LENNOX Gas Changeover Kit Instruction Manual
- June 5, 2024
- Lennox
Table of Contents
LENNOX Gas Changeover Kit
GAS UNITS KITS & ACCESSORIES
WARNING
- This conversion kit is to be installed by a licensed professional service technician (or equivalent) or other qualified agency in accordance with the manufacturer’s instructions, all codes and requirements of the authority having jurisdiction in the USA, and the requirements of the CSA-B149 installation codes in Canada.
- If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
- The qualified agency performing this work assumes responsibility for this conversion.
- There are circumstances in which odorant used with
- LP/propane gas can lose its scent. In case of a leak,
- LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.
Installation
- Set the thermostat to the lowest setting. Shut off the gas supply to the furnace, then turn off the electrica power at the unit disconnect switch.
- Remove the access panel. Move the automatic gas valve switch to OFF. See figure 8. Disconnect the gas supply from the gas valve.
- Disconnect the wiring harness at the gas valve.
- Remove the screw that secures the burner box front cover and remove front cover. See figure 4 or 5.
- Remove the four manifold securing screws. Remove the manifold/gas valve assembly. Replace the main burner orifices with the provided orifices. Torque to approximately 35 in-lbs. See figure 4 or 5.
- NOTE – LP/Propane orifices will be labeled (LP .034).
- Gas Valve Conversion
- Remove both high fire and low fire springs from the gas valve.
- Replace both high fire and low fire springs with the provided LP springs color-coded white.
- Install the high fire adjustment screw and adjust approximately 12 turns.
- Install the low fire adjustment screw and adjust approximately 8 turns.
- Install both regulator screw covers.
- NOTE – Step 6 is for gas conversion only. Manifold pressure must be checked as shown on page 4 “Measuring and Adjusting Manifold Pressure”.
- EL280(X) and SL280(X) NOX units being converted from natural to LP /Propane.
- Remove the burner box assembly from the vestibule panel.
- Remove the screws which secures each of the NOx inserts to the clamshell. Remove the NOx inserts and reinstall the screws.
- Re-install the burner box assembly.
- Re-install the manifold/valve assembly.
- Thread provided fitting to gas valve inlet until hand tight. Using properly sized wrench, tighten fitting 2 to 3 full turns being careful to position the side port to allow clearance for the pressure switch and harness.
- Thread the gas supply to the fitting until hand tight. A field provided coupling may be needed. Using properly sized wrench to support fitting, tighten supply line into fitting 2 to 3 full turns to achieve leak free joint.
- Thread pressure switch (S145) to fitting 2 to 3 turns past hand tight, then wire as shown in figure 6.
- Restore the electrical power to the unit.
- Inspect all sides of assembly. Turn on gas supply. Immediately check the entire fitting surface and assembly joints for gas leaks. Affix nameplate conversion sticker next to unit nameplate.
- Complete the information required on the gas converter sticker: date, name, and address. Affix sticker to the exterior of the unit in a visible area.
- Follow the steps given in the start-up and adjustment section.
Start-Up & Adjustment
BEFORE PLACING THE UNIT INTO OPERATION –
Smell all around the appliance area for gas. Be sure to smell next to the
floor because LP/Propane gas is heavier than air and will settle on the floor.
Use only your hand to move the gas control switch. Never use tools. If the
switch will not move by hand, do not try to repair it. Force or attempted
repair may result in a fire or explosion.
Placing the Unit into Operation
Follow the lighting instructions provided on the unit. If lighting instructions are not available, refer to the following section. Units are equipped with a two-stage integrated ignition system. The integrated ignition control automatically lights the burners each time the thermostat calls for heat.
-
STOP! Read the safety information at the beginning
of this section. -
Set the thermostat to its lowest setting.
-
Turn off all electrical power to the furnace.
-
Do not try to light the burners by hand.
-
Remove the unit access panel.
-
Move the switch on the gas valve to OFF. Do not force the switch. Wait five (5) minutes for any gas to clear out. If you then smell gas,
-
STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas to the next step.
-
Move the switch on the gas valve to ON.
-
Replace the unit compartment access panel.
-
Turn on all electrical power to the unit.
-
Set the thermostat to desired setting.
-
If the furnace will not operate, see section E- “Turning Gas Off to the Unit” and call the gas supplier.
Gas Pressure Measurement
A – Supply Pressure Measurement
An inlet pressure post located on the gas valve provides access to the supply
pressure. See figure 8. Back out the 3/32 hex screw one turn, connect a piece
of 5/16 tubing and connect to a manometer to measure supply pressure. Check
the unit on high fire. On multiple unit installations, check the unit
separately and with the other units operating. See table 1 for supply line
pressure. Following the supply pressure check, turn off unit, remove the
manometer and tighten post hex screw.
B – Measuring & Adjusting the Manifold Pressure
NOTE – Pressure test adapter kit (10L34) is available from Lennox to
facilitate manifold pressure measurement. All units – A manifold pressure post
located on the gas valve provides access to the manifold pressure. See figure
8. Back out the 3/32 hex screw one turn, connect a piece of 5/16 tubing and
connect to a manometer to measure manifold pressure. ML296/EL296/95AF2 – To
correctly measure manifold pressure, the differential pressure between the
positive gas manifold and the negative burner box must be considered. The
furnace should operate at least 5 minutes before checking manifold pressure
- Connect the test gauge positive side “+“ to the manifold pressure post on gas valve as noted above.
- ML296/EL296/95AF2 only – Tee into the gas valve regulator vent hose and connect to test gauge negative “-”.
- All units – Ignite unit on low fire and let run for 5 minutes to allow for steady-state conditions.
- After allowing the unit to stabilize for 5 minutes, record low fire manifold pressure and compare to the value given in table 1. If necessary, make adjustments. Figure 8 shows the location of low fire adjustment screw
- Repeat on high fire and compare to the value given in table 1. If necessary, make adjustments. the location of the high fire adjustment screw.
- Shut the unit off and remove the manometer as soon as an accurate reading has been obtained. Take care to replace the pressure tap plug.
- Start unit and perform leak check. Seal leaks if found.
Manifold Pressure in.wg.| Gas Line Pressure in.wg.
---|---
low fire| high fire| minimum| maximum
4.5| 10.0| 11.0| 13.0
C – Gas Flow (Approximate)
The furnace should operate at least 5 minutes before checking gas flow. Determine the time in seconds for two revolutions of gas through the meter. (Two revolutions assure a more accurate time.) Divide by two and compare to time in table 2. If manifold pressure matches table 1 and rate is incorrect, check gas orifices for proper size and restriction. Remove temporary gas meter if installed.
D- Proper Combustion
The furnace should operate minimum 15 minutes with correct manifold pressure
and gas flow rate before checking combustion. Take combustion sample beyond
the flue outlet. See tables 3 and 4 .
NOTE – Shut unit off and remove manometer as soon as supply line
pressure, manifold pressure and combustion sample have been
GAS METER CLOCKING CHART
Unit Capacity
| Seconds for One Revolution
LP/Propane
1 cu ft Dial| 2 cu ft Dia/
-045| 200| 400
-070| 136| 272
-090| 102| 204
-110| 82| 164
-135| 68| 136
2500 btu/cu ft
Upflow/Horizonta l
Unit Capacity
| CO2% For L.P.
---|---
Lows Fire| High Fire
045| 6.4 – 7.4| 8.8 – 9.8
070| 6.3 – 7.3| 8.7 – 9.7
090| 6.8 – 7.8| 8.9 – 9.9
110| 7.1 – 8.1| 9.3 – 10.3
135| 7.1 – 8.2| 9.1 – 10.1
Downflow Unit
Capacity
| CO2% For L.P.
Low Fire| High Fire
045| 6.6 – 7.6| 9.1 – 10.1
070| 6.5 – 7.5| 8.6 – 9.6
090| 6.9 – 7.9| 9.1 – 10.1
110| 7.3 – 8.3| 9.5 – 10.5
The carbon monoxide reading should not exceed 100 ppm.
All Models| Firing Rate| CO2% Nat| CO2% L.P.
---|---|---|---
Upflow Horizontal| High Fire| 6.8 – 7.4| 7.5 – 9.0
Low Fire| 4.2 – 5.7| 5.0 – 6.0
Downflow| High Fire| 6.0 – 7.4| 6.9 – 8.4
Low Fire| 4.8 – 6.0| 5.7 – 7.0
The carbon monoxide reading should not exceed 100 ppm.
E – Turning Off Gas To the Unit
- Set the thermostat to its lowest setting.
- Turn off all the electrical power to the unit.
- Remove the unit access panel.
- Move the switch on the gas valve to OFF.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>