XUNChip XM7571 Ceiling-mounted smoke sensor User Manual

June 5, 2024
XUNChip

XM7571
User Manual
File Version: V22.4.15

XUNChip XM7571 Ceiling mounted smoke sensor

XM7571 using the standard RS485 bus MODBUS-RTU protocol, easy access to PLC, DCS, and other instruments or systems for monitoring conductivity state quantities.The internal use of high-precision sensing core and related devices to ensure high reliability and excellent long-term stability can be Sha has XUNCHIP Industrial Co., Ltd XUNCHIP Brand Division customized RS232, RS485, CAN,4-20mA, DC0~5V\10V, ZIGBEE, Lora, WIFI, GPRS and other output methods.

Technical Parameters

Technical parameter Parameter value
Brand XUNCHIP
Smoke measuring range 0~5000ppm
Smoke allow deviation ±7%
Smoke Repeatability test ±5%
Smoke detection chip Import digital
Temperature characteristics ±0.5%/℃
Communication Interface RS485
Default baud rate 9600 8 n 1
Power DC6~24V 1A
Running temperature -40~80°C
Working humidity 5%RH~90%RH

Product Size

Contour dimension

XUNChip XM7571 Ceiling mounted smoke sensor - fig1

XUNChip XM7571 Ceiling mounted smoke sensor - fig2

System Diagram

The signal line is made of twisted pairs with water-proof, oil-proof, and corrosion-proof. It has a fast response speed, high data transmission efficiency, and a standard length of one meter
RS485 wiring method
XUNChip XM7571 Ceiling mounted smoke sensor - fig3 4-20mA wiring method
XUNChip XM7571 Ceiling mounted smoke sensor - fig4Switch connection mode
XUNChip XM7571 Ceiling mounted smoke sensor - fig5

Installation method

Ceiling

XUNChip XM7571 Ceiling mounted smoke sensor - fig6

Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the default baud rate is 9600,8,n,1.
1. Read data (function code 0x03)
Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 01 84 0A.

Address Function Code Start Address Data Length Check Code
01 03 00 00 00 01 84 0A

For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6, response format:

Address Function Code Length Data 1 Check Code
01 03 02 00 79 79 A6

Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is converted to decimal value is 121, for general Sobo products, the temperature and humidity data magnification is 100, and the light data The magnification is 1 or 10. The data magnification of this product is 1, the real value is 121/1=121, and so on.
2. Common data address table

Configuration Address| Register Address| Register Description| Data Type| Value Range
---|---|---|---|---
40001| 00 00| conductivity| Read Only| 0~65535
40101| 00 64| Model Code| Read/Write| 0~65535
40102| 00 65| total number of measuring points| read/write| 1~20
40103| 00 66| device address| read/write| 1~249
40104| 00 67| baud rate| read/write| 0~6
40105| 00 68| communication mode| read/write| 1~4
40106| 00 69| protocol type| read/write| 1~10

3 Read and modify device address
(1) Read or query device address
If you don’t know the current device address and there is only one device on the bus, you can query the device address through the command 03 00 66 00 01 71 9E.

Device Address Function Code Start Address Data Length Check Code
FA 03 00 66 00 01 71 9E

FA means 250 is the general address, when you don’t know the address, you can use 250 to get the real device address, 00 66 is the device address register. For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 01 79 84, and its format parsing is shown in the following table:

Device Address Function Code Start Address Model Code Check Code
01 03 02 00 01 79 84

In the response data, the first byte 01 represents the real address of the current device.
(2) Change device address
For example, if the current device address is 1 and we want to change it to 02, the command is: 01 06 00 66 00 02 E8 14 .

Device Address Function Code Register Address Target Address Check Code
01 06 00 66 00 02 E8 14

After the change is successful, the device will return the information: 02 06 00 66 00 02 E8 27, and its format analysis is shown in the following table:

Device Address Function Code Register Address Target Address Check Code
02 06 00 66 00 02 E8 27

In the response data, after the modification is successful, the first byte is the new device address. Generally, after the device address is changed, it will take effect immediately. At this time, the user needs to change the query command of his software accordingly. .
4 Read and modify the baud rate
(1) Read baud rate
The default factory baud rate of the device is 9600. If you need to change it , you can change it according to the following table and the corresponding communication protocol. For example, to read the baud rate ID of the current device, the command is: 01 03 00 67 00 01 35 D5, the format is parsed as follows.

Device Address Function Code Start Address Data Length Check Code
01 03 00 67 00 01 35 D5

Read the baud rate code of the current device. Baud rate code: 1 is 2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 03 F8 45, and its format analysis is shown in the following table:

Device Address Function Code Data Length Baud Rate Code Check Code
01 03 02 00 03 F8 45

According to the baud rate code, 03 is 9600, that is, the baud rate of the current device is 9600.
(2) Change the baud rate
For example, change the baud rate from 9600 to 38400, that is, change the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 16 .

Device Address Function Code Register Address Target Baud Rate Check Code
01 06 00 67 00 05 F8 16

Change the baud rate from 9600 to 38400, that is, change the code from 3 to 5. The new baud rate will take effect immediately, and the device will lose response at this time, and the baud rate of the device needs to be checked accordingly and Modified.
5 Read and modify correction value
(1) Read correction value
When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified in a range of plus or minus 1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the displayed value is too small by 100, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command, 100 is hexadecimal 0x64;If you need to reduce it, you can set a negative value, such as -100, the corresponding hexadecimal value is FF 9C, the calculation method is 100 -65535=65435, and then converted to hexadecimal, it is 0x FF 9C. Device The correction value starts from 00 6B. We take the first parameter as an example to illustrate. When there are multiple parameters, the correction value is read and modified in the same way.

Device Address Function Code Start Address Data Length Check Code
01 03 00 6B 00 01 F5 D6
--- --- --- --- ---

For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 64 B9 AF, and its format parsing is shown in the following table:

Device Address Function Code Data Length Correction Value Check Code
01 03 02 00 64 B9 AF

In the response data, the first byte 01 represents the real address of the current device, and 00 6B is the first state correction value register. If the device has multiple parameters, other parameters operate in the same way as this The same, generally, temperature and humidity have this parameter, and lighting generally does not have this parameter.
(2) Change the correction value
For example, if the current state is too small, we want to add 1 to its real value and add 100 to the current value. The correction operation command is: 01 06 00 6B 00 64 F9 FD .

Device Address Function Code Register Address Target Address Check Code
01 06 00 6B 00 64 F9 FD

After the operation is successful, the device will return the information: 01 06 00 6B 00 64 F9 FD, after the successful change, the parameters will take effect immediately.
6 Read and modify the alarm threshold value
(1) Read alarm threshold value
When the actual alarm threshold needs to be adjusted, we can read or adjust the alarm threshold through the following communication protocol. The threshold can be modified in the range of 100-1000. For example, we read the current alarm valve Value, the command is 01 03 00 6C 00 01 44 17. In the command, 108 is hexadecimal 0x6C.

Device Address Function Code Start Address Data Length Check Code
01 03 00 6C 00 01 44 17

For the correct query command, the device will respond, for example, the response data is: 01 03 02 03 E8 B8 FA, and its format analysis is shown in the following table:

Device Address Function Code Data Length Correction Value Check Code
01 03 02 03 E8 B8 FA

In the response data, the first byte 01 represents the real address of the current device, and 03 E8 is the register parameter value.
(2) Change the alarm threshold
For example, the current alarm threshold is too small, we want to change it to 1000, and the operation command is 01 06 00 6C 03 E8 49 69.

Device Address Function Code Register Address Target Address Check Code
01 06 00 6C 03 E8 49 69

After the operation is successful, the device will return the letter 01 06 00 6C 03 E8 49 69 , and the parameters will take effect immediately after successful modification.

Disclaimer

This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product Sha nghai XUNCHIP Industrial Co., Ltd XUNCHIP Brand Division
specifications and product descriptions may be modified at any time without notice.

Contact Us
Brand: XUNCHIP
Address: Room 208, Building 8, No. 215, Nandong Road, Baoshan District, Shanghai, Xinxin Brand
Business Department
Chinese site: http://www.xunchip.com
International site: http://www.xunchip.com
SKYPE: soobuu
E-mail: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
Sha nghai XUNCHIP Industrial Co., Ltd XUNCHIP Brand Division

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

XUNChip User Manuals

Related Manuals