Sensata ISOSLICE-6 4 Output Relay Isoslice Unit Owner’s Manual
- June 3, 2024
- Sensata
Table of Contents
Sensata ISOSLICE-6 4 Output Relay Isoslice Unit Owner’s Manual
Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss, or expense resulting from errors or omissions, and reserve the right of amendment without notice.
This document may not be reproduced in any way without the prior written permission of the company
Isoslice-6
This isoslice unit has 4 relay outputs.
Channel Number
The channel number is set up using the 8-way dipswitch.
Address Switch | Action |
---|---|
8 | add 1 |
7 | add 2 |
6 | add 4 |
5 | add 8 |
4 | add 16 |
3 | add 32 |
2 | add 64 |
1 | is not used |
Switches
1 = On, 0 = Off
Channel | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
---|---|---|---|---|---|---|---|
1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
2 | 0 | 0 | 0 | 0 | 0 | 0 | 1 |
3 | 0 | 0 | 0 | 0 | 0 | 1 | 0 |
4 | 0 | 0 | 0 | 0 | 0 | 1 | 1 |
5 | 0 | 0 | 0 | 0 | 1 | 0 | 0 |
6 | 0 | 0 | 0 | 0 | 1 | 0 | 1 |
7 | 0 | 0 | 0 | 0 | 1 | 1 | 0 |
8 | 0 | 0 | 0 | 0 | 1 | 1 | 1 |
9 | 0 | 0 | 0 | 1 | 0 | 0 | 0 |
10 | 0 | 0 | 0 | 1 | 0 | 0 | 1 |
11 | 0 | 0 | 0 | 1 | 0 | 1 | 0 |
12 | 0 | 0 | 0 | 1 | 0 | 1 | 1 |
13 | 0 | 0 | 0 | 1 | 1 | 0 | 0 |
14 | 0 | 0 | 0 | 1 | 1 | 0 | 1 |
15 | 0 | 0 | 0 | 1 | 1 | 1 | 0 |
16 | 0 | 0 | 0 | 1 | 1 | 1 | 1 |
Led Control
There are 4 LEDs to indicate the state of the individual relays. The action of
these LEDs is controlled by the 4-way dip switch. By default, the LED will be
on when the relay is energized, when the corresponding dipswitch (switch 1 is
relay 1, etc.) is in the off position.
Individual LED actions can be reversed by switching the corresponding
dipswitch on.
Connections
- 7. Relay 4 NO
- 8. Relay 4 NC
- 12. Relay 4 COM
- 5. Relay 3 NO
- 6. Relay 3 NC
- 11. Relay 3 COM
- 1. Relay 1 NO
- 2. Relay 1 NC
- 9. Relay 1 COM
- 3. Relay 2 NO
- 4. Relay 2 NC
- 10. Relay 2 COM