resideo TH6000 Series FocusPRO Programmable Thermostat Installation Guide
- June 5, 2024
- resideo
Table of Contents
FocusPRO® TH6000 Series
Programmable Thermostat
Installation Guide
This manual covers the following models
- TH6110D: For 1 Heat/1 Cool systems
- TH6220D: For up to 2 Heat/2 Cool systems
- TH6320U: For up to 3 Heat/2 Cool systems
(Remove battery holder to find model number)
System Types
- Gas, oil, or electric heat with air conditioning
- Warm air, hot water, high-efficiency furnaces, heat pumps, steam, gravity
- Heat only — two-wire systems, three-wire zone valves (Series 20), and normally open zone valves
- Heat only with fan
- Cool only
- 750 mV heating systems
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can
damage the product or cause a hazardous condition.
Need Help?
For assistance with this product please visit
http://customer.resideo.com or call Resideo Customer Care toll-free at
1-800-468-1502
Wallplate installation
- Separate wallplate from thermostat.
- Mount wallplate as shown below.
It’s easier to grasp the wallplate and remove it after completely removing the battery holder.
CAUTION : ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube,
do not place the old control in the trash. Contact your local waste management
authority for instructions regarding recycling and proper disposal.
Power options
Wiring
Terminal designations
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
Conventional Terminals: | Heat Pump Terminals: |
---|
Rc 24VAC power from the cooling transformer
R 24VAC power from the heating transformer
W Heat relay (stage 1)
W2 Heat relay (stage 2)
Y Compressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
G Fan relay
C 24VAC common. For 2 transformer systems, use common wire from the cooling
transformer.| Rc 24VAC power from the cooling transformer
R 24VAC power from the heating transformer
O/B Changeover valve
Y Compressor contactor (stage 1)
Y2 Compressor contactor (stage 2) -TH6320U only
G Fan relay
Aux Auxiliary heat relay
E Emergency heat relay
L Sends output when set to Em. Heat
C 24VAC common
|
Wiring guide — conventional systems
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
Y | Compressor contactor |
C | 24VAC common [3] |
W | Heat relay |
G | Fan relay |
M29440
Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
C | 24VAC common [3] |
W | Heat relay |
Rc | [R+Rc joined by jumper] |
---|---|
R | Series 20 valve terminal “R” [1] |
Y | Series 20 valve terminal “W” |
C | 24VAC common [3] |
W | Series 20 valve terminal “B” |
Rc | [R+Rc joined by jumper] |
---|---|
R | Power [1] |
Y | Normally open zone valve |
C | 24VAC common [3] |
Rc | Power (cooling transformer) [1,2] |
---|---|
R | Power (heating transformer) [1,2] |
Y | Compressor contactor |
C | 24VAC common [3, 4] |
W | Heat relay |
G | Fan relay |
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire.
A shielded cable is not required.
[1] Power supply. Provide disconnect means and overload protection as
required.
[2] Remove jumper for 2-transformer systems.
[3] Optional 24VAC common connection.
[4] The common connection must come from the cooling transformer.
[5] In Installer Setup, set system type to Heat Only.
[6] In Installer Setup, set system type to 2Heat/2Cool Conventional.
[ 7] In Installer Setup, set the changeover valve to O or B.
Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
C | 24VAC common [3] |
W | Heat relay |
G | Fan relay |
M29445
Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
Y | Compressor contactor |
C | 24VAC common [3] |
G | Fan relay |
****Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
Y | Compressor contactor (stage 1) |
C | 24VAC common [3] |
W | Heat relay (stage 1) |
G | Fan relay |
W2 | Heat relay (stage 2) |
Y2 | Compressor contactor (stage 2) |
Rc | Power (cooling transformer) [1,2] |
---|---|
R | Power (heating transformer) [1,2] |
Y | Compressor contactor (stage 1) |
C | 24VAC common [3, 4] |
W | Heat relay (stage 1) |
G | Fan relay |
W2 | Heat relay (stage 2) |
Y2 | Compressor contactor (stage 2) |
See [notes] below
[8] In Installer Setup, set system type to 2Heat/1Cool Heat Pump.
[9] In Installer Setup, set system type to 2Heat/2Cool Heat Pump.
[10] In Installer Setup, set system type to 3Heat/2Cool Heat Pump.
[11] L terminal sends a continuous output when the thermostat is set to Em.
Heat. Connect to Resideo zoning panels to switch the panel to Emergency Heat.
[12] Install field jumper between Aux and E if there is no emergency heat
relay.
****Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
Y | Compressor contactor |
C | 24VAC common [3] |
0/B | Changeover valve [7] |
G | Fan relay |
****Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
Y | Compressor contactor |
C | 24VAC common [3] |
0/B | Changeover valve [7] |
G | Fan relay |
Aux | Auxiliary heat relay [12] |
E | Emergency heat relay [12] |
L | Sends output when set to Em. Heat [11] |
Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
Y | Compressor contactor |
C | 24VAC common [3] |
0/B | Changeover valve [7] |
G | Fan relay |
Aux/E | Auxiliary/Emergency heat relay |
L | Sends output when set to Em. Heat [11] |
****Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
Y | Compressor contactor (stage 1) |
C | 24VAC common [3] |
0/B | Changeover valve [7] |
G | Fan relay |
Aux/E | Auxiliary/Emergency heat relay |
Y2 | Compressor contactor (stage 2) |
L | Sends output when set to Em. Heat [11] |
Rc | Power [1] |
---|---|
R | [R+Rc joined by jumper] |
Y | Compressor contactor (stage 1) |
C | 24VAC common [3] |
0/B | Changeover valve [7] |
G | Fan relay |
Aux/E | Auxiliary/Emergency heat relay |
Y2 | Compressor contactor (stage 2) |
L | Sends output when set to Em. Heat [11] |
See [notes] on page 4.
Thermostat mounting
Align the 4 tabs on the wallplate with slots on the back of the thermostat,
then push gently until the thermostat snaps in place.
Push excess wire back into the wall opening.
Plug wall opening with non-flammable insulation.
Installer setup
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
Setup function
Settings & options (factory default in bold)
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
1| System type| 0
1
2
3
4
5
6
7
8
9
10| 1 heat/1 cool conventional
1 heat/1 cool heat pump (no aux. heat)
Heat only — 2-wire systems, 3-wire zone valves (Series 20), and normally open
zone valves
Heat only with a fan
Cool only
2 heat/1 cool heat pump (with aux. heat)
2 heat/2 cool conventional
2 heat/1 cool conventional
1 heat/2 cool conventional
2 heat/2 cool heat pump (no aux. heat) – TH6320U only
3 heat/2 cool heat pump (with aux. heat) – TH6320U only
---|---|---|---
CV| Changeover valve (0/B terminal)| 0
1| Changeover valve (0/B terminal energized in cooling)
Changeover valve (0/B terminal energized in heating)
Cri| Fan control (heating)| 0
1| Gas or oil furnace — equipment controls the fan in heating
Electric furnace — thermostat controls the fan in heating
5| Stage 1 heat cycle rate (CPH: cycles/hour)| 5
1
3
9| For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
For hot water systems & furnaces of over 90% efficiency
For electric furnaces
6| Stage 2 heat cycle rate/Auxiliary heat cycle rate (CPH)| 5
1
3
9| For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
For hot water systems & furnaces of over 90% efficiency
For electric furnaces
7| Auxiliary heat cycle rate (CPH)
Only TH6320U for 3H/2C Heat Pumps| 5
1
3
9| For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
For hot water systems & furnaces of over 90% efficiency
For electric furnaces
8| Emergency heat cycle rate (CPH)| 9
1
3
5| For electric emergency heat
For steam or gravity systems
For hot water systems & furnaces of over 90% efficiency
For gas or oil furnaces of less than 90% efficiency
9| Stage 1 compressor cycle rate (CPH)| 3| Recommended for most
compressors [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
10| Stage 2 compressor cycle rate (CPH)| 3| Recommended for most
compressors [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
12| Manual/Auto changeover| 0
1
2| Manual changeover (Heat/Cool/Off)
Auto changeover (Heat/CooVAuto/Off)See page 8
Auto changeover only (Auto) See page 8
13| Adaptive Intelligent Recovery| 1
0| OnSee page 8
Off
14| Temperature display| 1
0| Fahrenheit
Celsius
15| Compressor protection| 5| Five-minute compressor off time See
page 8 [Other options: 0, 1, 2, 3 or 4-minute off time]
16| Schedule format| 0
1| 5/2 (programmable weekdays and weekends)
5/1/1 (weekdays, Saturday & Sunday programmable)
27| The heat temperature range stops| 90| Max. heat temperature
setting is 90° F (32° C) [Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]
28| The cool temperature range stops| 50| Min. cool temperature
setting is 50° F (10° C) [Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]
Installer system test
System test
System status
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
10| Heating system| 0
1
2
3| Heat and fan turn off.
Stage 1 heat turns on. The fan turns on if Setup Function 1 is set to 1, 5, 9,
or 10 OR Setup Function 3 is set to 1 See page 6
Stage 2 heat turns on
Stage 3 heat turns on – TH6320U only
20| Emergency heating system| 0
1
2| Heat and fan turn off
Heat and fan turn on
Stage 2 heat turns on (auxiliary heat) – TH6220D only
30| Cooling system| 0
1
2| The compressor and fan turn off
The compressor and fan turn on
Stage 2 compressor turns on
40| Fan system**| 0
1| The fan turns off
Fan turns on
CAUTION: Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
Special functions
Auto Changeover (Setup Function 12): When set to Auto, the thermostat
automatically selects heating or cooling depending on the indoor temperature.
The thermostat will automatically adjust the heat and cool settings to
maintain a 3-degree separation (fixed).
Note: If you select Auto Changeover Only, the System Setting on the
thermostat will stay locked in the Auto position, preventing the user from
changing it to Em Heat, Heat, Cool, or Off.
Adaptive Intelligent Recovery™ (Setup Function 13): This allows the
thermostat to “learn” how long the furnace and air conditioner take to reach
programmed temperature settings, so the temperature is reached at the
scheduled time.
Compressor Protection (Setup Function 15): Forces the compressor to wait
a few minutes before restarting, to prevent damage.
During the wait time, the message Cool On or Heat On (heat pumps only) will
flash on the display.
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Battery holder | Part Number 50007072-001 |
---|---|
Cover plate assembly* | Part Number 50002883-001 |
12 pack of medium cover plates* | Part Number 50007298-001 |
Specifications
Temperature Ranges|
- Heat: 40° to 90°F (4.5° to 32°C)
- Cool: 50° to 99°F (10° to 37°C)
---|---
Operating Ambient Temperature|
- 32° to 120°F (0° to 48.9°C) Shipping Temperature
- -20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity|
- 5% to 90% (non-condensing)
Physical Dimensions|
- 3-9/16″ H x 5-13/16″ W x 1-1/2″ D
- 91 mm H x 147 mm W x 38 mm D
ELECTRONIC WASTE NOTICE
The product should not be disposed of with other household waste. Check for
the nearest authorized collection centers or authorized recyclers. The correct
disposal of end-of-life equipment will help prevent potential negative
consequences for the environment and human health.
FCC statement at: https://customer.resideo.com/en-US/support/residential
/codes-and-standards/FCC15105/Pages/default.aspx
www.resideo.com
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
69-1920EFS—03 M.S.
Rev. 07-21
Printed in the United States
© 2021 Resideo Technologies, Inc.
All rights reserved.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
® U.S. Registered Trademark. Patents pending.
Copyright © 2021 Resideo Technologies, Inc.
All rights reserved.
References
- Resideo Customer Portal
- Smart Home Solutions in EMEA | Resideo
- Resideo Customer Portal
- FCC Rules Part 15: Residential Codes & Standards | Resideo
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>