thermo-hygro STC-1000 Thermostat Heating and Refrigeration Auto Switch Controller User Manual
- June 5, 2024
- Thermo Hygro
Table of Contents
thermo-hygro STC-1000 Thermostat Heating and Refrigeration Auto Switch Controller
STC-1000 temperature controller regulates the temperature by turn on/off the
power status of the connected load.
Within dual individually relays, this unit could connect two loads
simultaneously, one for refrigeration, another for heating, and the heating
and the refrigeration controlling modes auto switch according to the room
sensor temperature; that’s why it was called “All-Purpose Temperature
Controller.”
Package
Controller x 1 PCS
Clips x 2 PCS
Sensor x 1 PCS
Manual x 1 PCS
Waterproof Cover x 1 PCS
Specification
Input Power: 220V AC ± 10% 50/60HZ; (12/24/48/110V Option)
Maximum current: 10A (Default) under 220V AC
Sensor: NTC Sensor (NTC), 25°C /10 KΩ, the sensor cable 200cm
Protection Class: IP65 to the front panel
Storage: -10°C ~ 60°C, RH<90%, without condensation
Measuring Range: -50.0°C ~ 120°C
Controlling Range: -50.0°C ~ 99.9°C
Resolution: 0.1°C
Accuracy: ± 1°C
Power Consumption: ≤ 3W
Environmental Information
|
Package:
| The package’s material is 100% recyclable. Just dispose of it through
specialized recyclers.
---|---|---
Product:
| The electro components can be recycled or reused if it is disassembled for specialized companies.
Disposal:
| Please do not burn or throw the controllers in domestic garbage. Observe the respective law in your region concerning the environmentally responsible manner of disposing of its devices.
Interface & Operation
Front Panel & Icon
Under normal status
- Press the key to check the temperature set-point F1;
- Press the key to check the Hysteresis value F2;
- Hold the key for 3s to power off / on;
- Hold the key and the key at the same time for 5s to restore factory settings
Indicators / Characters
Indicator| Meaning| Light on| Light off| Light
Flashing
---|---|---|---|---
Cool| Refrigerating| Working| Stop| Delay
Heat| Heater status| Working| Stop| N/A
Set| Setting status| On Set| Non-setting| N/A
Dimensions & Installation
A. Suggested amount dimension: 71 29 85 + mm (WHD)
B. Detach the slide fasteners, put the controller into the hole, wiring follow
the diagram
C. Install the fasteners, and install the waterproof cover
D. Please avoid installing in the below environments:
- Relative humidity > 90%, have condensation.
- The places that temperature <-10°C or >60°C.
- The places that have inflammable and explosives.
- Strong vibration or struck.
- Exposed to the continuous water mist spraying.
- Exposed to the dust.
- Exposure to corrosive and pollution gas (gas, smoke, or salt fog that contains sulfur or ammonia.
- Wireless electromagnetic interference or strong magnetic fields (near to transmitting antenna or switch board room);
Wiring Diagram
A. Need not to distinguish + or – when wiring the NTC sensor’s cable or the
Input power.
• Wiring the 5 to the live wire and terminal 6 to a heater, or the opposite.
• Wiring the 7 to the live wire and terminal 8 to a refrigerator, or opposite.
The heating and cooling mode will switch automatically.
B. The input voltage must be within the voltage value marked in the diagram ±10% value.
C. Suggest Load Power ≤ (The voltage of Load * Max current of Relay)/Factor
• The factor for Inductive Load like compressor, heating pump, usually be 5~8;
• The factor for Resistive Load like Electric heating rod, Electric blanket
usually is 1.5 ~ 2;
• The factor for an Incandescent lamp usually is 15.
Configurations
Multi-language Video Tutorial on Youtube
Code and Function Menu
Hold the button for 3s to enter the menu list .
Code| Function|
Min
| Max| Default|
Unit
---|---|---|---|---|---
F1| Temperature Setpoint|
-50.0
|
99.9
|
10.0
|
°C
F2| Temperature Hysteresis / Return Difference|
0.3
|
10.0
|
0.5
|
°C
F3| Protection Delay Time for Refrigerator|
1
|
10
|
3
|
Min
F4| Temperature Calibration|
-10.0
|
10.0
|
0
|
Hour
F1: Temperature Setpoint
It is the room temperature value users wish to keep around.
F2: Temperature Hysteresis / Return Difference Value
A. Switch to heating mode once found
Measured Temperature ≤ Temp Set-point – Return Difference
B. Switch to Refrigeration mode once found
Measured Temperature ≥ Temp Set-point + Return Difference But the compressor
will not start up until the compressor’s delay time is over.
F3: Compressor Delay Time:
The purpose of this value is to protect the compressor.
F4: Temperature Calibration
F4 = Real Temperature – Measured Temperature
How to Set Parameters?
Step1: Hold the for 3s to enter the menu list; the display shows the code
F1
Step2 : Press the or to select the code you want to update;
Step3: Press the to check the current value.
Hold the and press or key to change the value;
Step4: Release keys to back to function menu list.
Repeat operation from Step 2 / 3 / 4 to adjust other parameters;
Step5: After configuring all values, remember to press the for saving
data , and back to normal monitor status, the display shows the room sensor
temperature.
The modified value will be discarded and back to normal status if
without operation in 8 seconds.
When Will is the Load Works/Stops?
Loads | Startup Condition | Stop Condition |
---|---|---|
Refrigeration | Room Temp ≥ F1 + F2 and The instant period passed the delay | |
time (F3) | Room Temp ≤ F1 | |
Heating | Room Temp ≤ F1 – F2 | Room Temp ≥ F1 |
- Room Temp: Measured temperature value by the controller’s sensor.
- F2: Return difference Hysteresis.
- The instant period is counts from load stops last moment to the instant time;
Means, the time should be later than the compressor’s last stops moment + delay time.
Error & Solution
When an alarm occurred, the buzzer scream “di-di-di,” press any key to stop screaming; but the error code on display will not disappear until all the failures are resolved
Code | Reason | Troubleshooting |
---|---|---|
E1 | The memory unit broken | Press/key to restoring the default data or get |
factory reset.
EE| Sensor error| Ensure the sensor was installed firmly or replace a new
sensor, display back to normal in 10 seconds once the problem is fixed.
HH| Room temp. > 99.9°C| Check the room temperature and all loads, then stop
the loads from working manually if necessary.