ERGENIC ERG ARC-SL2114K Portable Air Conditioner Instruction Manual
- June 5, 2024
- ERGENIC
Table of Contents
PORTABLE AIR CONDITIONER
ERG ARC-SL2109K/ ERG ARC-SL2112K/ERG ARC-SL2114K
Instruction Manuel
Read this user manual before using this innovative Air Conditioner and keep it safe for future reference.
The refrigerant used in mobile air conditioners is the environmentally
friendly hydrocarbon R290. This refrigerant is odorless and compared to the
alternative refrigerant, the R290 is an ozone-free refrigerant, and its effect
is very low.
Read the instructions before use and repair.
The drawings provided in this manual may not be the same as the physical
objects. Refer to the physical objects.
Attention Matters
Safety warnings:
- Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
- The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.)
- Do not pierce or burn.
- Be aware that refrigerants may not contain an odor.
- The appliance shall be installed, operated, and stored in a room with a floor area larger than 14m.
- Keep any required ventilation openings clear of obstruction;
- Servicing shall be performed only as recommended by the manufacturer.
- The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
- Any person who is involved with working on or breaking into a refrigerant circuit should hold a currently valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with an industry-recognized assessment specification.
- Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of a person competent in the use of flammable refrigerants.
- All working procedure that affects safety means shall only be carried out by competent persons.
Notes:
The air conditioning is only suitable for indoor use and is not suitable for other applications.
Follow local grid interconnection rules while installing the air conditioning and ensure that it is properly grounded. If you have any questions on electrical installation, follow the instructions of the manufacturer, and if necessary, ask a professional electrician to install it.
Place the appliance in a flat and dry place and keep a distance of above 50cm between the unit and the surrounding objects or walls.
After the air conditioning is installed, ensure that the power plug is intact and firmly plugged into the mains power outlet, and place the mains power cable orderly to prevent someone from being tripped or pulling out the plug.
Do not put any object into the air inlet and outlet of the air conditioning. Keep the air inlet and outlet free from obstructions.
When drainage pipes are installed, ensure that the drainage pipes are properly connected, and are not distorted or bent.
- While adjusting the upper and lower wind-guide strips of the air outlet, pluck it with your hands gently to avoid damaging wind-guide strips.
When moving the appliance, make sure that it is in an upright position.
The unit should stay away from gasoline, flammable gas, stoves, and other heat sources. - Don’t disassemble, overhaul and modify the appliance arbitrarily, otherwise it will cause a unit malfunction or even bring harm to persons and properties. To avoid danger, if a failure occurs, ask the manufacturer or professionals to repair it.
- Do not install and use the appliance in the bathroom or other humid environments.
- Do not pull the plug to turn off the appliance.
- Do not place cups or other objects on the body to prevent water or other liquids from spilling into the air conditioning.
*Do not use insecticide sprays or other flammable substances near the appliance. - Do not wipe or wash the appliance with chemical solvents such as gasoline and alcohol. When you need to clean the appliance, you must disconnect the mains power supply, and clean it with a half-wet soft cloth. If the appliance is really dirty, scrub with a mild detergent.
- The appliance can be used by children aged 8 years and above and persons with reduced physical, sensory or mental capabilities if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and maintenance shall not be made by children without supervision. If the mains power cable is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a hazard. The appliance shall be installed in accordance with national wiring regulations.
- Do not operate the appliance in a wet room such as a bathroom or laundry room.
Transportation, marking, and storage of units
-
Transport of equipment containing flammable refrigerants
Compliance with the transport regulations -
Marking of equipment using signs
Compliance with local regulations -
Disposal of equipment using flammable refrigerants
Compliance with national regulations -
Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer’s instructions. -
Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
Features and Components
Component
- Adjustable slide bar
- Slide bar connector
- Exhaust hose
- Exhaust pipe joint
- Remote control
Control Setting
Control panel operation instructions
Operation interface:
1: Swing Key
2: Timer Key
3:Fan Key
4:Up Key| 5: Display Window
6: Down Key
7: Mode Key
8: Sleep Mode Key
9: Power Key
---|---
-
SWING Key: The SWING function only works after turning on the unit, you can turn the swing on or off.
-
TIMER Key: When the unit is on, press the key to close timing; When the unit is off, press the key to open timing.
Press the key, when the timing symbol flashes, press up and down key to select the required timing value.
Timing values can be set in 1-24 hours and the timing value is adjusted up or down by one hour. -
FAN SPEED Key: In cooling and fan mode, press this key to select high, middle, and low speed. This function is not available in SLEEP mode and DEHUMIDIFYING mode.
-
UP Key: Under timer mode, press this key to adjust the time upwards.
Under cooling mode, press this key to adjust the temperature higher.
This function is not available under FAN mode and DEHUMIDIFYING mode. -
Display Window
-
DOWN Key: Under timer mode, press this key to adjust the timer downwards.
Under cooling mode, press this key to adjust the temperature lower.
This function is not available under FAN mode and DEHUMIDIFYING mode. -
Mode Key: When the unit is on, press this key to switch between cooling → dry(dehumidifier)→ fan mode.
-
Sleep Mode: When the power is on and in cooling mode, press the ‘SLEEP’ button to start the sleep mode.
Under sleep mode, the FAN speed is set to LOW speed and not adjustable. The SLEEP mode can be canceled by pressing the button. -
Power Key: Press this key to turn on and turn off the unit.
MEMORY FUNCTION: The appliance maintains its settings during a power failure.
Operation instructions of remote control
The air conditioner can be controlled with the remote control. TwoAAA- batteries are required to use the remote control.
POWER : Press the POWER button to turn the unit on and off.
MODE : Press the MODE button to switch between cooling,
dry(dehumidifier), and fan modes.
UP : Press the UP button to increase the desired temperature and set the
duration of the timer.
DOWN : Press the DOWN button to reduce the desired temperature and set
the duration of the timer.
FAN : Press the FAN button to cycle between high, medium, and low fan
speeds.
TIMER : Press the TIMER button to set the duration of the power on or
power off timer.
SWING : Press the swing button to change the orientation of the louvers
to direct the air
TEMPERATURE UNIT : Press to switch between displaying the temperature in
Celsius and Fahrenheit.
SLEEP MODE : Press to turn on the sleep mode. The unit will work with
energy-saving logic and the lowest fan speed.
Protection function
-
Frost Protection Function:
In cooling mode, if the temperature of the exhaust pipe is too low, the unit will automatically enter protection status; if the temperature of the exhaust pipe rises to a certain temperature, it can automatically revert to normal operation. -
Overflow Protection Function:
When the water in the water pan exceeds the warning level, the unit will automatically sound an alarm, and the “FULL” indicator light will flash. At this point, you need to move the drainage pipe connecting the unit or the water outlet to the sewer or another drainage area to empty the water (details see Drainage Instructions at the end of this chapter). After the water is emptied, the unit will automatically return to its original state. -
Protection Function of the Compressor
To increase the service life of the compressor, it has a 3-minute delay booting protection function after the compressor is turned off.
Installation and adjustment
1. Installation:
Warning: Before using the unit, keep it upright for at least two hours.
The unit can be easily moved in the room. In the moving process, ensure that
the unit is in the upright position and should be placed on a flat surface. Do
not install and use the unit in the bathroom or other humid environments.
1.1 Install the heat pipe assembly (as shown in Fig.1)
- take out the outer connector assembly and the exhaust pipe assembly, and remove the plastic bags;
- insert the heat pipe assembly (the end of the exhaust joint) into the back panel vent slot (push to the left) and complete the assembly (as shown in figure 1).
1.2 Installation of window sealing accessories
-
Half-open the window, and mount the window sealing plate assembly to the window (as shown in Fig.2 and Fig.3). Components can be placed in the horizontal and vertical directions.
-
Pull various components of the window sealing plate assembly open, adjust their opening distance to bring both ends of the assembly into contact with the window frame, and fix various components of the assembly.1.2 Install the window sealing plate assembly
Notes: 1: The flat end of the exhaust pipe joints must be snapped into place.
2: The pipe cannot be distorted nor has substantial turning (greater than 45 °). Keep the ventilation of the exhaust pipe unblocked. -
Move the unit with installed heat pipe and fittings before the window, and the distance between the body and walls or other objects shall be at least 50 cm (as shown in Fig.4).
-
Elongate the exhaust pipe and snap the flat end of the exhaust pipe joints into the hole of the window sealing plate assembly (as shown in Fig.5 and Fig.6).
Notes:1: The flat end of the exhaust pipe joints must be snapped into place.
2: The pipe cannot be distorted nor has substantial turning (greater than 45 °). Keep the ventilation of the exhaust pipe unblocked.
Important Notice:
The length of the exhaust hose shall be 280~1,500mm, and this length is based
on the specifications of the unit. Do not use extension tubes or replace them
with other different hoses, or this may cause a malfunction.
The exhaust hosts must be unblocked; otherwise, it may cause overheating.
Drainage Instructions
This unit has two drainage methods: manual drainage and continuous drainage.
- Manual drainage:
- When the unit stops after the water is full, turn off the unit power and
unplug the power plug.
Notes: Move the unit carefully, so as not to spill the water in the water pan at the bottom of the body. - Place the water container below the side water outlet behind the body.
- Unplug the water plug, and the water will automatically flow into the water
container. Notes:
1)Keep the water plug properly.
2)During drainage, the body can be tilted slightly backward.
3)If the water container cannot hold all the water before the water container is full, insert the water outlet with the water plug as soon as possible to prevent water from flowing to the floor or the carpet.
4)When the water is discharged, insert the water plug.
- Continuous drainage (Optional) (only applicable to dehumidifying mode), as shown in the figure:
1)Remove the rubber plug and keep it for future use.
2)Set the drainage pipe into the water outlet.
3)Connect the drainage pipe to the water container.
Maintenance
Cleaning: before cleaning and maintenance, turn off the unit and unplug the plug.
-
Clean the surface
Clean the surface of the unit with a wet soft cloth. Don’t use chemicals, such as benzene, alcohol, gasoline, etc; otherwise, the surface of the unit will be damaged or even the whole unit will be damaged. -
Clean the filter screen
If the filter screen is clogged with dust, and the effectiveness of the unit is reduced, be sure to clean the filter screen once every two weeks. -
Clean the upper filter screen frame
1)Unscrew one screw fixed by the EVA filter net and back shell with a screwdriver, and take out the EVA filter net.
Put the EVA filter screen into warm water with neutral detergent (about 40℃ / 104℉) and dry it in the shade after rinsing clean.
Unit Storage:
- Unscrew the drainage cover, unplug the water plug, and discharge the water in the water pan into other water containers or directly tilt the body to discharge the water into other containers.
- Turn on the unit, adjust it to low-wind ventilation mode, and maintain this state until the drainage pipe becomes dry, so as to keep the inside of the body in a dry state and prevent it from mildewing.
- Turn off the unit, unplug the power plug, and wrap the mains power cable around the wrapping post; install the water plug and the drainage cover.
- Remove the exhaust pipe and keep it properly.
- Cover the unit with a plastic bag. Store the unit in a dry place, keep it out of the reach of children, and take dust control measures.
- Remove batteries from the remote control and keep them properly.
Note: Ensure that the body is placed in a dry place and keep all components properly.
Troubleshooting I
- Information on servicing
- Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. - Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of flammable gas or vapor being present while the work is being performed. - General work area
All maintenance staff and others working in the local area shall be instructed on the nature of the work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off.
Ensure that the conditions within the area have been made safe by control of flammable material. - Checking for the presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe. - Presence of a fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area. - No ignition sources
No person carrying out work in relation to a refrigeration system that involves exposing any pipework that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removal, and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed. - Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out.
The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. - Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
– The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
– The ventilation unit and outlets are operating adequately and are not obstructed;
– If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
– Marking the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
– Refrigeration pipes or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials that are inherently resistant to being corroded or are suitably protected against being so corroded. - Checks to electrical devices
Repair and maintenance of electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise the safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
• That capacitor is discharged: this shall be done in a safe manner to avoid the possibility of sparking;
• That there no live electrical components and wiring are exposed while charging, recovering or purging the system;
• That there is continuity of earth bonding.
- Repairs sealed components
- During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
- Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, an excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.
- Ensure that the apparatus is mounted securely.
- Ensure that seals or sealing materials have not degraded such that they no
longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s
specifications.
NOTE: The use of silicone sealant may inhibit the effectiveness of some types of leak detection equipment.
Intrinsically safe components do not have to be isolated prior to working on them.
-
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and currently permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while living in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak. -
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. -
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. -
Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If leakage of refrigerant is found which requires brazing, all of the refrigerants shall be recovered from the system, or isolated (by means of shut-off valves) in a part of the system remote from the leak. Oxygen-free nitrogen (OFN) shall then be purged through the system both before and during the brazing process. -
Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose-conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:
• Remove refrigerant;
• Purge the circuit with inert gas;
• Evacuate;
• Purge again with inert gas;
• Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to the atmosphere, and finally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available. -
Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
• Cylinders shall be kept upright.
• Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging prior to commissioning. A follow-up leak test shall be carried out prior to leaving the site. -
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
• Mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• All personal protective equipment is available and being used correctly;
• The recovery process is supervised at all times by a competent person;
• Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down the refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that the cylinder is situated on the scales before recovery takes place.
g) Start the recovery unit and operate in accordance with the manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from the site promptly and all isolation valves on the equipment are closed off.
j) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked. -
Labeling
Equipment shall be labeled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. -
Recovery
When removing refrigerants from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. Special cylinders for the recovery of refrigerant). Cylinders shall be complete with a pressure relief valve and associated shut- off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery unit, check that it is in satisfactory working order, has been properly maintained, and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
Consult the manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process.
When oil is drained from a system, it shall be carried out safely.
Fuse parameters of the unit
Type: 5TE or 932 or 5H Voltage: 250V Current: 3.15 A
Troubleshooting
Do not repair or disassemble the air conditioning by yourself. The unqualified repair will lead to the failure of the warranty card and may cause damage to users or their properties.
Problems | Reasons | Solutions |
---|---|---|
The air conditioning does not work. | There is no electricity. | Turn it on |
after connecting it to a socket with electricity.
The water-full indicator will light.| Discharge the water inside.
The ambient temperature is too low or too high| Recommend to use the machine
at the temperature of 7-35 °C.
In cooling mode, the room temperature is lower than the set temperature; in
heating mode, the room temperature is higher than the set temperature.| Change
the set temperature.
In dehumidification mode, the ambient temperature is low.| The machine is
placed in a room with an ambient temperature of greater than 17 ‘C.
The cooling effect is not good| There is direct sunlight.| Pull the Curtain.
Doors or windows are open; there are a lot of people; or in cooling mode,
there are other sources of heat.| Close doors and windows, and add new air
conditioning.
The filter screen is dirty.| Clean or replace the filter screen.
The air inlet or outlet is blocked.| Clear obstructions.
Big Noise| The air conditioning is not placed on a flat surface.| Put the air
conditioning in a flat and hard place (to reduce noise).
The compressor does not work.| Frost protection starts.| Wait for 3 minutes
until the temperature is lowered, and then restart the machine.
Overheat protection starts.
The remote control does not work.| The distance between the machine and the
remote control is too far.| Let the remote control get close to the air
conditioning, and make sure that the remote control directly faces the
direction of the remote control receiver.
The remote control is not aligned with the direction of the remote control
receiver.
Batteries are dead.| Replace batteries.
Displays ‘El’.| The room temperature sensor is abnormal.| Check the room
temperature sensor and related circuitry.
Displays ‘E2’| The pipe temperature sensor is abnormal.| Check the pipe
temperature sensor and related circuitry.
Note: If problems not listed in the table occur or recommended solutions do not work, contact the professional service organization.
Addendum
The schematic diagram for air conditioning
The specific technical parameters of the unit shall be subject to the
nameplate on the appliance
This symbol on the product or in the instructions means that your electrical and electronic equipment should be disposed at the end of its life separately from your household waste. There are separate collection systems for recycling in the EU. For more information, please see contact the local authority or your retailer where you purchased the product.
We
Pirox International B.V.
Blaak 6 | 3011 TA Rotterdam | The Netherlands
Hereby declare under our sole responsibility that the product:
Model number: ERG ARC-21109/ ERG ARC-SL2109K/ ERG ARC-SL2112K/ ERG ARC-SL2114K
Product description: Ergenic portable air-conditioner
To which this declaration relates is in conformity with the requirements of
the following standards:
Particular safety requirements for electrical heat pumps, air conditioners,
and dehumidifiers IEC 60335-2-40
The LVD directive 2014/35/EU
EN 60335-2-40: 2003/A13:2012
EN 60335-1:2012/A13:2017
EN 62233:2008
The EMC directive 2014/30/EU;
EN 55014-1:2017
EN 55014-2:2015
EN 61000-3-2:2014
EN 61000-3-3:2013
EN 61000-3-11:2000
ERP requirement (EU) 206/2012
(2018/C 092/03):2018-03-09; EN 145-2:2013; EN 14511-3:2013; EN 14825:2016; EN
12102-1:2017
ROHS directive (EU) 2015/863 amending annex II to directive 2011/65/EU
IEC 62321-3-1:2013; IEC 62321-4:2013; IEC 62321-5:2013; IEC 62321-7-1:2015;
IEC 62321-6:2015; IEC 62321-8:2017
This certifies that the following designated product:
Model number: ERG ARC-21109/ ERG ARC-SL2109K/ ERG ARC-SL2112K/ ERG ARC-SL2114K
Product description: Ergenic portable air-conditioner
Complies with the requirements of the following directives and carries the CE
marking accordingly:
Particular safety requirements for electrical heat pumps, air conditioners,
and dehumidifiers IEC 60335-2-40
The EMC directive 2014/30/EU
The LVD directive 2014/35/EU
ERP requirement (EU) 206/2012
ROHS directive (EU) 2015/863 amending annex II to directive 2011/65/EU
This declaration is the responsibility of the manufacturer/importer:
Pirox International B.V.
Rotterdam, 1 March 2020
R.J. de Bruin,
CE COMPLIANCE
Hereby Pirox International B.V. declares that this product is in accordance
with essential requirements and other relevant terms of the European
regulation 2004/108/EC. RoHS 2011/65/EU.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>