EMERSON Bettis SCE300 OM3 Local Interface Module Instruction Manual

June 4, 2024
Emerson

Bettis OM3 – SCE300
Local Interface Module
Instruction Manual

**Section 1: Optional Module 3: Local Interface Module

**

1.1 Local Interface Functionality
The OM3 Local Interface module is supplied as an option on Bettis SCE300 actuators and fits all models. It is possible to receive the actuator already equipped with the OM3 if
ordered together with the basic version. Alternatively, only for the waterproof version, it is possible to order the OM3 as a separate kit to be installed afterward on the basic actuator. The subsequent retrofitting of the OM3 on the existing SCE300 is not allowed in the explosion-proof version. The OM3 is an optional module allowing local control with the following additional functionalities:

  • Selection of Local/Remote actuator control through the selector (lockable in both positions).
  • Open/Close command through the nonintrusive pushbuttons.
  • Actuator position indication by means of 2 LEDs.

NOTE:
For decommissioning instructions, please refer to the relevant section in the Installation, Operation, and Maintenance Manual for Bettis SCE300 electric actuator.
WARNING
SCE300 actuator must be electrically isolated before any disassembling and reassembling operations. Before any disassembling or reassembling operations, please follow in detail the relevant paragraph of the basic installation and operating manual (latest revision available).
WARNING
The electronic parts of the SCE300 actuators and all optional modules can be damaged by a discharge of static electricity. Before you start, touch a grounded metal surface to discharge any static electricity.
WARNING
SCE300 actuators can be operated through a Bluetooth™ PDA or PC with the following configuration:

  • The commands are enabled by Bluetooth, only when the BT control is active. When operating with Bluetooth™, the controls via PDA or PC have priority over any other remote commands and allow full actuator operability from a distance also when the valve is not visible. Special attention must be paid under this condition to avoid any damages or injuries to people working close to the valve. Bettis will not accept any responsibility for damages or injuries caused by improper use of your Bluetooth™ PDA or PC.

WARNING
It is assumed that the installation, configuration, commissioning, maintenance, and repair works are carried out by qualified personnel and checked by responsible specialists.
WARNING
Repair work, other than operations outlined in this manual, is strictly reserved for qualified Emerson personnel or personnel authorized by the company itself.

1.2 Manufacturer
Manufacturer with respect to Machinery Directive 2006/42/EC: Emerson as specified on the actuator label.

Section 2: Assembling Procedure

To assemble the OM3 Local Interface module onto the SCE300 actuator, proceed as follows:

  • Ensure that all the parts received with the OM3 are available, see Figure 1:

Figure 1: OM3 kit for SCE300 actuator

Table 1.

Pos. Q.ty Description
1 1 Local Interface module
2 4 Screws for connecting connector
  • Gather the right tools for the assembly: a 5 mm Allen key and a screwdriver as shown in Figure 2.

Figure 2: Tools for installing OM3 kit

  • With the Allen key loosen the 4 cover screws and remove the terminal board enclosure cover, see Figure 3. You will see the terminal board inside the actuator. Remove the ground cable from the cover in the enclosure. The position of the connections is shown on the yellow label that you will find inside the cover just removed, see Figure 4.

Figure 3: Removing terminal board enclosure cover

Figure 4: Electrical connections

WARNING
Pay attention not to damage the joint surfaces of the cover/enclosures.

  • Connect the Local Interface module to the ground stud by screwing the ‘ground kit’ (screw + toothed washer).

Figure 5: Grounding the Local Interface

  • Take the 4 screws for connecting the Local Interface black connector to the terminal board, in pos. 28-29-30-31 (see Figure 6 and wiring diagram) and connect it with the screwdriver shown in Figure 7.

Figure 6: Position of the Local Interface connector on the terminal board

Figure 7: Connecting the Local Interface connector

  • Now the Local Interface is connected to the actuator, see Figure 8.
  • Take the 4 screws removed from the terminal board cover and use them to fix the Local Interface to the actuator, using the 5 mm Allen key, see Figure 9.

Figure 8: OM3 kit connected to the SCE300 terminal board

Figure 9: Fixing the local interface onto the SCE300 actuator

NOTE:
Please note that the design of the Local Interface black connector has been engineered to allow the installation in one way only. Due to the special design, it is not possible to reverse the connection of the 4 cables to the terminal board and it is not possible to make a wrong connection of the connector.

  • The installation of the OM3 Local Interface module onto the SCE300 actuator is now complete.

Section 3: Description of OM3 Local Interface

Figure 10

Table 2.

Pos. Description
1 2-position lockable selector switch
2 OPEN push-button
3 CLOSE push-button
4 OPEN position and correct with maneuver indicating LED (default green

color)
5| CLOSE position and correct with maneuver indicating LED (default red color)

3.1 Local Operator Interface
The following functions are available through the SCE300 Local Interface module (OM3):

  • Selection of Local/Remote actuator control through the selector (lockable in both positions).
  • Local actuator control: OPEN/CLOSE command through the non-intrusive pushbuttons.
  • Actuator position indication by means of 2 LEDs (green and red).

3.2 Description of the Local Interface
3.2.1 2-Position Selector

  • Local: to enable the local control only.
  • Remote: to enable the remote control and local control via Bluetooth with PC and PDA.

3.2.2 LEDs Indicating the Position of the SCE300 Actuator
The two LEDs indicate the actuator status according to the following logic:

Table 3.

Green LED Red LED Indication
ON OFF The actuator stopped in the completely OPEN position
OFF ON The actuator stopped in the completely CLOSED position
OFF Flashing Actuator running in the CLOSING direction
Flashing OFF Actuator running in the OPENING direction
ON ON The actuator stopped in the INTERMEDIATE position

NOTES:
It is possible to invert LEDs color, so:

  • red color for OPEN position and maneuver;
  • green color for CLOSE position and maneuver.

To do this, see the configuration section in the Installation, Operation, and Maintenance manual document.
It is also possible to invert LED color by means of a Bluetooth optional connection (if present).

3.2.3 OPEN/CLOSE Pushbuttons
The two OPEN and CLOSE pushbuttons are push-to-run types only. Once the pushbuttons are released, the actuator stops.

Section 4: To Locally Operate the Actuator

Once you have made sure that the actuator basic configuration is as requested by your application, bring the 2-position selector to LOCAL and control the actuator by OPEN and CLOSE pushbuttons.
The actuator can be driven to the desired position by pressing and holding the OPEN or CLOSE pushbutton. When the pushbutton is released, the motor is de- energized and stops. Once you have reached the fully open or fully closed positions, the actuator will stop automatically.

Section 5: OM3 Wiring Diagram

NOTES:

  1. Power connection L1-L2 for V DC or V AC single phase motor supply from 24 V to 48 V or from 100 V to 240 V.
    Power connection L1-L2-L3 for 3-phase motor supply from 208 V to 575 V (check the actuator label for the correct voltage to be applied).

  2. Remote command options:

  3. Contacts are shown in intermediate position CLC1-CLC2 end of travel signaling in CLOSING.
    Contacts are shown in intermediate position OPC1-OPC2 end of travel signaling in OPENING.

  4. Output contact rating: 240 V AC / 5 A – 30 V DC / 5 A – 120 V DC / 0.5 A.

  5. Control commend rating: 24 to 120 V AC or V DC.
    Control signal: minimum duration > 600 ms.
    Total current drawn for remote controls < 25 mA.

  6. Blinker or local selector monitoring function (when OM3 is present) to be configured.

Section 6: Identification

6.1 Water-, Dust-Proof Version
SCE300 actuators with OM3 are designed and manufactured according to EN 60529 standards.
Specific types of protection are printed on the label, as follows:

  • IP 66/68
  • NEMA 4/4X/6 according to NEMA 250

6.2 Label for Application In Water-, Dust-Proof Areas
Marking Description:

A. Manufacturer logo
B. Product model
C. Nominal output torque value
D. Product code
E. Serial number
F. Stroking time range
G. Power supply data
H. Max current absorption in ampere (at 24 V DC)
I. Environmental data
L. Actuator duties
M. Weatherproof protection degree (EU and US)
N. Weatherproof certificate reference (EU and US)
O. Manufacturer details
P. Year of construction

6.3 Explosion-Proof Version
The version of SCE300 with OM3 suitable for installation in hazardous areas is designed and manufactured according to EN 50014, 50018, 50019, and EN 50281-1-1 standards. The driven valve or associated gear reducer will form part of a separate risk analysis according to Directive ATEX 94/9/EC and following the EN 13463 norms. SCE300 actuators have IP 66/68 protection degrees in accordance with EN 60529.

WARNING
Whenever SCE300 actuators must be installed in a hazardous area as defined by the applicable rules, it is mandatory to check whether the actuator nameplates indicate their suitability to a hazardous area and the appropriate protection degree. Maintenance and repair works must be carried out by qualified personnel and checked by responsible specialists.

6.4 ATEX Label for Application in Hazardous Areas

A. Manufacturer logo
B. Product model
C. Nominal output torque value
D. Product code
E. Serial number
F. Stroking time range
G. Power supply data
H. Max current absorption in ampere (at 24 V DC)
I. Environmental data
L. Actuator duties
M. Explosion-proof protection degree
N. Weatherproof protection degree
O. ATEX certificate reference
P. Manufacturer details
Q. Year of construction
R. Notified Body for ATEX quality assurance (Ineris)
S. ATEX marking

Section 7: Safety Instructions

7.1 Foreword
This section is an integration of the base manual when an additional Local Control Panel is added to a base unit; when this combination is used, both manuals must be used.

7.2 General Safety Instructions
The devices to which these safety instructions apply are Electrical Actuators for industrial valves Series SCE300 equipped with optional module Local Control Panel identified by SCE300-OM3. The above Electrical Actuators are designed for use on industrial and control valves suitable to be installed on heavy industrial, chemical, petrochemical, plants, refinery, and/or pipelines for hazardous fluids.
The Electrical Actuators SCE300 with OM3 is produced by Emerson and identified by Product designation: SCE300-XXX/OM3. For the general Instructions relevant to the Installation, Operation Configuration, Maintenance, and Troubleshooting, the base Instruction and Operating Manual must be used.
The Electrical Actuators SCE300-OM3 are designed in accordance with the applicable International Rules and Specifications but in any case, the following regulations must be observed:

  • The general installation and safety regulations are effective at the site of installation.
  • The proper use of personal protective devices (glasses, clothing, gloves).
  • The proper use of tools, lifting, and transport equipment.

WARNING
Before the installation in hazardous areas, as defined by the local rules, it is mandatory to check if the nameplate of the Electric Actuator specifies the appropriate degree of protection.

7.3 Check for the Right Application
Before the installation, check for protection mode and for the ambient temperature range written on the appropriate label.

WARNING
Installation in ambient with the presence of explosive atmospheres not covered by the specified grade of protection specified in the label, or which could reach temperatures outside the range specified in the label, will invalidate the safety and the warranty.

7.4 Applicable Standards and Regulations

EN ISO 12100-1| Safety of machinery – Basic concepts, general principles for design Part 1-Basic terminology, methodology
---|---
EN ISO 12100-2| Safety of machinery – Basic concepts, general principles for design Part 2-Technical principles and specification
IEC/EN 60204-1| Electrical equipment of industrial machines: Part 1-General requirements
2006/42/EC| Machinery Directive
2014/35/EU| Low Voltage Directive
2014/30/EU| EMC Directive

7.5 Terms and Conditions
Emerson guarantees every single product to be free from defects and to conform to current goods specifications. Except when differently specified, the warranty period is one
year from the date of installation by the first user, or eighteen months from the date of shipment to the first user, whichever occurs first. No warranty is given for products that have been subject to improper storage, improper installation, misuse, or which have been modified or repaired by unauthorized personnel. Repair works due to improper use will be charged at standard rates.

7.6 Manufacturer’s Liability
Emerson declines all liability in the event of:

  • Use of product in contravention of local safety at work legislation.
  • Incorrect installation, disregard, or incorrect application of the instructions provided on the product nameplate and in this Installation and Operation and Maintenance Manual.
  • Modification of the product without Emerson’s authorization.
  • Work done on the product by unqualified or unsuitable personnel.

Section 8: Installation

8.1 Working Conditions
The Electric Actuators SCE300 with OM3 is suitable for the following ambient temperatures from -40 °C to +65 °C (from -40 °F to +149 °F).
NOTE:
Check the ‘temperature ambient range’ embossed on the nameplate, for the correct utilization with respect to the ambient temperature conditions.

8.2 Electrical Connections
Before applying electrical power to the actuator check that the electrical parameters (supply voltage and current) shown on the nameplate, are correct for this installation.
NOTE:
The installation and maintenance must be carried out in accordance with the applicable rules regarding the electrical installations in hazardous areas (other than mines) classified as Zone 1 (gas): IEC 60079-10; IEC 60079-14; IEC 60079-17 and/or other national standards.

8.3 Instructions for the Intrinsically-Safe Enclosures
NOTE:
The installation and maintenance of Electric Actuators SCE300 with OM3 must be carried out in accordance with the applicable rules regarding the electrical installations in hazardous areas (other than mines) classified as Zone 1 (gas): IEC 60079-10; IEC 60079-14;
IEC 60079-17 and/or other national standards.

WARNING
Do not operate the Electric Actuator electrically when the Local Control Panel is removed from the terminal board enclosure. Operating the unit with electrical enclosures not protected by their covers could cause personal injury.

8.4 Installation in Ambient with Explosive Dust
NOTE:
The installation and maintenance must be carried out in accordance with IEC 61241-14. Special attention must do to the following points:

  • The cable glands must have a protection degree at a minimum of IP 66/68 (IEC 60529).
  • Periodically verify the quantity of dust deposited on the enclosure and clean it in case the quantity becomes more than 5 mm.

Section 9: Special Maintenance

WARNING
The maintenance and any repair works must be carried out by personnel specifically qualified and fully trained for works in hazardous areas.

9.1 Periodic Inspections
A. Frequency of inspection may depend form the installation and working conditions; in general, at least one inspection every two years is recommended.
B. Inspect the Electrical Actuator with particular attention to electrical enclosures conditions.
WARNING
Any damage or breaking found on the enclosures, lack of screws fixing the covers, or loosening screws must require immediate maintenance action.
C. Keep the external surface clean: if the Electrical Actuators are installed in a dusty environment the specification stated in IEC 61241-14 be followed ensuring in particular that the dust layer does not exceed 5 mm.
D. Check the condition of cable connection and mounting bolts: any loose connection must be amended.

9.2 Repairs of Intrinsically-Safe Parts
WARNING

In case the maintenance should require the replacement of any component which forms part of the Local Control Panel only an original spare provided by Emerson MUST be used. Direct repair or reconstruction of the above components is not permitted without Emerson’s permission. Not performing this procedure will invalidate the product safety and contractual guarantee.
Original spare parts must be required to Emerson: to ensure that the right spare is provided, the serial number printed on the Electric Actuator label MUST be specified when spares are ordered.

World Area Configuration Centers (WACC) offer sales support, service, inventory, and commissioning to our global customers.
Choose the WACC or sales office nearest you:

NORTH & SOUTH AMERICA
19200 Northwest Freeway
Houston TX 77065 USA
T +1 281 477 4100
Av. Hollingsworth
325 Iporanga Sorocaba
SP 18087-105 Brazil
T +55 15 3413 8888| MIDDLE EAST & AFRICA
P. O. Box 17033
Jebel Ali Free Zone Dubai
T +971 4 811 8100
P. O. Box 10305
Jubail 31961 Saudi Arabia
T +966 3 340 8650
24 Angus Crescent
Longmeadow Business Estate East
P.O. Box 6908 Greenstone
1616 Modderfontein Extension 5 South Africa
T +27 11 451 3700
---|---
ASIA PACIFIC
No. 9 Gul Road

01-02 Singapore 629361

T +65 6777 8211No. 1 Lai Yuan Road
Wuqing Development Area
Tianjin 301700
P. R. China
T +86 22 8212 3300| EUROPE
Holland Fasor 6
Székesfehérvár 8000 Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC) Italy
T +39 0523 944 411

For the complete list of sales and manufacturing sites, please visit www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com

www.emerson.com/bettis

VCIOM-17109-EN ©2022 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Bettis™ is a mark of one of the Emerson family of companies.
All other marks are property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

VCIOM-17109-EN Rev. 0

Documents / Resources

| EMERSON Bettis SCE300 OM3 Local Interface Module [pdf] Instruction Manual
Bettis SCE300, OM3 Local Interface Module, Bettis SCE300 OM3 Local Interface Module, Interface Module, Local Interface Module
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals