Emerson XMC25D COPELAND LARGE OUTDOOR REFRIGERATION UNITS Installation Guide

June 5, 2024
Emerson

XMC25D COPELAND LARGE OUTDOOR REFRIGERATION UNITS
Installation Guide

  1. Install the refrigeration unit according to Application Guidelines AGL_Unit_LOCU_EN “Copeland™ Large Outdoor Refrigeration Units”.
  2. Prefill the unit with refrigerant and set all valves into the operating position.
  3. Set up the unit controller (XMC25D) for the required application.

NOTE: The value of parameter D29 must be lower than the value C16-C17/2 (unit switching-off point) to avoid the low-pressure alarm.
The XMC25D controller provides 2 programming levels:

  1. Pr1 with direct access
  2. Pr2 is protected with a password (intended for experts)

Explanation of LED functionalities

LED Mode Function
On Compressor 1 enabled
Flashing Anti-short cycle delay enabled
On Condensing fans enabled
On Display in bar
Flashing Programming mode
On Display in PSI
Flashing Programming mode
On When browsing the service menu
Flashing In fast access menu
On When browsing the Alarm menu
Flashing A new alarm occurred
On An alarm is occurring
On Digital unloader solenoid On

How to program the “Pr1” parameters

Access pre-
program level| | Press simultaneously for about 3 seconds to access the pre- programming level. The message rtC (real time clock) is displayed.
---|---|---
Access
program level| | Use the UP and DOWN keys to switch to the Par label.
Access Pr1| | Press the SET key to enter programming level 1. The first parameter CO1 is displayed.
Select item| | Select a parameter or submenu using the arrows.
Show value| | Press the SET key.
Modify| | Use the arrows to modify the value.
Confirm and
store| | Press the SET key: the value will blink for 3 seconds, then the display will show the next parameter.
EXIT| | Press simultaneously to exit the programming mode or wait for 30 seconds without pressing any key.

The following “Pr1” parameters must be verified before commissioning:

Parameter| Description 111111| Unit| Factory settings| Comments
---|---|---|---|---
OMTE| OLE| OLTE
C01| Com pressor cut-in pressure setpoint| bar| | 1.0| –| Only for OLE-49 units
CO2| Compressor cut-out pressure setpoint| bar
| –| 0.5| –| Only for OLE-49 units
C07| Refrigerant selection for regulation| –| R449A| R404A, R134A, R407A, R407F, R407C, R448A, R449A, R507
C16| Digital compressor setpoint| bar| 3.| –| 1.0| For digital units
C17| Proportional band for compressor regulation| bar
| 2.0| –| 1.0| For digital units
C21| Cycle time for digital compressor| sec| 20| –| 20| For digital units
C24| Minimum capacity for digital compressor| ok| 20| –| 30| For digital units
C25| Maximum capacity for digital compressor| %| 100| –| 100| For digital units
D29| Low-pressure alarm value| bar*| 0.5| 0.0| 0.0|
0.00E+00| Maximum fan motor speed| ok| 85| 80| 80|
0.00E+00| Delta temperature condenser floating setpoint| °C| 8| 8| 8|
T18| Access to Pr2 level| –| Password:3 2 1|

  • Pressure values are always relative

Time and date (Pr2 Level) have to be adjusted before commissioning:

Parameter| Description| Factory I
settings| Range
---|---|---|---
NO1| Current minutes| | 0 to 59
NO2| Current hours| | 0 to 23
NO3| Day of the month| | 1 to 31
N04| Month| | 1 to 12
N05| Year| | 0 to 99

NOTE: Error L21 can happen during the first commissioning. This lockout indicates a wrong phase sequence.
In this case, two phases at the power supply terminals must be changed.
NOTE: This guide is for quick installation purposes. For detailed instructions, please refer to Application Guidelines AGL_Unit_LOCU_EN “Copeland™ Large Outdoor Refrigeration Units”.

  • The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding
    the products or services described herein or their use or applicability.

  • Emerson Climate Technologies GmbH and/or its affiliates (collectively “Emerson”), as applicable, reserve the right to modify the design or specifications of such
    products at any time without notice.

  • Emerson does not assume responsibility for the selection, use, or maintenance of any product. Responsibility for proper selection, use, and maintenance of any
    Emerson’s product remains solely with the purchaser or end-user.

  • Emerson does not assume responsibility for possible typographic errors contained in this publication.

TI_Unit_LOCU_02_EN_Rev01

Documents / Resources

| Emerson XMC25D COPELAND LARGE OUTDOOR REFRIGERATION UNITS [pdf] Installation Guide