Sensata FREQCON-6 24V AC or DC Powered Isolating Signal Converter User Manual
- June 3, 2024
- Sensata
Table of Contents
FREQCON-6 24V AC or DC Powered Isolating Signal Converter
User Manual
Whilst every effort has been taken to ensure the accuracy of this document, we
accept no responsibility for damage, injury, loss, or expense resulting from
errors or omissions, and reserve the right of amendment without notice.
This document may not be reproduced in any way without the prior written
permission of the company.
Aug 2022
INTRODUCTION
1.1 Hardware Features
The FREQCON-6 is a Frequency to Analog Signal Converter. It supports a wide
range of signal inputs, from Hall effect transducers to +-24V signals. It also
produces 3 types of analog output: voltage, mA source, or mA sink.
The unit can be powered by any DC voltage between 12 and 36Vdc or 12 and
32Vac.
The instrument is packaged in a very compact 12.5mm wide enclosure which can
be mounted on a standard TS35 DIN rail.
1.2 Isolation Details
The FREQCON-6 has full 3 port isolation of 1000V between the Input Stage,
Output Stage, and Power Supply for functional reasons.
UNPACKING
The instrument should be carefully inspected for signs of damage that may have
occurred in transit. In the unlikely case that damage has been sustained, DO
NOT use the instrument, but please retain all packaging for our inspection and
contact your supplier immediately.
The instrument comes with the following items as standard:
1 Freqcon-6 Isolating Signal Converter
1 Freqcon-6 User Guide
If the instrument has been factory configured the input and output details
will be listed on the Serial number label on the side of the unit. If this
label is blank, then the unit will be set to its default configuration which
is 0-10kHz logic level input and 4-20mA source output. Please check that the
details on the side label are correct, especially the power supply voltage.
If re-configuration is required, please refer to Section 4 of this manual.
CONNECTIONS
The FREQCON is housed in a compact DIN rail mounting enclosure, with 8
terminals, arranged in 4 rows of 2 terminals. Two rows are at the top of the
front panel and 2 rows are at the bottom. All the sensor input terminals are
on the bottom rows and the power supply and analog outputs are on the top
terminals.
The diagram below shows how to connect all the different input, output, and
power supply types.
CONFIGURING THE FREQCON
WARNING!
DO NOT OPEN THE UNIT OR ADJUST SWITCHES WITH THE POWER SUPPLY, INPUT, OR
OUTPUT CONNECTED
The FREQCON is an extremely versatile device that can support many different
types of frequency input. The unit is configured by turning the power off,
selecting the internal switch settings required, and turning the power back
on.
To open the Freqcon, 2 catches just below the outer terminal blocks must be
pushed in gently, one at a time. The front of the case can then be pulled and
the unit will come out of the box. There are 2 switch banks, S1 and S3, located inside the
FREQCON as shown below:
Switch S1 configures the input type and range and switch S3 configures the
output type, range, and a few additional functions. The switch settings are
explained in the next few pages. The diagrams refer to switch positions 0 and
1, with 0 being OFF and 1 being ON. This is illustrated in the picture above.
4.1 Frequency Input
Select the range from the table below and set Switch S1 to the required
values. Switches 1 to 8 control the input type, while switches 9 to 12 control
the input frequency range.
Input Frequency (Hz) | Switch S1 |
---|---|
1 | 2 |
10 | 11 |
0 to 0.01
0 to 0.03
0 to 0.1
0 to 0.3| | | | | | | | | 0
1
0
1| 0
0
1
1| 0
0
0
0| 0
0
0
0
0 to 1
0 to 3
0 to 10
0 to 30| | | | | | | | | 0
1
0
1| 0
0
1
1| 1
1
1
1| 0
0
0
0
0 to 100
0 to 300
0 to 1000
0 to 3000| | | | | | | | | 0
1
0
1| 0
0
1
1| 0
0
0
0| 1
1
1
1
0 to 10000
0 to 30000
0 to 100000
0 to 250000| | | | | | | | | 0
1
0
1| 0
0
1
1| 1
1
1
1| 1
1
1
1
WARNING!
DO NOT OPEN THE UNIT OR ADJUST SWITCHES WITH THE POWER SUPPLY, INPUT OR
OUTPUT CONNECTED
Please note that PC Software is available to provide information on switch
settings for your input and output requirements.
4.2 Input types
Select the range from the table below and set Switch S1 to the required
values.
Input Type | Switch S1 |
---|---|
1 | 2 |
10 | 11 |
TTL Logic
2 Wire Proximity
Switch Contact
NPN transistor
PNP transistor
Mag Pickup| 0
0
1
0
0
1| 0
0
1
0
0
0| 0
0
0
0
1
0| 0
1
0
0
0
0| 0
0
0
0
0
0| 0
0
0
1
0
0| 1
1
1
1
1
0| 0
0
0
0
0
0| | | |
The switching threshold can be adjusted to allow smaller signals to be picked up and counted. S1 switches 5 and 7 control this. The threshold voltage in the table below indicates the voltage level at input terminal 9 that the signal must exceed for it to be counted and the frequency calculated.
5 | 7 | Threshold |
---|---|---|
Off | On | 0.25 V |
Off | Off | 4.00 V |
On | On | 0.10 V |
On | On | 2.08 V |
+8V transmitter supply is always available on input 10. Switch 8 will increase
the transmitter supply to +24V.
WARNING!
DO NOT OPEN THE UNIT OR ADJUST SWITCHES WITH THE POWER SUPPLY, INPUT OR OUTPUT
CONNECTED
Please note that PC Software is available to provide information on switch
settings for your input and output requirements.
4.3 Averaging and Stepchange Adjustment
Averaging and step change are controlled by the pots situated next to
S1: 4.4 Averaging
Fully counterclockwise: Averaging off
Fully clockwise: Averaging over 45 seconds approx.
Averaging is performed by storing a running total of the previous samples,
adding the new sample value to this running total, then dividing by the total
number of samples to get the average. The oldest sample is then subtracted
from the running total. When a step change occurs, the running total is reset
to 0, so that averaging can recommence at the new level.
The pot level must be set when the power is off. The pots are read at power
up.
4.5 Stepchange
Fully anticlockwise : 0%
Fully clockwise: 100%
- At 0%, a step change will occur if the change in frequency is greater than 0% of the full scale. Since this is true for every change in frequency, step change will occur instantly, negating the effects of averaging.
- At 50%, a step change will occur if the change in frequency is greater than 50% of full scale.
- At 100%, a step change will occur if the change in frequency is greater than 100 % of full scale. Since this is impossible, step change is off when this pot is fully clockwise.
Example: 0 to 10,000 Hz input range, 50% step change, average over last
100 samples.
Input is 8,000 Hz and drops to 4,000 Hz. No step change will occur because the
fall was 4,000Hz which is only 40% of the full scale, the new 4000 Hz value
will be averaged into the current running total.
Example 2: 0 to 10,000Hz, 50% stepchange
Input 8,000Hz drops to 2500Hz. Stepchange occurs and output changes
immediately. Averaging starts again at 2500 Hz
The pot level must be set when the power is off. The pots are read at power
up.
4.6 Interaction
There is an interaction between step change and averaging. If the frequency
changes by more than the step change value causing a step change, the number
of samples the new frequency is averaged over will be reset to 0, causing a
less averaged interpretation of the input frequency for a few seconds until
enough new samples have been taken to average the current reading against.
If averaging is on and step change is at 0%, averaging will not work because
the step change will happen every time the frequency changes, causing the
values used to calculate the average to be reset each time.
4.7 Output Configuration
Select the range from the table below and set Switch S3 to the required
values.
Examples:
Switch S3 Examples
| 1| 2| 3| 4| 5| 6| 7| 8| 9|
10| 11| 12
4-20mA Source
0-20mA Source
0-10V
4-20mA Sink| 1
1
1
1| 0
0
0
1| 1
1
1
0| 0
0
0
1| 1
1
1
0| 0
0
1
0| 0
0
0
0| 0
0
0
0| 0
0
0
0| 0
0
0
0| 0
0
0
0| 0
1
1
0
WARNING!
DO NOT OPEN THE UNIT OR ADJUST SWITCHES WITH THE POWER SUPPLY, INPUT OR
OUTPUT CONNECTED
Please note that PC Software is available to provide information on switch
settings for your input and output requirements.
CALIBRATING THE FREQCON
When the unit is shipped the FREQCON will be calibrated for the input and
output types and ranges noted on the side label. If this label is blank, then
the unit will be calibrated for 0-10kHz logic level input and 4-20mA source
output.
If the unit is re-ranged by the user, it is necessary to re-calibrate the unit
to obtain maximum accuracy. The calibration is achieved by using both switches
on the front panel to select the zero or span input and then using the
switches as raise/lower buttons to adjust the output to the value required.
The mode the unit is in is indicated by the color of the LED:
Green | Normal Operation |
---|---|
Red | Span Adjust |
Yellow | Zero Adjust |
The setting of the zero and span points is non-interactive, so each point needs only be set once. A typical calibration sequence would be as follows:
LED Colour | Mode | Action |
---|---|---|
Green | Normal | Apply full-scale input. |
Press and release both buttons together to enter span mode
RED| Span Adjust| Press the raise / lower buttons to adjust the output value
Press and release both buttons together to return to normal mode
Green| Normal| Apply zero-scale input
Press and release both buttons together to enter zero mode
YELLOW| Zero Adjust| Press the raise / lower buttons to adjust the output
value
Press and release both buttons together to return to normal mode
Green| Normal| Use product
The unit is now calibrated and ready for use.
Note: The unit will retain the new settings on power down.
INSTALLATION
The FREQCON input and output circuits are classed as Separated Extra Low
Voltage (SELV). This means that they must not be externally connected to
voltages exceeding 30V ac or 60V dc, nor do they generate voltages above these
limits internally. Where a higher voltage input is required a specially
designed DIVIDER unit can be used to condition the input signal before
connection to the process input terminals.
The FREQCON unit clips directly onto the ‘Top Hat’ (TS35) symmetrical DIN
rail. Ideally, the mounting orientation should be vertical, with the power
supply situated on the top face to minimize temperature rise. Good airflow
around the unit will maximize the reliability of the instrument.
The use of bootlace ferrules is recommended for wiring terminations.
Do not exceed the terminal torque rating of 0.4 Nm – use an appropriate
screwdriver. The unit can be removed from the DIN rail by sliding a small
screwdriver into the slot at the rear of the enclosure on the lower face and
gently levering the metal clip, whilst lifting the unit from the rail.
TROUBLESHOOTING
The FREQCON has some built-in self-diagnostic functions. If the LED on the front panel is flashing, then the fault mode can be found by counting the number of flashes between gaps and using the table below to locate the problem.
No of Flashes | Nature of Fault | Corrective Action |
---|---|---|
0 (Green On) | Unit Working – no suspected fault | Check Wiring and switch |
settings
2,3,4,5,6,8,9,10,11,12 green| Hardware Error, extreme noise, poor supply|
Switch off the unit, check the switch settings, and wiring, and retry. If
still faulty, please contact the supplier
7 green| Frequency out-of-scale burnout| Reduce frequency
3 or 4 Red| The span point is too close to the zero point| Change input span
value and retry
3 or 4 Yellow| Zero point is too close to the spawn point| Change input zero
value and retry
No LED| Power Failure| Check supply lines and voltage
7.1 Incorrect Reading
- Check that Unit is configured for the correct Sensor
- Check that Input Scaling is as required.
- Check that Linearisation has not been set incorrectly.
7.2 Sensor Failure
- Check that the sensor wiring is correct.
- Check that the FREQCON is configured for the correct sensor.
- Check that frequency is not out of range.
SPECIFICATIONS ( @ 25°C)
Operating Temperature | 0 to 55 °C |
---|---|
Operating Altitude | Sea Level to 2000m |
Humidity | 0-90% RH |
Power Requirements | 12 to 36Vdc |
12 to 32Vac
Current Consumption| 110mA @ 24Vdc (NPN O/C in, 20mA out)
109mA @ 24Vdc (TTL logic in, 20mA out)
Transmitter Power Supply| 8V or 22V to 29V @ up to 24mA
Depending on the supply voltage and load
Calibration accuracy| ±0.01% full scale
Linearity| ±0.01% full scale
Temperature Stability| 27ppm / °C
Maximum Voltage Output| 11.5 V into a minimum of 7Kohm
Maximum Current Output| 23.0 mA into a maximum of 1Kohm
Time Response (90% of a step change)| 50ms ± 10ms
The unit has full 3 port Isolation to 1kV between Power Supply, Input, and
Output.
The unit can also withstand transients of 2.5kV for 50 µsecs.
Dimensions| 114.5 mm x 99mm x 12.5mm (H x D x W)
Mounting| DIN Rail TS35
Connections| Screw Clamp with pressure plate
Conductor Size| 0.5 to 4.0 mm
Insulation Stripping| 12 mm
Maximum Terminal Torque| 0.4 Nm
Weight| Approx. 95g
EMC Emissions| EN50081-1:1992
EMC Immunity| EN50081-2:1993
LVD Standards| EN50082-1:1997
Installation Category (IEC 664)| EN61010-1:1993
Pollution Degree (EN61010-1:1993)| II
Equipment Class (IEC 536)| II
220808
Documents / Resources
|
Sensata FREQCON-6 24V AC or DC Powered Isolating Signal
Converter
[pdf] User Manual
FREQCON-6 24V AC or DC Powered Isolating Signal Converter, FREQCON-6, 24V AC
or DC Powered Isolating Signal Converter, Isolating Signal Converter, Signal
Converter, Converter
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>