sonbus SM6363B Small weather station shutters multi function sensor User Manual
- June 5, 2024
- SONBUS
Table of Contents
Sonbus SM6363B Small weather station shutters multi-function sensor
SM6363B uses the standard RS485 bus MODBUS RTU protocol, and easy access to PLC DCS and other instruments or systems for monitoring temperature, humidity, carbon dioxide, and atmospheric pressure state quantities. The internal use of high precision sensing core and related devices to ensure high.
reliability and excellent long term stability can be customized
RS232,RS485,CAN,4 20mA,DC0~5V 10V,ZIGBEE,Lora,WIFI,GPRS and other output
methods.
Technical Parameters
Technical parameter | Parameter value |
---|---|
Brand | SONBEST |
Temperature measuring range | -30℃~80℃ |
Temperature measuring accuracy | ±0.5℃ @25℃ |
CO2 range | 0~5000ppm |
CO2 accuracy | ±100ppm |
Atmospheric pressure range | 30~110kpa |
Atmospheric pressure accuracy | ±0.5% |
Communication Interface | RS485 |
Default baud rate | 9600 8 n 1 |
Power | DC9~24V 1A |
Running temperature | -40~80°C |
Working humidity | 5%RH~90%RH |
Product Size
How to wiring?
Application solution
How to use it?
Communication Protocol
The product uses RS485 MODBUS RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1
Read Data (Function id 0x03)
Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host
computer sends the command:01 03 00 00 00 04 44 09 .
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
01 | 03 | 00 00 | 00 04 | 44 09 |
For the correct query frame, the device will respond with data:01 03 08 00 7C 00 00 00 00 00 00 28 10 , the response format is parsed as follows:
Device ID| Function id| Data
Length
| Data 1| Data 2| Data 3| Data 4| Check
Code
---|---|---|---|---|---|---|---
01| 03| 08| 00 79| 00 7A| 00 7B| 00 7C| 28 10
Data Description: The data in the command is hexadecimal. Take data 1 as an
example. 00 79 is converted to a decimal value of 121. If the data
magnification is 100, the actual value is 121/100=1.21.
Others and so on.
Data Address Table
Address | Start Address | Description | Data type | Value range |
---|---|---|---|---|
40001 | 00 00 | temperature | Read Only | 0~65535 |
40002 | 00 01 | humidity | Read Only | 0~65535 |
40003 | 00 02 | carbon dioxide | Read Only | 0~65535 |
40004 | 00 03 | atmospheric |
pressure
| Read Only| 0~65535
40101| 00 64| model code| read/write| 0~65535
40102| 00 65| total points| read/write| 1~20
40103| 00 66| Device ID| read/write| 1~249
40104| 00 67| baud rate| read/write| 0~6
---|---|---|---|---
40105| 00 68| mode| read/write| 1~4
40106| 00 69| protocol| read/write| 1~10
- read and modify device address
- Read or query device address
If you don’t know the current device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
FA | 03 | 00 64 | 00 02 | 90 5F |
FA is 250 for the general address. When you don’t know the address, you can
use 250 to get the real device address, 00 64 is the device model register.
For the correct query command, the device will respond, for example, the
response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the
following table:
Device ID | Function id | Start Address | Model Code | CRC16 |
---|---|---|---|---|
01 | 03 | 02 | 55 3C 00 01 | 3A 79 |
Device ID | Function id | Start Address | Destination | CRC16 |
--- | --- | --- | --- | --- |
01 | 06 | 00 66 | 00 02 | E8 27 |
Device ID | Function id | Data Length | Rate ID | CRC16 |
--- | --- | --- | --- | --- |
01 | 03 | 02 | 00 03 | F8 45 |
Change the baud rate
For example, changing the baud rate from 9600 to 3 8400, ie changing the
code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64
15 .
Device ID | Function id | Start Address | Target Baud Rate | CRC16 |
---|---|---|---|---|
01 | 03 | 00 66 | 00 01 | 64 15 |
Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.
Read Correction Value
Read Correction Value
When there is an error between the data and the reference standard, we can
reduce the display error by adjusting the correction value. The correction
difference can be modified to be plus or minus 1000, t hat is, the value range
is 0 1000 or 64535 65535. For example, when the display value is too small, we
can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the
command 100 is hex 0x64 If you need to reduce, you can set a negative value,
such as 100, corresponding to the hexadecimal value ofFF 9C, which is
calculated as 100 65535=65435, and then converted to hexadecimal to 0x FF 9C.
The correction value starts from 00 6B. We take the first parameter as an
example. The correction value is read and modified in the same way for
multiple parameters.
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
01 | 03 | 00 6B | 00 01 | F5 D6 |
For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:
Device ID | Function id | Data Length | Data value | CRC16 |
---|---|---|---|---|
01 | 03 | 02 | 00 64 | B9 AF |
In the response data, the first byte 01 indicates the real address of the
current device, and 00 6B is the first state quantity correction value
register. If the device has multiple parameters, other parameters
operate in this way. The same, the general temperature, and humidity have this
parameter, the light generally does not have this item.
Change correction value
For example, the current state quantity is too small, we want to add 1 to its
true value, and the current value plus 100 correction operation command is:01
06 00 6B 00 64 F9 FD.
Device ID | Function id | Start Address | Destination | CRC16 |
---|---|---|---|---|
01 | 06 | 00 6B | 00 64 | F9 FD |
After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after a successful change.
Disclaimer
This document provides all information about the product, does not grant any
license to intellectual property, does not express or imply, and prohibits any
other means of granting any intellectual property rights, such as the
statement of sales terms and conditions of this product, other issues. No
liability is assumed. Furthermore, our company makes no warranties, express or
implied, regarding the sale and use of this product, including the suitability
for the specific use of the product, the marketability or the]infringement
liability for any patent, copyright or other intellectual property rights,
etc. Product specifications and product descriptions may be modified at any
time without notice.
Contact Us
- Company: Shanghai Sonbest Industrial Co., Ltd
- Address: Building 8, No.215 Northeast road, Baoshan District, Shanghai, China
- Web: http://www.sonbest.com
- Web: http://www.sonbus.com
- SKYPE: soobuu
- Email: sale@sonbest.com
- Tel: 86 021 51083595 / 66862055 / 66862075 / 6686107
References
- Home-上海æœåšå®žä¸šæœ‰é™å…¬å¸
- Home-SONBEST -SONBUS.COM| THE SENSOR COMPANY
- Home-SONBEST -SONBUS.COM| THE SENSOR COMPANY
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>