 | |
PURY-EP1050YSNW- A2 | PURY-EP500YNW-A2 PURY-EP550YNW-A2 | |
PURY-EP1100YSNW- A2 | PURY-EP550YNW-A2 PURY-EP550YNW-A2 |
PURY- (E)P200-550YNW-A2 If the CMY-R160-J1 joint is not used for P/M100-140, the capacity should be multiplied by the correlation factor 0.97.
Piping Length
Item| Pipe Section| Max Length
Total piping length| A+B+a+b+c+d| See Chart 1
Furthest piping length| A+B+d| 165 m
Length between OU & BC| A| 110 m (See Chart 1 on Page 8)
Length between furthest IU & BC| B+d| 60 m 1 (40m 2)
Height between OU & IU (OU above IU)| H| 50 m 3
Height between indoor & outdoor units (OU below IU)| H`| 40 m 4
Height between IU and BC| h1| 15 m 5
Height between IU and IU| h2| 30 m 6
- See chart 2 for maximum distance based on height difference (Page 8).
- When P200 or P250 indoor units are connected to the system, the maximum distance from the BC controller to the farthest indoor unit is 40 m.
- 90 m is available depending on the model and installation conditions. Please refer to design tool schematic & ‘Height Check’ document.
- 60 m is available depending on the model and installation conditions. Please refer to design tool schematic & ‘Height Check’ document.
- Distance of Indoor sized P200, P250 from BC must be less than 10 m.
- Distance of Indoor sized P200, P250 from BC must be less than 20 m.
PURY- (E)P400-1100YSNW-A2
Outdoor Twinning Kits:
Outdoor Unit YSNW | Twinning Kit |
---|---|
P400 ~ P650 | CMY-R100VBK4 |
P700 ~ P1100 | CMY-R200VBK4 |
When outdoor units equal to or larger than size P950, please ensure to use BC
controller CMB-P1016V-KA1.
If the CMY-R160-J1 Joint is not used for P/M 100-140, the capacity should be
multiplied by a correction factor 0.97.
Piping Length
Item| Pipe Section| Max Length
Total piping length| I+J+A+B+C+D+ E+
a+b+c+d+e+f| See Chart 1
Furthest piping length| I(J)+A+C+E+f| 165 m
Length between OU & BC| I(J)+A| 110 m (See Chart 1
on Page 8)
Length between furthest IU & Main BC| B+d| 60 m 1 (40m 2)
Length between furthest IU & Main BC via Sub-BC| C+E+f| 60 (90) m 7
Height between OU & IU (OU above IU)| H| 50 m 3
Height between indoor & outdoor units (OU below IU)| H`| 40 m 4
Height between IU and BC| h1| 15 m 5
Height between IU and IU| h2| 30 m 6
Height between BC (Main or Sub) and BC (Sub)| h3| 15 m (10 m 8)
Distance between Main unit and Sub unit (Outdoor)| I+J| 5 m
Height between Main unit and Sub unit (Outdoor)| h4| 0.1 m
-
See chart 2 for maximum distance based on height difference (Page 8).
-
When P200 or P250 indoor units are connected to the system, the maximum distance from the BC controller to the farthest indoor unit is 40 m.
-
90 m is available depending on the model and installation conditions. Please refer to design tool schematic & ‘Height Check’ document.
-
60 m is available depending on the model and installation conditions. Please refer to design tool schematic & ‘Height Check’ document.
-
Distance of Indoor sized P200, P250 from BC must be less than 10 m.
-
Distance of Indoor sized P200, P250 from BC must be less than 20 m.
-
If height difference between BC Controller and indoor unit is zero, then 90 m is possible (Refer to Chart 3 On page 9). Increase the size of the high-pressure pipe and the liquid pipe between the main BC and sub BC by one size.
When using P/M32, P/M40, P/M50, P/M100, or P/M125 model of indoor units, increase the size of the liquid branch pipe between the Sub BC and indoor unit by one size. When using indoor models P/M140 or larger and if height difference between BC Controller and indoor unit is zero, then the restrictions of 60 m cannot be exceeded. -
When using 2 Sub BC controllers, max. height ‘’h3’’ is 10m.
Outdoor Unit – BC Controller (Pipe A) Outdoor Unit – BC Controller (Pipe A)Outdoor Unit| Liquid – mm (in)| Gas – mm (in)
P200| 15.88 (5/8”)| 19.05 (3/4”)
P250-P300| 19.05 (3/4”)| 22.20 (7/8”)
P350| 19.05 (3/4”)| 28.58 (1-1/8”)
P400-P600| 22.20 (7/8”) *9| 28.58 (1-1/8”)
P650| 28.58 (1-1/8”)| 28.58 (1-1/8”)
P700-P800| 28.58 (1-1/8”)| 34.93 (1-3/8”)
P850-P950| 28.58 (1-1/8”)| 41.28 (1-5/8”)
P1000| 28.58 (1-1/8”)| 41.28 (1-5/8”)
P1000| 28.58 (1-1/8”)| 41.28 (1-5/8”)
P1050-P1100| 34.93 (1-3/8”)| 41.28 (1-5/8”) -
For P550 Y(S)NW & P600 Y(S)NW OU when the high-pressure piping length exceeds 65 m, use ø22.2 (ø7/8) pipe until 65 m and then after use ø28.58 (ø1-1/8).
BC Controller – Branch (Pipe B)
Outdoor Unit – BC Controller (Pipe B) BC to Branch Joint
Total Capacity of Indoor Units| Liquid – mm (in)| Gas – mm (in)
≤P/M140| 9.52 (3/8”)| 15.88 (5/8”)
P/M141-P/M200| 9.52 (3/8”)| 19.05 (3/4″)
P/M201-P/M250| 9.52 (3/8”)| 22.20 (7/8″)
BC Controller – BC Controller (Pipe C, D, E)
BC Controller – BC Controller (Pipe C, D, E)
Total Capacity of Indoor Units| Liquid – mm (in)| High Pressure
Gas HP– mm (in)| Low Pressure Gas LP – mm (in)
≤P/M200| 9.52 (3/8”)| 15.88 (5/8”)| 19.05 (3/4”)
P/M201 ~ P/M300| 9.52 (3/8”)| 19.05 (3/4”)| 22.20 (7/8”)
P/M301 ~ P/M350| 12.70 (1/2”)| 19.05 (3/4”)| 28.58 (1-1/8”)
P/M351 ~ P/M400| 12.70 (1/2”)| 22.20 (7/8”)| 28.58 (1-1/8”)
P/M401 ~ P/M600| 15.88 (5/8”)| 22.20 (7/8”)| 28.58 (1-1/8”)
P/M601 ~ P/M650| 15.88 (5/8”)| 28.58 (1-1/8”)| 28.58 (1-1/8”)
P/M651 ~ P/M800| 19.05 (3/4”)| 28.58 (1-1/8”)| 34.93 (1-3/8”)
P/M801 ~ P/M1000| 19.05 (3/4”)| 28.58 (1-1/8”)| 41.28 (1-5/8”)
P/M1001| 19.05 (3/4”)| 34.93 (1-3/8”)| 41.28 (1-5/8”)
BC Controller or Branch –Indoor Unit (Pipe a, b, c, d, e, f)
BC Controller or Branch – Indoor Unit (Pipe a, b, c, d, e, f )
Total Capacity of Indoor Units| Liquid – mm (in)| Gas – mm (in)
P10 ~ P50, M20 to M50| 6.35 (1/4”)| 12.70 (1/2”)
P63 ~ P140, M63 to M140| 9.52 (3/8”)| 15.88 (5/8”)
P200| 9.52 (3/8”)| 19.05 (3/4”)
P250| 9.52 (3/8”)| 22.70 (7/8”)
Outdoor Unit – Outdoor Unit (Pipe I,J)
Outdoor Unit – Outdoor Unit (Pipe I,J)
Outdoor Unit| Liquid – mm (in)| Gas – mm (in)
P200| 15.88 (5/8”)| 19.05 (3/4”)
P250-P300| 19.05 (3/4”)| 22.20 (7/8”)
P350| 19.05 (3/4”)| 28.58 (1-1/8”)
P400-P550| 22.20 (7/8”)| 28.58 (1-1/8”)
Chart 1 Chart 2
Chart 3
*7 Increase the size of the high-pressure pipe and the liquid pipe between the main BC and sub BC by one size.
When using P/M32, P/M40, P/M50, P/M100, or P/M125 model of indoor units,
increase the size of the liquid branch pipe between the sub BC and indoor unit
by one size.
Corporate Sales
Tel: 0870 3000 070| Birmingham
Tel: 0121 329 1970| Bristol
Tel: 01454 202050
---|---|---
London South
Tel: 01737 387170| Manchester
Tel: 0161 866 6060| Scotland
Tel: 01506 444960
Wakefield
Tel: 01924 241120| Ireland
Tel: +353 (0)1 419 8800| London North & East Anglia
Tel: 01707 282480
MELSmart Technical Services: 0161 866 6089
Technical Help – option 1
Warranty – option 3
Training – option 6 followed by option 1
email: air.conditioning@meuk.mee.com
website:
airconditioning.mitsubishielectric.co.uk
website:
recycling.mitsubishielectric.co.uk
| @meuk_les
@green gateway| | mitsubishielectricuk_les
---|---|---|---
| Mitsubishi Electric Living
Environmential Systams UK| | mitsubishielectric2
| Mitsubishi Electrnic
Cooling and Heating UK| |
thehubmitsubishielectric.co.uk
UNITED KINGDOM Mitsubishi Electric Europe Living Environmental Systems
Division
Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. Telephone:
01707 282880 Fax: 01707 278881
IRELAND Mitsubishi Electric Europe
Westgate Business Park, Ballymount, Dublin 24, Ireland. Telephone: (01) 419
8800 Fax: (01) 419 8890 International code: (003531)
Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi
Glectric Europe 2022. Mitsubishi and Mitsubishi Gectnic are trademarks of
Mitsubishi Electric Europe B.V. The company reserves the right to make any
variation in technical specification to the equipment described, or to
withdraw or replace products without prior Notification or public
announcement. Mitsubishi Electric is constantly developing and improving its
products. All descriptions, illustrations, drawings and specifications in this
publication present only general particulars and shall not form part of any
contract. All goods are supplied subject to the Company’s General Conditions
of Sale, a copy of which is available on request. Third-party product and
brand names may be trademarks or registered trademarks of their respective
owners.
Note: The fuse rating is for guidance only. Please refer to the relevant
databook for detailed specification. It is the responsibility of a qualified
electrician/electrical engineer to select the correct cable size and fuse
rating based on current regulation and site specific conditions. Mitsubishi
Electric’s air conditioning equipment and heat pump systems Contain a
fluorinated greenhouse gas, R410A (GWP:2088), R32 (GWP-:675), R407C
(GWP:1774), R134a (GWP: 1430), R513A (GWP-631), R454B (GWP-466), R1234ze
(GWP:7) or R1234yf (GWP:4). ‘These GWP values are based on Regulation (EU) No
517/2014 from IPCC 4th edition. in case of Regulation (EU) No.626/2011 from
IPCC 3rd edition, these are as folows. R410A (GWP:1975), R32 (GWP:550), R407C
(GWP: 1650) or R134a (GWP: 1300).
Effective as of January 2022