STELPRO SECM SERIES HEATING CABLE MAT Installation Guide
- June 5, 2024
- StelPro
Table of Contents
INSTALLATION GUIDE
SECM SERIES
HEATING CABLE MAT
WARNING
Before installing and operating this product, the user and/or installer must
read, understand and follow these instructions and keep them handy for future
reference.
If these instructions are not followed, the warranty will be considered null
and void, and the manufacturer deems no further responsibility for this
product. The following instructions must be adhered to in order to avoid
serious injury or property damage and potentially fatal electric shocks. This
product must be installed by a qualified person in accordance with this
installation guide. All electric connections must be made by a qualified
electrician, according to the electrical (Canadian Electrical Code Part 1 or
National Electrical Code) and building codes effective in your region. Cut off
power supply at circuit breaker/fuse before installation or making repairs.
The maximum current rating of the circuit breaker or fuse of the branch
circuit supplying this product must be limited to 20 amps. This heating cable
mat has a usage marking W and X and is designed for indoor embedded floor
heating applications in which the heating section of the cable, including the
cable connection joint, is completely embedded in concrete. It is usable in a
dry or wet environment. Never use this mat for any other purpose.
The mat must not exceed the size of the room or space where it will be used as
a primary heating source. The heating section of the mat must not pass through
or be installed in a wall.
A floor-warming thermostat along with its specified temperature sensor must be
installed and connected with this product.
This heating cable mat must be grounded and connected to a ground fault
circuit interrupter (GFCI). The GFCI must be Class A (5 mA) for a bathroom or
a
shower.
A 6 in (150 mm) spacing must be maintained between the mat and any plumbing
drain or non-heating duct and obstacles to avoid. The minimum temperature for
heating cable mat installation is 0°C. The minimum radius of curvature of the
mat is 13 mm (½ in).
NEVER CUT THE HEATING CABLES WITHIN THE MAT. This would change the cable
resistance and could lead to a fire. The mat must be laid flat and must not be
folded over itself. If the installer or user modifies the unit, they will be
held responsible for any damage resulting from this modification and the
warranty and CSA certification
will be void. Never energize the heating cable mat while it is rolled. This
would lead to overheating which could damage the mat and may cause a fire.
During manipulation of the mat, avoid folding the heating cable mat on itself
with force – this could damage its sheath and the internal wires.
Note: When a part of the product specification must be changed to improve operability or other functions, priority is given to the product specification itself. In such instances, the instruction manual may not entirely match all the functions of the actual product. Therefore, the actual product and packaging, as well as the name and illustration, may differ from the manual. Make sure that the connections have been made safely and securely. Pull on each wire to ensure that it is firmly embedded in the connector or terminal block. Failing to follow these instructions may cause a fire hazard.
THANK YOU FOR CHOOSING THE °STELPRO FLOOR HEATING SYSTEM
This guide has been written to guide you during the installation of your floor
heating system. It has been prepared according to North American construction
standards. Because construction standards vary from one area to another,
consult a certified electrician in your region before installing the floor
heating system.
The floor heating system is designed to heat a room with a heating cable mat
embedded in concrete with or without floor covering. It can heat floor
covering materials such as marble, ceramic and porcelain tiles, slate,
granite, as well as poured surfaces. Before using the floor heating system
under any other floor covering, contact your floor covering
manufacturer. Do not cover the floor where a heating cable has been installed
with a mat.
The floor heating system will heat your house regardless of the size or shape
of the room. If, however, the room has a much greater heat loss than normal,
like a solarium, or has little free floor space, like a tightly furnished
bathroom, you may need an additional heat source.
This product is designed for indoor use only, in residential, commercial, and
institutional buildings. The SECM floor heating system is available in heating
cable mat sets of 240 volts (see the SELECTION TABLES). The standard heating
density is 12 W/square foot (129 W/m²).
The 240 volts models can be electrically supplied at 208 volts, but the
heating density will be reduced to 9 W/square foot (97 W/m²). To complete the
installation, °STELPRO provides a temperature sensor with the heating cable
mat set. Installation instructions for the mat and temperature sensor are
provided further in this guide. It is important to
connect the sensor to the heating cable thermostat. Please note that you must
install the sensor before the concrete, even if you haven’t bought the
thermostat yet.
It is also recommended that you install two sensors (the sensor provided with
the thermostat and the sensor provided with the mat) in case one of them is
damaged during installation. Only one sensor can be connected to the
thermostat.
WHAT YOU SHOULD KNOW
CATALOG NUMBER DESCRIPTION
The SECM series heating cable mat part numbers inform you of the following
parameters: surface, voltage and wattage.
EXAMPLE: Catalog #: SECM2W0400S033
Voltage: SECM2: 240 V
W0400: Power: 400 watts
S033: 33 square feet
240 VOLTS
| DIMENSIONS (FT)| AREA| POWER| CURRENT
CATALOG NO.| LENGTH| WIDTH| SQ. FT| WATTS| AMPS
SECM2W0150S012| 2| 6.25| 12| 150| 0.63
SECM2W0300S025| 2| 12.5| 25| 300| 1.25
SECM2W0400S033| 2| 16.7| 33| 400| 1.67
SECM2W0500S042| 2| 20.8| 42| 500| 2.08
SECM2W0600S050| 2| 25| 50| 600| 2.50
SECM2W0750S063| 2| 31.3| 63| 750| 3.13
SECM2W0850S071| 2| 35.4| 71| 850| 3.54
SECM2W1000S083| 2| 41.7| 83| 1000| 4.17
SECM2W1100S092| 2| 45.8| 92| 1100| 4.58
SECM2W1250S104| 2| 52.1| 104| 1250| 5.21
SECM2W1375S115| 2| 57.3| 115| 1375| 5.73
SECM2W1500S125| 2| 62.5| 125| 1500| 6.25
SECM2W1750S146| 2| 72.9| 146| 1750| 7.29
SECM2W2000S167| 2| 83.3| 167| 2000| 8.33
SECM2W2250S188| 2| 93.8| 188| 2250| 9.38
SECM2W2400S200| 2| 100| 200| 2400| 10.00
SECM2W2500S208| 2| 104.2| 208| 2500| 10.42
SECM2W2625S219| 2| 109.4| 219| 2625| 10.94
SECM2W2750S229| 2| 114.6| 229| 2750| 11.46
SECM2W2875S240| 2| 119.8| 240| 2875| 11.98
SECM2W3000S250| 2| 125| 250| 3000| 12.50
SECM2W3250S271| 2| 135.4| 271| 3250| 13.54
SECM2W3500S292| 2| 145.8| 292| 3500| 14.58
REQUIRED TOOLS:
– Measuring tape | Thermostat temperature sensor |
---|---|
– Wire stripper | Cable ducts |
– Screwdriver | Adhesive tape |
– Multimeter/ohmmeter | Duct tape |
– 1000 V megohmmeter (megger) | Scissors |
MATERIAL PROVIDED:
– Heating cable mat | – Label to affix in the electrical box |
---|---|
– Plastic clips | – Temperature sensor |
– Warranty card
VALIDATING YOUR FLOOR HEATING CABLE MAT AND THERMOSTAT SELECTION
AREA TO HEAT
Before installing your new floor heating system, make sure you have selected
the right heating cable mat. Re-measure the area that will accommodate the
mat(s) in your room:
– Do not forget to exclude all areas that cannot be heated (cupboards,
bathtub, etc.), as well as all areas that you do not want to heat.
The following clearances must be respected when choosing the mat for the room:
A 3 in. (75 mm) spacing between the heating cable mat and the surrounding
walls and 6 in. (150 mm) from outer walls
A 8 in. (200 mm) spacing between the heating cable and all other heat sources
and heating ducts
A 6 in. (150 mm) spacing from any drain or fixed obstacle to be bypassed
A 3 in. (75 mm) spacing between cables at all time.
A 1 ½ in. (40 mm) distance from the concrete surface
A ½ in. (13 mm) distance from any open combustible surface
– Compare the area to be heated with the total area covered by the selected
mat(s). It is better to use a mat that is a bit smaller rather than a mat that
is too big, which may cause problems. If more than one mat is used to fit the
room, the total current must not exceed 20 amps per circuit.
– It is recommended to draw the mat layout on a sheet of paper before
starting.
In Canada only: The heating cable mat can be installed under the floor
covering of a shower floor fabricated on site with a mortar base. The mat can
be installed under or over the waterproof membrane but must be embedded in
mortar. Although the code allows installation of the mat either under or above
the waterproof membrane, °STELPRO recommends installing the mat under the
membrane to minimize water exposure.
In the United States: If the heating cable mat is being installed in a shower
floor fabricated on site, it must be located under the waterproof membrane and
embedded in the mortar base.
THERMOSTAT SELECTION
A floor warming thermostat along with its specified temperature sensor must be
installed and connected with this product. Only a thermostat equipped with a
floor sensor maximizes the floor heating system’s efficiency and, therefore,
your comfort. All other control methods (ambient-air only thermostat or
switch) are not to be used, since the floor could overheat and cause damage to
the system. °STELPRO’s heating cable mats and thermostats are each supplied
with a temperature sensor that needs to be embedded in concrete along with the
mat. It is recommended that both sensors be installed in case one is damaged
during the installation of the heating system. The heating cable mat must be
connected to a ground-fault circuit interrupter (GFCI), either integrated in
the thermostat or panel mounted. For a bathroom or shower, the GFCI circuit
must be Class A (5 mA). Floor warming or heating cable thermostats supplied by
°STELPRO have an integrated GFCI built in. The maximum thermostat current must
correspond to the sum of mat currents wired to it. The maximum allowable
current for a °STELPRO floor warming thermostat is 16 amps. Also, the voltage
of the branch circuit must correspond to the voltage prescribed for the
thermostat. All thermostats wired to the heating cable mat must be certified
by a recognized certification agency and wired in accordance with electrical
and building codes applicable in your region.
LOCATION OF THE INSTALLED THERMOSTAT AND TEMPERATURE SENSOR
Make sure the thermostat is installed in the same corner of the room as the
mat power lead cables:
– The mats can be installed in any direction.
– The standard length of the power lead cables is 10 ft (3 m).
Plan the location of the thermal sensor(s) between two cable runs of the mat
at a distance of at least 24 in. (60 cm) from the wall. The sensor(s) should
be installed in an area where the temperature will reflect the overall
temperature of the floor. Therefore, it should not be located in areas likely
to alter the temperature measurement, like a doorway, an external heat source,
or an area exposed to the sun. Make sure the sensor wire does not overlap the
heating cable. (We recommend the installation of two sensors. Only one sensor
can be connected to the thermostat.)
REQUIRED TESTS AND WARRANTY CARD
INTRODUCTION – IMPORTANCE OF THE REQUIRED TESTS
WARNING!
The warranty booklet must be FILLED OUT and RETURNED to °STELPRO for the warranty to be activated. Otherwise,
THE WARRANTY WILL NOT BE ACTIVATED OR VALID.
ALL REQUIRED INFORMATION AND UNDERTAKEN TESTS MUST BE RECORDED- ED IN
THE BOOKLET. Please refer to the installation manual for a detailed
description of the tests and the required material. Contact Customer Services
as needed. You also can fill out the warranty card on our website:
www.stelpro.com/warranty
Each mat is subject to factory quality control. However, several operations
may compromise its integrity, starting from the moment you unpack the mat to
the first start-up. In order to ensure that the mat is not damaged during its
installation and/or manipulation and for warranty purposes, electrical tests
must be conducted while the mat is still in its sealed bag and during two
specific subsequent steps. Do not install a heating cable mat if the seal is
broken.
Measurements must be recorded in the warranty card and be compared to initial
measurements taken when the mat was in the sealed bag to enable you to detect
any changes related to the electrical properties of the heating cables in the
mat.
Since it could be very expensive to repair the mat once it is embedded in
concrete, it is crucial to detect any breaks that may occur during the
installation process as soon as possible. Therefore, it is important to
conduct the required ohm readings when prescribed.
If the mat’s heating cables get damaged during installation, you must call a
qualified repair technician suggested by °Stelpro. To do so, call Stelpro
Customer Service or consult the website
(www.stelpro.com). Any installation-related heating
cable mat damages are not covered by the warranty.
CHRONOLOGICAL ORDER OF THE REQUIRED TESTS
FIRST SERIES OF TESTS (1, 2, and 3): While the mat is still in the bag
SECOND SERIES OF TESTS (1, 2, and 3): After the installation of the mat and
before the concrete pouring
THIRD SERIES OF TESTS (1, 2, and 3): After the concrete has been poured and
has cured completely
TESTS 1, 2 AND 3
TEST # 1: CONDUCTORS’ RESISTANCE TEST
This test requires the use of an ohmmeter or multimeter.
N.B. Since all measuring instruments are different, we recommend you consult
the resistance measurement section of your instrument’s user guide.
TIPS
Using a manual range multimeter:
The selected range must correspond to the multimeter’s lowest ohm range that
encompasses the mat’s nominal ohm value.
In order to perform the resistance test, you must set your multimeter at the
“Ohm” or “Ω” setting and take a resistance measurement between the two power
leads (BLACK AND RED). If the ohm reading taken on the two power leads varies
significantly, the lowest value from ±10 ohms or 10% of the nominal value
printed on the mat’s tag either means the mat has been damaged or the
measuring instrument is not set properly, or is simply out of calibration. The
ohm measurement must be recorded on your warranty card. If measurements are
different than the ones taken at the factory, do not install the cable and
contact customer service.
TEST # 2: CONTINUITY TEST BETWEEN THE CONDUCTORS AND THE GROUND BRAID
This test requires the use of a multimeter.
N.B. Since all measuring instruments are different, we recommend you consult
the resistance measurement section of your instrument’s user guide.
The mat’s heating cables are protected by a ground braid. An electrical
insulator prevents any contact between the braid and the conductor. To verify
that there is no continuity between the braid and the conductor, you must
perform a resistance test. Select the highest resistance measurement setting
on your multimeter to begin and diminish as required or select “Ohm” or “Ω” if
your multimeter has auto ranging. Measure the resistance between the ground
cable (GREEN) and one of the two power leads (BLACK OR RED). If there is no
continuity or no contact between the two (if the test is successful), the
multimeter will display either “OL” for “overload” or “I” for “Infinity,”
depending on the instrument used. If the test fails, neither “OL” nor “I” will
be displayed and you will have a number reading. The test result must be
recorded on your warranty card.
TEST # 3: INSULATION RESISTANCE TEST (CAPACITY OF THE CABLE ELECTRICAL
INSULATOR TO PREVENT CURRENT LEAKAGE)
CAUTION: HIGH VOLTAGE TESTING
This test requires the use of a 1000 V megohmmeter.
N.B. Since all megohmmeters are different, we recommend you consult your
instrument’s user guide.
This test is meant to detect breaks throughout the conductor insulation of
each mat’s heating cable. These breaks often remain undetected during the
continuity test, since they are not necessarily short circuits between each
conductor and the ground braid. These breaks are likely to cause a current
leakage to the ground. Such leakage is usually detected by the mandatory
ground fault circuit interrupter “GFCI” (thermostat with integrated GFCI or
panel-mounted GFCI). When excessive current leakage is detected, the GFCI
trips the circuit, disabling the floor heating system.
In order to perform the insulation resistance test using a megohmmeter (Mohm
logo), you must take an insulation measurement between the ground cable
(GREEN) and one of the two power leads (BLACK OR RED). Make sure the applied
voltage of the megohmmeter is set at 1000 V. The insulation resistance
measurement must be equal to or greater than 1 gigaohm (1 gigaohm = 1 G ohm =
1000 M ohms = 1000 megaohms). The insulation resistance measurement must be
recorded on your warranty card.
INSTALLATION
SUBFLOOR PREPARATION
°STELPRO recommends installing the heating cable set on rigid thermal
insulation 2 in. thick with an RSI coefficient of 7.5 to 10 R to minimize heat
loss. The panels can be jointed using a tongue and groove method or with
adhesive tape. Make sure that the joints are solid and that the panels cannot
move.
The surface must be clean of any dust, debris, protruding nails, screws, or
others that could damage the mat during installation. The heating cable mat
for embedded concrete can also be installed under the steel mesh.
FIRST SERIES OF TESTS
With the mat still in the box, perform the first series of tests as described
in the REQUIRED TESTS AND WARRANTY CARD, TESTS 1, 2, and 3 sections. Measured
values must be recorded on your warranty card. If a break or damage is
detected during the series of tests, the mat should be returned to the
original place of purchase.
HEATING CABLE MAT INSTALLATION TIPS
– Avoid applying excessive pressure on the mat while rolling.
– Avoid dropping objects onto the mat.
– During installation, make sure your shoes are free of any hard debris that
could damage the mat heating cables.
– Be very careful not to trip over the mat. Tripping may cause self-injury and
could damage the mat heating cables.
– The mat installation must not be performed at a temperature below freezing
point (0°C).
STEP-BY-STEP MAT INSTALLATION
ROUTING THE POWER LEADS TO THE THERMOSTAT ELECTRICAL BOX
Make sure the supply branch circuit is not energized. The maximum current
rating of the branch circuit must be limited to 15 amps. Determine the ideal
location for the thermostat in accordance with the electrical codes effective
in your area and install the conduit for the cold lead.
Remove all material from the box (mat, floor clips, temperature sensor). The
thermostat sensor must be placed in the conduit to protect it. If power relays
are used or slave thermostats, put the sensor cable in a different conduit
than the cold lead. Unroll the mat on the thermal insulation and fit it to the
room, placing the power leads at the area where the thermostat needs to be.
Make sure that you respect all clearance distances. Place the cold lead in the
conduit and keep the mechanical joint outside. No part of the heating cable
can be in the conduit or in the wall. Secure the joint to the subfloor using
clips or tape.
FIXING THE MAT TO THE SUBFLOOR
Use the floor clips to secure the cable on the thermal insulation. It is
recommended to use clips at every two feet of cable. Secure the ends of the
mat with more clips, if necessary. You can use adhesive tape to secure the
cable o the subfloor. To fit the mat to the room or to avoid an obstacle, the
mesh can be cut and the cable mat reoriented. Use scissors to carefully cut
the mesh to avoid damaging the cable.
SECOND SERIES OF TESTS
As described in the REQUIRED TESTS AND WARRANTY CARD, TESTS 1, 2, and 3
sections conduct the second series of tests when the mat has been secured to
the floor, before covering it with concrete. Measured values must be recorded
on your warranty card.
If a break or damage is detected, the installation should be stopped and the
mat should be repaired before continuing the installation.
ROUTING THE TEMPERATURE SENSOR CABLE TO THE ELECTRICAL BOX
Once the mat has been fixed to the subfloor and the second series of tests
have been completed with positive results attained, route the mat power leads
and the temperature sensor cable to the electrical box through the conduits.
The temperature sensor must be placed as close as possible to the surface of
the concrete floor. The sensor must be completely covered by concrete. Place
the cable sensor between two runs of cables and make sure not to cross the
heating cable. The sensor should not be placed where sunlight will shine on
the floor.
POURING THE CONCRETE
– Always be careful when walking on the mat to avoid damaging the cable.
– Always put protection (ex. plywood) over the heating cable in order to avoid
contact with the concrete pipe or pipe junctions.
– Make sure that the nozzle of the concrete pipe never touches the cable.
– Use adequate pressure to ensure the cable stays secured and is not damaged.
– Never use concrete with fiberglass or metal parts.
– If pouring concrete by wheelbarrow, never roll over the heating cable.
– Protect the cable by putting plywood on the path of the wheelbarrow.
– Always protect the cable from the wheelbarrow tip when pouring.
– The cable and temperature sensor must be completely covered by concrete.
– The thickness of the concrete slab must be 4 to 6 in. (10 to 15 cm).
– The thickness of the concrete floor must be 1.5 to 4 in. (4 to 10 cm).
– Level the concrete using conventional means while making sure not to touch
the cables, temperature sensor or mesh.
– NEVER USE A RAKE WITH FORKS POINTING DOWN.
THIRD SERIES OF TESTS Once the mortar embedding the mat has completely cured, perform the third series of tests as described in the REQUIRED TESTS AND WARRANTY CARD, TESTS 1, 2, and 3 sections. Measured values must be recorded on your warranty card. During the series of tests, if a break or damage is detected, you must call a qualified repair technician suggested by °STELPRO to complete the repair. To do so, call °STELPRO’s Customer Service or visit our website (www.°STELPRO.com). Any installation- related mat damages are not covered by the warranty.
ELECTRICAL POWER SUPPLY AND THERMOSTAT CONNECTIONS
The initial start-up of the floor heating system must be delayed until the end
of the curing period (typically 28 days) of the concrete. Refer to the
concrete manufacturer’s specifications for the required curing times.
PREPARATION BEFORE CONNECTION
– Ensure the circuit is not energized.
– The CSA identification tag of the heating cable mat must be in the junction
box. Do not remove it from the cable.
– The wiring of the mat to the thermostat or relay must be done according to
the thermostat/relay manufacturer’s instructions.
– Connect the ground wire (GREEN) to the junction box.
– The floor heating system must be connected to a ground-fault circuit
interrupter “GFCI”, either integrated in the thermostat or panel mounted.
If the floor heating system is located in a bathroom or shower, the GFCI must
be Class A (5 mA rating). Place the warning label on the electric panel board
to mark the branch circuit supplying the floor heating cable.
LIMITED WARRANTY
This limited warranty is offered by °STELPRO Design Inc. (“°STELPRO”) and
applies to the following product made by °STELPRO: SECM series. Please read
this limited warranty carefully. Subject to the terms of this warranty,
°STELPRO warrants its products and their components against defects in
workmanship and/or materials for the following periods from the date of
purchase: 20 years (heating cable). This warranty applies only to the original
purchaser; it is non-transferable and cannot be extended.
CLAIM PROCEDURE
If at any time during the warranty period the unit becomes defective, you must
cut off the power supply at the main electrical panel and contact 1) your
installer or distributor, 2) your service center or 3) °STELPRO’s customer
service department. In all cases, you must have a copy of the invoice and
provide the information written on the product nameplate. °STELPRO reserves
the right to examine or to ask one of its representatives to examine the
product itself or any part of it before honoring the warranty. °STELPRO
reserves the right to replace the entire unit, refund its purchase price or
repair a defective part. Please note that repairs made within the warranty
period must be authorized in advance in writing by °STELPRO and carried out by
persons authorized by °STELPRO.
Before returning a product to °STELPRO, you must have a °STELPRO authorization
number (RMA). To obtain it, call the customer service department at 1 800
363-3414 (electricians and distributors – French), 1 800 343-1022
(electricians and distributors – English), or 1 866 766-6020 (consumers). The
authorization number must be clearly written on the parcel or it will be
refused.
CONDITIONS, EXCLUSIONS, AND DISCLAIMER OF LIABILITY
This warranty is exclusive and in lieu of all other representations and
warranties (except of title), expressed or implied, and °STELPRO expressly
disclaims and excludes any implied warranty of merchantability or implied
warranty of fitness for a particular purpose. °STELPRO’s liability with
respect to products is limited as provided above. °STELPRO shall not be
subject to any other obligations or liabilities whatsoever, whether based on
contract, tort, or other theories of law, with respect to goods or services
furnished by it, or any undertakings, acts, or omissions relating thereto.
Without limiting the generality of the foregoing, °STELPRO expressly disclaims
any liability for property or personal injury damages, penalties, special or
punitive damages, damages for lost profits, loss of use of equipment, cost of
capital, cost of substitute products, facilities or services, shutdowns,
slowdowns, or for other types of economic loss or for claims of a dealer’s
customers or any third party for such damages. °STELPRO specifically disclaims
all consequential, incidental, and contingent damages whatsoever.
This warranty does not cover any damages or failures resulting from 1) a
faulty installation or improper storage; 2) an abusive or abnormal use, lack
of maintenance, improper maintenance (other than that prescribed by °STELPRO),
or use other than that for which the unit was designed; 3) a natural disaster
or an event out of °STELPRO’s control, including, but not limited to,
hurricanes, tornadoes, earthquakes, terrorist attacks, wars, overvoltage,
flooding, water damage, etc. This warranty does not cover any accidental or
intentional losses or damages, nor does it cover damages caused by negligence
on the part of the product user or owner. Moreover, it does not cover the cost
of disconnection, transport, and installation.
The warranty is limited to the repair or the replacement of the unit or the
refund of its purchase price, at the discretion of °STELPRO. Any parts
replaced or repaired within the warranty period with the written authorization
of °STELPRO will be warranted for the remainder of the original warranty
period. This warranty will be considered null and void and °STELPRO will have
the right to refuse any claims if products have been altered without the
written authorization of °STELPRO and if the nameplate numbers have been
removed or modified. This warranty does not cover scratches, dents, corrosion,
or discoloration caused by excessive heat, chemical cleaning products, and
abrasive agents. It does not cover any damage that occurred during shipping.
Some states and provinces do not allow the exclusion or limitation of
incidental or consequential damages, and some of them do not allow limitations
on how long an implied warranty lasts, so these exclusions or limitations may
not apply to you. This warranty gives you specific legal rights, and you may
have other rights which vary from state to state or from province to province.
This product complies with
CSA and UL
standards
INSSECM0622
For further information or to consult this guide online,
please visit our website at www.°STELPRO.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>