Emerson R412013605-BAL-001-AD Bus coupler with link structure DDL Instruction Manual
- June 4, 2024
- Emerson
Table of Contents
- Operating instructions
- About this documentation **
- Presentation of information
- Symbols
- Abbreviations
- Notes on safety
- Scope of delivery
- About This Product
- Assembly
- Electrically connecting the product
- Commissioning
- In operation
- Disassembly and exchange
- Disposal
- Maintenance and repairs
- Maintenance
- Troubleshooting
- Technical data
- Appendix
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
R412013605-BAL-001-AD Bus coupler with link structure DDL
Instruction Manual
Operating instructions
AVENTICS™ PROFINET
Bus coupler with link structure DDL
About this documentation **
**
Documentation validity
This document contains important information on the safe and appropriate
assembly, operation, and maintenance of the product and how to remedy simple
malfunctions yourself.
Read this documentation completely, especially chapter 2. Notes on safety
before working with the product.
Required and supplementary documentation
Only commission the product once you have obtained the following documentation
and understood and complied with its contents.
Required and supplementary documentation
Title | Document number | Document Type |
---|---|---|
DDL system description | R499050030 | Operating instructions |
System documentation
Further information on the components can be found in our online catalog.
Presentation of information
Warnings
In this documentation, there are warning notes before the steps whenever there
is a risk of personal injury or damage to equipment. The measures described to
avoid these hazards must be followed.
Structure of warnings
SIGNAL WORD
Hazard type and source
Consequences of non-observance
Precautions
Meaning of the signal words
DANGER
Immediate danger to the life and health of persons.
Failure to observe these notices will result in serious health consequences,
including death.
WARNING
Possible danger to the life and health of persons.
Failure to observe these notices can result in serious health consequences,
including death.
CAUTION
A possible dangerous situation.
Failure to observe these notices may result in minor injuries or damage to
property.
NOTICE
Possibility of damage to property or malfunction.
Failure to observe these notices may result in damage to property or
malfunctions, but not in personal injury.
Symbols
Recommendation for the optimum use of our products. Observe this information to ensure the smoothest possible operation.
Abbreviations
This documentation uses the following abbreviations:
Table 1: Abbreviations
Abbreviation | Meaning |
---|---|
VS | Valve system |
DDL | Drive & Diagnostic Link |
FE | Functional Earth |
Notes on safety
About this chapter
The product has been manufactured according to the accepted rules of current
technology. Even so, there is danger of injury and damage to equipment if the
following chapter and safety instructions of this documentation are not
followed.
- Read these instructions completely before working with the product.
- Keep this documentation in a location where it is accessible to all users at all times.
- Always include the required documentation when you pass the product on to third parties.
Intended use
The product is an electrical system component.
The product may be used as follows:
- only for industrial applications.
- within the performance limits listed in the technical data. The product is intended for professional use only.
Intended use includes having read and understood these instructions completely, especially section g 2. Notes on safety and the DDL system description R499050030.
Improper use
Any use other than that described under intended use is improper and is not
permitted. The installation or use of unsuitable products in safety-relevant
applications can result in unanticipated operating states in the application
that can lead to personal injury or damage to equipment. Therefore, only use a
product in safety-relevant applications if such use is specifically stated and
permitted in the product documentation. For example, in areas with explosion
protection or in safety-related components of control systems (functional
safety). AVENTICS GmbH is not liable for any damages resulting from improper
use. The user alone bears the risks of improper use of the product.
Improper use of the product includes:
- is used for any application not stated in these instructions, or
- is used under operating conditions that deviate from those described in these instructions or in the DDL system description (R499050030) or
Personnel qualifications
The work described in this document requires basic electrical and pneumatic
knowledge, as well as knowledge of the appropriate technical terms. In order
to ensure safe use, these activities may therefore only be carried out by
qualified technical personnel or an instructed person under the direction and
supervision of qualified personnel.
Qualified personnel is those who can recognize possible dangers and institute
the appropriate safety measures, due to their professional training,
knowledge, and experience, as well as their understanding of the relevant
regulations pertaining to the work to be done. Qualified personnel must
observe the rules relevant to the subject area.
General safety instructions
General information
- Observe the regulations for accident prevention and environmental protection.
- Observe the safety instructions and regulations of the country in which the product is used or operated.
- Only use AVENTICS products that are in perfect working order.
- Follow all the instructions on the product.
- Persons who assemble, operate, disassemble, or maintain AVENTICS products must not consume any alcohol, drugs, or pharmaceuticals that may affect their ability to respond.
- To avoid injuries due to unsuitable spare parts, only use accessories and spare parts approved by the manufacturer.
- Comply with the technical data and ambient conditions listed in the product documentation.
- If unsuitable products are installed or used in safety-relevant applications, this may result in unintended system operating states that may lead to injuries and/or equipment damage. Therefore, only use a product in safety-relevant applications if such use is specifically stated and permitted in the product documentation.
- You may only commission the product if you have determined that the end product (such as a machine or system) in which the AVENTICS products are installed meets the country-specific provisions, safety regulations, and standards for the specific application.
- Do not modify or convert the device.
- Only use the device within the performance range provided in the technical data.
- Do not place any mechanical loads on the device under any circumstances. Do not place any objects on it.
- The warranty only applies when the product is used as intended.
- Observe the related safety notes in the operating instructions.
Transport and storage
- A problem-free and safe operation of the devices requires proper transport, correct storage, installation, and assembly.
During cleaning
- Only clean the device using a slightly damp cloth. Only use water and, if necessary, a mild detergent.
Control network malfunction
Products with Ethernet connections are designed to be used on specific
industrial control networks. Observe the following safety measures:
-
Always follow industry best practices for network segmentation.
-
Avoid exposing products with Ethernet connection directly to the Internet.
-
Minimize internet and business network exposure for all control system devices and/or control systems.
-
Ensure that products, control system devices, and/or control systems are not accessible from the Internet.
-
Locate control networks and remote devices behind firewalls and isolate them from the business network.
-
If remote access is required, only use secure methods such as Virtual Private Networks (VPNs).
NOTICE! Recognize that VPNs and other software-based products may have vulnerabilities. A VPN is only as secure as the connected devices it serves. Always use the current version of the VPN, the firewall, and other software- based products. -
Ensure that the latest released software and firmware versions are installed on all products connected to the network.
Safety instructions related to the product and technology Prior to installation
-
The bus coupler (electrostatically endangered components) may only be opened by trained personnel.
-
Make sure the relevant system component is without pressure or voltage before assembling or when connecting and disconnecting plugs. Protect the system against being
restarted. -
Only use a power pack with safe isolation in accordance with DIN EN 60742, classification VDE 0551 for the supply voltage. Please pay attention to external fuses that comply with this description.
-
The warranty will not apply if the product is incorrectly assembled. During assembly
-
Always assemble the bus coupler on a mounting plate or in a control cabinet.
-
Refer to the operating instructions.
-
Lay the lines so that no one can trip over them.
-
Other system parts may be damaged by uncontrolled device movements if it has not been properly mounted. Make sure that the device is securely fastened.
-
Ground the devices according to national regulations.
-
Only use cables indicated in the operating instructions or quotation drawings.
Commissioning
- Installation/assembly and commissioning of the device may only be carried out in a voltage-free and pressure-free state by trained and qualified specialists.
- Only put the device into operation if it has been completely assembled, correctly wired and tested.
- Before connecting or disconnecting the plugs, switch off the operating voltage to prevent damage to the electrical system.
In operation
- Observe the related safety notes in the operating instructions.
Scope of delivery
- 1x bus coupler PROFINET DDL
- 1 set of operating instructions
About This Product
Performance specifications
The bus coupler is used to connect the DDL system to a PROFINET field bus. The
bus coupler communicates with the fieldbus system and monitors the DDL (Drive
and Diagnostic Link). The bus coupler is designed only for use as a device on
a PROFINET bus system. The bus coupler is a modular I/O device that conforms
to PROFINET specifications. The bus coupler connects the local I/O devices
with the PROFINET network. In the data model, these I/O devices are modularly
connected to the bus coupler.
The bus coupler functions as an interface between the PROFINET network and the
local DDL participants.
Product Description
Fig. 1: Product overview
1 | PROFINET LEDs | 4 | X7E2: PROFINET IN |
---|---|---|---|
2 | X7E1: PROFINET OUT | 5 | XPD: DDL connection |
3 | X1S: M12 power supply (integrated X1S power supply plug) | 6 | S1/S2 |
Product identification
Observe the product information on the product and packaging.
Assembly
CAUTION
The danger of injury if assembled under pressure or voltage!
Assembling when under pressure or electrical voltage can lead to injuries and
damage to the product or system components.
- Make sure that the relevant system component is without pressure and voltage before you assemble the product.
- Protect the system against being restarted.
5.1 Assembling the product
**CAUTION
The danger of injury due to incorrect assembly!**
Incorrect assembly can lead to uncontrolled product or system movements.
- Make sure that the bus coupler is correctly fastened.
- Make sure that the device is securely fastened with the correct tightening
torque.
1. Let the bus coupler acclimate itself for several hours before
installation; otherwise water may condense in the housing.
2. Make sure the relevant system part is without pressure and voltage.
3. Remove the four mounting screws.
4. Set the bus coupler in the desired position on the mounting plate
(any) or control cabinet (on the side).
5. Tighten the four M5 mounting screws (tightening torque: 6 Nm).
Dimensions
Fig. 2: Bus
coupler, dimensions
Electrically connecting the product
Connecting the DDL and bus coupler
The electrical connections of the bus coupler are established using threaded
M12x1 round plug connectors.
Attach the connectors to the bus coupler.
NOTICE
Material damage due to penetration of liquids and foreign objects!
Liquids and foreign objects could penetrate the plug connections if seals and
plugs are missing and cause damage to the product or system components.
- Use round plug connectors with the IP65 protection class or better.
- Make sure that the seals are integrated into the plug and not damaged.
- Close all unused plug connectors with sealing caps (blanking plugs).
- Make sure that all plugs are correctly connected before commissioning.
A functional ground is connected via the X1S connection. See g Table 2.
Connecting the supply voltage
Fig. 3: Connections and plugs
1 | X7E2, PROFINET |
---|---|
2 | X7E1, PROFINET |
3 | XPD |
4 | Integrated X1S POWER SUPPLY plug |
The valve coils are provided with voltage via the integrated X1S POWER SUPPLY (4) plug.
Fig. 4: POWER X1S
Table 2: Pin assignment X1S
Contact | Pin assignment |
---|---|
Pin 1 | 24 V electronics |
Pin 2 | 24 V valves |
Pin 3 | 0 V (max. 4 A) |
Pin 4 | FE |
The electronics of the bus coupler and the electronics of all I/O modules and
initiators connected through the DDL are supplied via X1S, Pin 1 (for modules
without external power supply).
When using modules without an external power supply, the switching voltage for
the connected valves must be supplied via X1S, Pin 2.
The separate supply voltages via pin 1 and pin 2 make it possible to switch
off only the valves in an emergency OFF situation, while the PLC, serial
interfaces, and initiators remain in operation. Shutting off the supply
voltage for the serial interface can cause the PLC to STOP.
NOTICE
Damage can occur if the device is assembled or disassembled under voltage/
load!
Inadvertently connecting and disconnecting the product or system parts under
voltage/load can cause damage.
Make sure that all relevant system parts are not under voltage before
inserting or disconnecting plug connectors.
- Only use 4-pin M12 connection sockets where pin 5 is closed, in order to rule out confusion with other connections.
- Make sure that the largest connection cross-section possible is selected, at least 0.55 mm².
- Secure both supply voltages with external 3-A-T fuses.
The applied supply voltage is indicated by a green LED (5 V): The LED
illuminates as soon as the electronics voltage > 18 V. See g Table 5. The
maximum permissible current in the 0 V line is limited to 4 A by the plug
connector.
Only use a shared power pack or a shared 0 V connection for the 24 V power
supply. This must be a power pack with safe isolation in accordance with DIN
EN 60742, classification VDE 0551.
Commissioning
The bus coupler may only be commissioned with the entire system in which it is
installed.
Contact the system manufacturer if you want to commission the bus coupler.
First-time commissioning
NOTICE
Damage due to uncontrolled device movements!
The bus coupler and other system parts may be damaged by uncontrolled device
movements.
Commissioning of the bus coupler may only be carried out in a pressure-free
state.
Making settings
The following prerequisites must be fulfilled:
- The transfer rate must be set the same for all DDL modules.
- The addressing conditions of the DDL (Drive & Diagnostic Link) must be fulfilled.
- The DDL configuration must be set and tested.
- The terminating resistor after the last DDL participant must be connected.
Setting the DDL address
No DDL address has to be set on the bus coupler.
For the DDL (Drive & Diagnostic Link) to function properly, the following
addressing conditions must be fulfilled:
• DDL address from 1-14, starting at 1, without gaps, no address assigned
twice DDL address 0: see DDL system description (R499050030). Setting the
transfer rate (DDL ode) The DDL transfer rate is determined with the 5-pin S2
DIP switch on the front side. All DDL participants must be set to the same
transfer rate.
Fig. 5: S2 DIP switch
Table 3: DDL baud rate
Switch | Bit | Open | On |
---|---|---|---|
S2 (5 bits) | 5 | DDL 125 kBaud | DDL 250 kBaud (default) |
The transfer rate can be set as follows:
- Open the cover of the S2 DIP switch.
- Move the S2.5 DIP switch to the desired position. See g Fig. 5.
- Close the cover of the S2 DIP switch.
Configuring the bus coupler
See section g 13.2. DDL participant parameters.
Starting the PROFINET interface
The bus system is connected using M12, 5-pin, and D-coded data plugs. The
physical sequence of the devices in a PROFINET system can be chosen
arbitrarily. The X7E1, PROFINET (2) and X7E2, PROFINET (1) connections are
therefore interchangeable and may only be configured when not in operation.
See g Fig. 3.
Fig. 6: X7E1 bus IN
Fig. 7: X7ES bus OUT
Table 4: Pin assignment, M12 data plug, D-coded
Contact | Pin assignment |
---|---|
Pin 1 | TD + |
Pin 2 | RD + |
Pin 3 | TD – |
Pin 4 | RD – |
Pin 5 | not assigned |
Commissioning the VS with bus coupler
Before commissioning the system, the following steps must have been carried
out and completed:
-
You have assembled the valve system and the bus coupler.
-
You have connected the bus coupler.
See section g 5.2. Electrically connecting the product. -
You have carried out the settings and configuration.
See section g 6.1.1. Making settings. -
You have configured the bus master so that it controls the valves correctly.
Assembly and commissioning may only be carried out by qualified electrical or pneumatic personnel or an instructed person under the direction and supervision of qualified personnel. See section g 2.4. Personnel qualifications.
CAUTION
Risk of uncontrolled actuator movements when the pneumatics are switched on!
There is a danger of personal injury if the system is in an undefined state.
- Put the system in a defined state before switching it on.
- Make sure that no personnel is within the hazardous zone when the compressed air supply is switched on.
- Also, observe the application instructions and safety information in the VS operating instructions.
1. Switch on the operating voltage.
2. Check the LED displays on all modules.
3. Switch on the compressed air supply.
Start-up procedure
The start-up procedure is as follows:
-
The bus coupler automatically starts the communication with the DDL modules and determines which modules are present. At the same time, the PROFINET controller informs the bus coupler of the configuration saved in the controller.
-
The bus coupler checks the configuration and returns the following error messages where necessary:
– DDL addresses the gap
– No DDL modules connected
– Fewer DDL modules are connected than configured
– More DDL modules are connected than configured -
If an error is recognized, the bus coupler waits 5 seconds and restarts the DDL communication. The user can then resolve the address error. See also section g 6.1.1. Making settings. The DDL LED stays red in the event of an error. If the error has been resolved, the LED extinguishes. See section g 13.2. DDL participant parameters. The bus coupler uses the first valid configuration. Any subsequent changes only take effect once the system has been restarted.
-
This information is used to create slots and subplots for PROFINET. The bus coupler then waits for the parameters from the controller.
-
The bus coupler and PROFINET controller then both start the cyclical exchange of data.
-
In the event of an abort by PROFINET, the bus coupler then starts up again as long as the parameters remain unchanged, as the DDL stack is only started once with the transfer of parameters. In the event of changes to the parameters, the bus coupler must be restarted.
In operation
Observe the following points for operation
- Do not change the switch and configuration during operation. Changed settings are only accepted once the device has been switched off and on again.
- Please note that compensating currents caused by differences in potential must not flow via the shielding.
Diagnosis
**LED diagnosis
** On top of the housing, light emitting diodes (LEDs) indicate the status of
the PROFINET interface and the power supply. See also section g 5.2.2.
Connecting the supply voltage.
Table 5: Overview of PROFINET LED displays
Label left | Label right | Meaning |
---|---|---|
5 V Green | DDL Red | 5 V: illuminates if the supply voltage is > 18 V DDL: |
• Illuminates for configuration errors (address, baud rate, terminating
resistor)
• Illuminates during initialization and flashes after successful
initialization
• OFF during DDL communication
SF Red| BF Red| SF: System Failure
BF: Bus Failure
LINK0 Green| | LINK0/ACT0: illuminated if a link exists, flashes when
sending and receiving data
LINK1 Green| | LINK0/ACT1: illuminated if a link exists, flashes when
sending and receiving data
The power supply for valves is not monitored at the bus coupler.
Software diagnosis
The bus coupler provides diagnostic data:
Detailed information on the structures for diagnosis of the individual DDL
participants can be found in the descriptions of the respective DDL
participants.
Transmitting the diagnosis to the PLC can be inhibited by using the S1.1 DIP
switch.
S1.1 to 0 | The diagnostic data will not be sent to the PLC (default). |
---|---|
S1.1 to 1 | The diagnostic data will be sent to the PLC. |
The warnings will be deleted automatically as soon as the cause has been eliminated. Only one message can be displayed.
When making changes at the DDL, it is recommended to always conduct a voltage reset.
Disassembly and exchange
Disassembling the bus coupler
NOTICE
Damage can occur if the device is under voltage!
Inadvertently disconnecting the voltage can damage the product or system
parts.
Make sure the relevant system component is not under voltage before
disassembling the device or when disconnecting plugs.
- Switch off the 24 V DC electronics power supply and valve supply.
- Remove the connected plugs.
- Loosen the bus coupler from the work surface.
- Remove the bus coupler.
Disposal
Dispose of the product in accordance with the currently applicable regulations in your country.
Maintenance and repairs
Cleaning and servicing
NOTICE
Damage to the surface caused by solvents and aggressive detergents!
The surfaces and seals could be damaged by solvents or aggressive cleaning
agents.
- Never use solvents or aggressive detergents.
- Only clean the device using a slightly damp cloth. Only use water to do this and, if necessary, a mild detergent.
Check that all seals and plugs for the plug connections are firmly fitted so
that no humidity can penetrate the bus coupler during cleaning.
Maintenance
The bus coupler is maintenance-free. However, the seals of the bus coupler may age faster under aggressive ambient conditions. Defective seals will lead to pneumatic leaks and non-compliance with the IP65 protection class.
- Regularly check that the seals on the bus coupler are in perfect order. Establish the maintenance intervals according to your ambient conditions and store them in the system-dependent maintenance plan.
- Observe the system-specific maintenance intervals.
Troubleshooting
Malfunction | Possible cause | Remedy |
---|---|---|
LED 5 V not illuminated | No voltage available Bus coupler is defective. | |
Incorrectly assembled or defective cable | Check the power supply to the bus |
coupler. Exchange the bus coupler.
Use tested cables.
LED L1/A1 or L2/A2 not illuminated| There is no physical connection between
the
PROFINET controller and bus couple.| Check the Ethernet cable and
PROFINET connections.
LED DDL is permanently illuminated| Faulty DDL configuration| Check the baud
rate, consecutive addressing 1-x, terminating resistor
present.
SF LED illuminated| Diagnosis is switched on and there is a diagnosis.| Check
the diagnosis of the participants.
BF LED illuminated| Configuration does not match the connected hardware.|
Adjust hardware configuration.
If you cannot remedy a malfunction, get in touch with our contact address (contact data: see back cover).
Technical data
General data
Dimensions (width x height x depth)| 50 mm x 120.5 mm x 106.5 mm
Weight| approx. 425 g
Storage conditions| < 80 % RH
Relative humidity| 0 … 95 %
Protection class according to EN 60529/ IEC529| IP65 (only when assembled and
with all plugs
Supply voltage| 24 V DC sensor voltage (± 20 %)
24 V DC valve voltage (±10 %)
For the supply voltage, only use a power pack with safe isolation.
Permissible ripple| 5 %
Mounting orientation| Any
Fuse for voltage: external valves| 3 A T
Fuse for voltage: external electronics| 3 A T
Warning: maximum current in the 0 V line| Max. 4 A
Internal voltage drop| 0.8 V
The current requirement for electronics| 90 mA
Power supply for initiators| Max. 3 A per DDL line
Power supply for valves| Max. 3 A per DDL line
Start-up time after switching on the supply| 2 s
Temperature range| +5 °C … +50 °C
Storage temperature| -20 °C … +70 °C
Standards and directives complied with| 2004/108/EC “Electromagnetic
compatibility city” (EMC directive)
DIN EN 61000-6-2 “Electromagnetic compatibility” (Interference immunity for
industrial environments)
DIN EN 61000-6-4 “Electromagnetic compatibility” (Interference emission for
industrial environments)
DIN EN 60204-1 “Safety of machinery – Electrical equipment of machines – Part
1: General requirements”
Appendix
PROFINET configuration
For the PLC configuration software, e. g. S7 Simatic Manager, the GSDML files
are required for the bus coupler, as well as each DDL module used.
The data model for the PROFINET DDL bus coupler is described by means of
various modules. Each module (no. 1 to max. 14) represents a DDL module and
each contains a submodule for input (no. 1), output (no. 2), and diagnosis
(no. 3). Diagnosis alarms and parameters are allocated to the respective
diagnosis submodule. In addition, module 0 contains the PROFINET-specific
submodules for DAP, device, and both ports. Submodule 1 (device) contains 4
bytes of bus coupler diagnosis data (life sign, error bits, and presence
list).
In view of the fact that there are compatibility issues with a number of
PROFINET CPUs, the 4 bytes of the bus coupler diagnosis data can also be
invoked using a 15th participant (DDL master diagnosis). This participant can
only be placed in slot 15.
Before start-up, the bus coupler must be assigned a device name via Ethernet
(DCP) so that the PROFINET controller can establish a connection. This device
name is saved in the flash drive. The device name is empty when delivered, as
is stipulated in the PROFINET
standards. So that the name can be assigned, a correct DDL configuration must
be connected to the bus coupler, indicated by a flashing DDL LED.
DDL participant parameters
The parameter descriptions of the individual DDL participants can be found in
the respective operating instructions.
PROFINET diagnosis alarms
The bus coupler provides a mechanism through which errors can be reported to
the PROFINET controller. Extended channel diagnosis is used. Bus coupler
alarms are displayed on slot 0, subslot 1. These include:
-
DDL addresses gap
-
No DDL modules connected
-
Fewer DDL modules are connected than configured
-
More DDL modules are connected than configured
With the exception of the message “no DDL modules”, the presence list is transmitted as an additional parameter.
In addition, the StdDiag byte is monitored by each connected DDL module, and the message: -
DDL module – StdDiag transmitted as a parameter with the StdDiag byte. All of these error reports may occur at the same time and are deleted once the respective error has been resolved.
DDL data line
The output of the DDL is short-circuit-resistant on all lines. However, DDL
participants can be damaged if 24 V is applied to the DDL H and DDL L signal
lines. For this reason, it is recommended to use preassembled cables. The
assignments for DDL connections are described in the DDL system description
(R499050030). The DDL termination plug is needed if the module is the last or
only participant of a DDL line. This ensures a defined line termination, and
the module complies with the IP65 protection class.
PROFINET supported functions
Table 6: Supported and limited PROFINET functions
Supported protocols| RTC – Real-time Cyclic Protocol, Class 1 RTA – Real-time
Acyclic Protocol
DCP – Discovery and Configuration Protocol CL-RPC – Connectionless Remote
Procedure Call
LLDP – Link Layer Discovery Protocol
SNMP – Simple Network Management Protocol
---|---
Maximum data quantity of the cyclical input| 16 bytes
Maximum data quantity of the cyclical out| 16 bytes
Maximum slot address| 255
Maximum subslot address| 10
Alarm types| Process Alarm, Diagnostic Alarm, Return of SubModule, Plug Alarm,
Pull Alarm
Used protocols (subset)| UDP, IP, ARP, ICMP (Ping)
Topology recognition| LLDP, SNMP V1, MIB2, Physical Device
VLAN- and priority tagging
Minimum cycle time| 1 ms
Conformity| Class A
Baud rate| 100 Mbit/s
Network protocol| Ethernet II, IEEE 802.3
Not supported| RT over UDP
| IRT “flex” (synchronized RT Class 2)
| Fast Start-Up
| Media redundancy
| Supervisor AR
| Shared Device not supported
| Multicast communication
| DHCP
DDL participant parameters
The parameter descriptions of the individual DDL participants can be found in
the respective operating instructions.
The data specified above only serve to describe the product. No statements
concerning a certain condition or suitability for a certain application can be
derived from our information. The given information does not release the user
from the obligation of own judgment and verification. It must be remembered
that our products are subject to a natural process of wear and aging.
An example configuration is depicted on the title page. The delivered product
may thus vary from that in the illustration. Translation of the original
operating instructions. The original operating instructions were created in
the German language. Subject to modifications. © All rights reserved by
AVENTICS GmbH, even and especially in cases of proprietary rights
applications. This document may not be reproduced or given to third parties
without our consent. The Emerson logo is a trademark and service mark of
Emerson Electric Co. AVENTICS is a mark of one of the Emerson Automation
Solutions family of business units. All other marks are property of their
respective owners.
Emerson Automation Solutions
AVENTICS GmbH
Ulmer Straße 4
30880 Laatzen, GERMANY
phone +49 511 2136-0
fax +49 511 2136-269
www.emerson.com/aventics
aventics@emerson.com
Further addresses:
www.emerson.com/contactus
References
- AVENTICS – Smart, reliable solutions for pneumatic automation | Emerson US
- Contact Us | Emerson US
- Contact Us | Emerson US
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>