XUNChip XM7571 Ceiling-mounted smoke sensor User Manual
- June 5, 2024
- XUNChip
Table of Contents
XM7571
User Manual
File Version: V22.4.15
XM7571 using the standard RS485 bus MODBUS-RTU protocol, easy access to PLC, DCS, and other instruments or systems for monitoring conductivity state quantities.The internal use of high-precision sensing core and related devices to ensure high reliability and excellent long-term stability can be Sha has XUNCHIP Industrial Co., Ltd XUNCHIP Brand Division customized RS232, RS485, CAN,4-20mA, DC0~5V\10V, ZIGBEE, Lora, WIFI, GPRS and other output methods.
Technical Parameters
Technical parameter | Parameter value |
---|---|
Brand | XUNCHIP |
Smoke measuring range | 0~5000ppm |
Smoke allow deviation | ±7% |
Smoke Repeatability test | ±5% |
Smoke detection chip | Import digital |
Temperature characteristics | ±0.5%/℃ |
Communication Interface | RS485 |
Default baud rate | 9600 8 n 1 |
Power | DC6~24V 1A |
Running temperature | -40~80°C |
Working humidity | 5%RH~90%RH |
Product Size
Contour dimension
System Diagram
The signal line is made of twisted pairs with water-proof, oil-proof, and
corrosion-proof. It has a fast response speed, high data transmission
efficiency, and a standard length of one meter
RS485 wiring method
4-20mA wiring method
Switch connection mode
Installation method
Ceiling
Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or
reply commands are hexadecimal data. The default device address is 1 when the
device leaves the factory, and the default baud rate is 9600,8,n,1.
1. Read data (function code 0x03)
Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the
upper computer sends the command: 01 03 00 00 00 01 84 0A.
Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 00 | 00 01 | 84 0A |
For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6, response format:
Address | Function Code | Length | Data 1 | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 79 | 79 A6 |
Data description: The data in the command is hexadecimal, take data 1 as an
example, 00 79 is converted to decimal value is 121, for general Sobo
products, the temperature and humidity data magnification is 100, and the
light data The magnification is 1 or 10. The data magnification of this
product is 1, the real value is 121/1=121, and so on.
2. Common data address table
Configuration Address| Register Address| Register Description| Data Type|
Value Range
---|---|---|---|---
40001| 00 00| conductivity| Read Only| 0~65535
40101| 00 64| Model Code| Read/Write| 0~65535
40102| 00 65| total number of measuring points| read/write| 1~20
40103| 00 66| device address| read/write| 1~249
40104| 00 67| baud rate| read/write| 0~6
40105| 00 68| communication mode| read/write| 1~4
40106| 00 69| protocol type| read/write| 1~10
3 Read and modify device address
(1) Read or query device address
If you don’t know the current device address and there is only one device on
the bus, you can query the device address through the command 03 00 66 00 01
71 9E.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
FA | 03 | 00 66 | 00 01 | 71 9E |
FA means 250 is the general address, when you don’t know the address, you can use 250 to get the real device address, 00 66 is the device address register. For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 01 79 84, and its format parsing is shown in the following table:
Device Address | Function Code | Start Address | Model Code | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 01 | 79 84 |
In the response data, the first byte 01 represents the real address of the
current device.
(2) Change device address
For example, if the current device address is 1 and we want to change it to
02, the command is: 01 06 00 66 00 02 E8 14 .
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 66 | 00 02 | E8 14 |
After the change is successful, the device will return the information: 02 06 00 66 00 02 E8 27, and its format analysis is shown in the following table:
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
02 | 06 | 00 66 | 00 02 | E8 27 |
In the response data, after the modification is successful, the first byte is
the new device address. Generally, after the device address is changed, it
will take effect immediately. At this time, the user needs to change the query
command of his software accordingly. .
4 Read and modify the baud rate
(1) Read baud rate
The default factory baud rate of the device is 9600. If you need to change it
, you can change it according to the following table and the corresponding
communication protocol. For example, to read the baud rate ID of the current
device, the command is: 01 03 00 67 00 01 35 D5, the format is parsed as
follows.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 67 | 00 01 | 35 D5 |
Read the baud rate code of the current device. Baud rate code: 1 is 2400; 2 is
4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example, the
response data is: 01 03 02 00 03 F8 45, and its format analysis is shown in
the following table:
Device Address | Function Code | Data Length | Baud Rate Code | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 03 | F8 45 |
According to the baud rate code, 03 is 9600, that is, the baud rate of the
current device is 9600.
(2) Change the baud rate
For example, change the baud rate from 9600 to 38400, that is, change the code
from 3 to 5, the command is: 01 06 00 67 00 05 F8 16 .
Device Address | Function Code | Register Address | Target Baud Rate | Check Code |
---|---|---|---|---|
01 | 06 | 00 67 | 00 05 | F8 16 |
Change the baud rate from 9600 to 38400, that is, change the code from 3 to 5.
The new baud rate will take effect immediately, and the device will lose
response at this time, and the baud rate of the device needs to be checked
accordingly and Modified.
5 Read and modify correction value
(1) Read correction value
When there is an error between the data and the reference standard, we can
reduce the display error by adjusting the correction value. The correction
difference can be modified in a range of plus or minus 1000, that is, the
value range is 0-1000 or 64535 -65535. For example, when the displayed value
is too small by 100, we can correct it by adding 100. The command is: 01 03 00
6B 00 01 F5 D6 . In the command, 100 is hexadecimal 0x64;If you need to reduce
it, you can set a negative value, such as -100, the corresponding hexadecimal
value is FF 9C, the calculation method is 100 -65535=65435, and then converted
to hexadecimal, it is 0x FF 9C. Device The correction value starts from 00 6B.
We take the first parameter as an example to illustrate. When there are
multiple parameters, the correction value is read and modified in the same
way.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 6B | 00 01 | F5 D6 |
--- | --- | --- | --- | --- |
For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 64 B9 AF, and its format parsing is shown in the following table:
Device Address | Function Code | Data Length | Correction Value | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 64 | B9 AF |
In the response data, the first byte 01 represents the real address of the
current device, and 00 6B is the first state correction value register. If the
device has multiple parameters, other parameters operate in the same way as
this The same, generally, temperature and humidity have this parameter, and
lighting generally does not have this parameter.
(2) Change the correction value
For example, if the current state is too small, we want to add 1 to its real
value and add 100 to the current value. The correction operation command is:
01 06 00 6B 00 64 F9 FD .
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 6B | 00 64 | F9 FD |
After the operation is successful, the device will return the information: 01
06 00 6B 00 64 F9 FD, after the successful change, the parameters will take
effect immediately.
6 Read and modify the alarm threshold value
(1) Read alarm threshold value
When the actual alarm threshold needs to be adjusted, we can read or adjust
the alarm threshold through the following communication protocol. The
threshold can be modified in the range of 100-1000. For example, we read the
current alarm valve Value, the command is 01 03 00 6C 00 01 44 17. In the
command, 108 is hexadecimal 0x6C.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 6C | 00 01 | 44 17 |
For the correct query command, the device will respond, for example, the response data is: 01 03 02 03 E8 B8 FA, and its format analysis is shown in the following table:
Device Address | Function Code | Data Length | Correction Value | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 03 E8 | B8 FA |
In the response data, the first byte 01 represents the real address of the
current device, and 03 E8 is the register parameter value.
(2) Change the alarm threshold
For example, the current alarm threshold is too small, we want to change it to
1000, and the operation command is 01 06 00 6C 03 E8 49 69.
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 6C | 03 E8 | 49 69 |
After the operation is successful, the device will return the letter 01 06 00 6C 03 E8 49 69 , and the parameters will take effect immediately after successful modification.
Disclaimer
This document provides all information about the product, does not grant any
license to intellectual property, does not express or imply, and prohibits any
other means of granting any intellectual property rights, such as the
statement of sales terms and conditions of this product, other issues. No
liability is assumed. Furthermore, our company makes no warranties, express or
implied, regarding the sale and use of this product, including the suitability
for the specific use of the product, the marketability or the infringement
liability for any patent, copyright or other intellectual property rights,
etc. Product Sha nghai XUNCHIP Industrial Co., Ltd XUNCHIP Brand Division
specifications and product descriptions may be modified at any time without
notice.
Contact Us
Brand: XUNCHIP
Address: Room 208, Building 8, No. 215, Nandong Road, Baoshan District,
Shanghai, Xinxin Brand
Business Department
Chinese site: http://www.xunchip.com
International site: http://www.xunchip.com
SKYPE: soobuu
E-mail: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
Sha nghai XUNCHIP Industrial Co., Ltd XUNCHIP Brand Division
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>