Emerson PESO India Certificates for Fisher™ FIELDVUE™ DVC6200 Series Digital Valve Controllers User Manual
- June 4, 2024
- Emerson
Table of Contents
PESO India Certificates for Fisher™ FIELDVUE ™
DVC6200 Series Digital Valve Controllers
User Manual
Note
This information supplements the nameplate markings affixed to the product and
the DVC6200 Series quick start guide (D103556X012), available from your
Emerson sales office or at Fisher.com. Always refer to the nameplate itself to
identify the appropriate certification.
Ex d IIC T5/T6 Gb
Ex d IIC T4/T5/T6 Gb
Government of India
Ministry of Commerce & Industry
Petroleum & Explosives Safety Organisation (PESO)
5th Floor, A-Block, CGO Complex, Seminary Hills,
Nagpur – 440006
Approval No: A/PA-IQ/TN/104/5985 (P505934)
To,
M/s. Fisher Controls International LLC, 205 SOUTH CENTER STREET,
Marshalltown IA
50159christopheranderson@emerson.com0164-17543747
U.S.A
Sub : Approval of Flame Proof Type Electrical Equipments under Petroleum
Rules 2002- Regarding.
Sir(s),
Please refer to your letter No. 01N779650 dated 13/04/2021 on the subject.
The following Ex electrical equipment(s) manufactured by you according to IEC
60079-0: 2011, IEC 60079-1: 2007, standards and covered under CSA Group Test
reports mentioned below is/are approved for use in Zone 1 of Gas IIC hazardous
areas coming under the Petroleum Rules, 2002 administered by this
Organization.
Sr.
No| Description| Safety
Protection| Equipment
reference
Number| | Test Agency|
---|---|---|---|---|---|---
Name| Certificate Certificate
No. Date| Drawing
no
1| DVC6000 / DVC
6200 DIGITAL
VALVE
CONTROLLERS| Ex d IIC
T5/T6 Gb,
Ex d 110
T4/T5/T6 Gb| P505934/1| CSA
Group| IECEx
CSA
16.0003X
Issue No 3| 10/0912020| GE09603
GE47752
This Approval is granted subject to observance of the following conditions:-
-
The design and construction of the equipment shall be strictly in accordance with the description, condition, and drawings, as mentioned in the CSA Group Test Reports, referred to above.
-
The equipment shall be used only with the approved types of accessories and associated apparatus.
-
Each piece of equipment shall be marked either by raised lettering cast integrally or by a plate attached permanently to the main structure to indicate conspicuously:-
(a) Name of the manufacturer
(b) Name and number by which the equipment is identified.
(c) Number & date of the test report of the CSA Group applicable to the equipment.
(d) Equipment reference number of this letter by which use of apparatus is approved.
(e) Protection level. -
A certificate to the effect that the equipment has been manufactured strictly in accordance with the drawing referred to in the CSA Group Test report and is identical to the one tested and certified at CSA Group shall be furnished with each piece of equipment.
-
The customer shall be supplied with a copy of this letter, an extract of the conditions and maintenance schedule, if any, recommended by CSA Group in their test reports, and a copy of the instructions booklet detailing the operation & maintenance of the equipment so as to maintain its Flame Proof characteristics.
-
The After sales service and maintenance of subject equipment shall be looked after by your representative EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED, 147 RAJIV GANDHI SALAI (OMR) KARAPAKKAM VILLAGE CHENNAI 600097
This approval also covers the permissible variations as approved under the CSA
Group test reports referred above. This approval is liable to be cancelled if
any of the conditions of the approval is violated or not complied with. The
approval may also be amended or withdrawn at any time if considered necessary
in the interest of safety.
The field performance report from actual users/your customers of the subject
equipment may please be collected and furnished to this office for
verification and record on annual basis. The Approval is Valid up to
31/12/2025
Yours faithfully,
(K Srinivasa Rao)
Controller of Explosives
For Chief Controller of Explosives
Nagpur
Copy to:
- Jt. Chief Controller of Explosives, South Circle Office, CHENNAI
- EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED,147 RAJIV GANDHI SALAI (OMR) KARAPAKKAM VILLAGE CHENNAI 600097
for Chief Controller of Explosives
Nagpur
(For more information regarding status, fees, and other details please visit
our website http://peso.gov.in)
This is System Generated document. A signature is not required.
Ex ia IIC or IIB T5/T6 Ga
Ex ia IIC T4/T5/T6 Ga
Approval No: A/PA-IQ/TN/104/5985 (P505938)
To,
MN. Fisher Controls International LLC, 205 SOUTH CENTER STREET, Marshalltown
IA 50158
christopheranderson@emerson.com1641-7543747
U.S.A
Sub: Approval of Intrinsically Safe Type Electrical Equ under Petroleum
Rules 2002- Regarding. Sir(s),
Please refer to your letter No. 01N772383 dated 13/04/2021 on the subject. The
following Ex electrical equipment(s) manufactured by you according to IEC
60079-0: 2011, IEC 60079-11: 2011, standards and covered under CSA Group Test
reports mentioned below is/are approved for use in Zone 1, Zone 2 of Gas
1113/11C hazardous areas coming under the Petroleum Rules, 2002 administered
by this Organization.
Sr.
No| Description| Safety
Protection| Equipment. qp
reference
Number| | TestAgenc y| Drawing
no
---|---|---|---|---|---|---
Name| Certificate
No.| Certificate
Date
1| DVC6000 I DVC
6200 DIGITAL
VALVE
CONTROLLERS| Ex is IIC or
IIBT5fT6Ga
Ex is IIC
T41511-6 Ga| P606938/1| CSA Group| IECEx CSA
16.0003X
Issue No 3| 10/9/2020| GE 9603 GE
47752
This Approval is granted subject to observance of the following conditions:-
-
The design and construction of the equipment shall be strictly in accordance with the description, condition, and drawings, as mentioned in the CSA Group Test Reports, referred to above.
-
The equipment shall be used only with the approved types of accessories and associated apparatus.
-
Each piece of equipment shall be marked either by raised lettering cast integrally or by a plate attached permanently to the main structure to indicate conspicuously:-
(a) Name of the manufacturer
(b) Name and number by which the equipment is identified.
(c) Number & date of the test report of the GSA Group applicable to the equipment.
(d) Equipment reference number of this letter by which use of apparatus is approved.
(e) Protection level. -
A certificate to the effect that the equipment has been manufactured strictly in accordance with the drawing referred to in the CSA Group Test report and is identical to the one tested and certified at CSA Group shall be furnished with each piece of equipment.
-
The customer shall be supplied with a copy of this letter, an extract of the conditions and maintenance schedule, if any, recommended by CSA Group in their test reports, and a copy of the instructions booklet detailing the operation & maintenance of the equipment so as to maintain its Flame Proof characteristics.
-
The After sales service and maintenance of subject equipment shall be looked after by your representative EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED, 147 RAJIV GANDHI SALAI (OMR) KARAPAKKAM VILLAGE CHENNAI 600097
This approval also covers the permissible variations as approved under the CSA
Group test reports referred above. This approval is liable to be canceled if
any of the conditions of the approval is violated or not complied with. The
approval may also be amended or withdrawn at any time if considered necessary
in the interest of safety.
The field performance report from actual users/your customers of the subject
equipment may please be collected and furnished to this office for
verification and record on annual basis.
The Approval is Valid up to 31/12/2025
Yours faithfully,
(K Srinivasa Rao)
Controller of Explosives
For Chief Controller of Explosives
Nagpur
Copy to: 1. Jt. Chief Controller of Explosives, South Circle Office, CHENNAI
2. EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED,147 RAJIV GANDHI SALAI
(OMR) KARAPAKKAM VILLAGE CHENNAI 600097
for Chief Controller of Explosives Nagpur (For more information regarding
status, fees, and other details please visit our website http://peso.gov.in)
This is System Generated document. A signature is not required.
Ex ia IIC or IIB T4/T5/T6 Ga
Ex d IIC T4/T5/T6 Gb
Approval No: AP/HQ/TN/104/5988 (P505937)
To,
M/s. Fisher Controls International LLC, 205 SOUTH CENTER STREET Marshalltown
IA 50158
christopheranderson@emerson.com1641-7543747
U.S.A
Sub: Approval of Flame Proof, Intrinsically Safe Type E under Petroleum Rules
2002- Regarding.
Sir(s),
Please refer to your letter No. OIN779668 dated 15/04/2021 on the subject. The
following Ex electrical equipment(s) manufactured by you according to EN
60079-0: 2012/A11: 2013, EN 60079-1: 2014, EN 60079-11: 2012, standards and
covered under CSA Group Test reports mentioned below is/are approved for use
in Zone 1 of Gas IIB/IIC hazardous areas coming under the Petroleum Rules,
2002 administered by this Organisation.
Sr
No| Description| Safety
Protection| Equipment| | Test Agency|
---|---|---|---|---|---|---
reference
Number| Name
Name| Certificate
No.| Certificate
Date| Drawing
no
….._ —
|
| DVC6000 / DVC 6200 DIGITAL VALVE
CONTROLLERS| E> is IIC or
IIB
T4/T5/T6Ga
Ex d IIC –
T4/T5/T6
Gb| P505937 1| CSA
1..3,group| SIRA
19ATEX1241X
Issue No 2| 15/09/2020| GE 9603
GE
47752
This Approval is granted subject to observance of the following conditions:-
-
The design and construction of the equipment shall be strictly in accordance with the description, condition, and drawings, as mentioned in the CSA Group Test Reports, referred to above.
-
The equipment shall be used only with the approved types of accessories and associated apparatus.
-
Each equipment shall be marked either by raised lettering cast integrally or by a plate attached permanently to the main structure to indicate conspicuously:-
(a) Name of the manufacturer
(b) Name and number by which the equipment is identified.
(c) Number & date of the test report of the CSA Group applicable to the equipment.
(d) Equipment reference number of this letter by w hi ch use of apparatus is approved.
(e) Protection level. -
A certificate to the effect that the equipment has been manufactured strictly in accordance with the drawing referred to in the CSA Group Test report and is identical to the one tested and certified at CSA Group shall be furnished with each piece of equipment.
-
The customer shall be supplied with a con/ of this letter, an extract of the conditions and maintenance schedule, if any, recommended by CSA Group in their test reports, and a copy of the instructions booklet detailing the operation & maintenance of the equipment so as to maintain its Flame Proof characteristics.
-
The After sales service and maintenance of the subject equipment shall be looked after by your representative
EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED, 147 RAJIV GANDHI SALAI
(OMR) KARAPAKKAM VILLAGE CHENNAI 600097
This approval also covers the permissible variations as approved under the CSA
Group test reports referred above. This approval is liable to be canceled if
any of the conditions of the approval is violated or not complied with. The
approval may also be amended or withdrawn at any time if considered necessary
in the interest of safety.
The field performance report from actual users/your customers of the subject
equipment may please be collected and furnished to this office for
verification and record on annual basis. The Approval is Valid up to
31/12/2025
Yours faithfully,
(K Srinivasa Rao)
Controller of Explosives
For Chief Controller of Explosives
Nagpur
Copy to: 1. Jt. Chief Controller of Explosives, South Circle Office, CHENNAI
2. EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED,147 RAJIV GANDHI SALAI
(OMR) KARAPAKKAM VILLAGE CHENNAI 600097
for Chief Controller of Explosives Nagpur
(For more information regarding status, fees, and other details please visit
our website http://peso.gov.in)
This is System Generated document. A signature is not required.
Ex NC IIC T5/T6 Gc
Ex nA IIC T4/T5/T6 Gc
Approval No: AP/HCifTN/104/5981 (P505929) To,
MIs. Fisher Controls International LLC, 205 SOUTH CENTER STREET, Marshalltown
IA 50158
christopheranderson@emerson.com1641-7543747
U.S.A
Sub: Approval of Non-Sparking Type Electrical Equipment under Petroleum Rules
2002- Regarding.
Sir(s),
Please refer to your letter No. OIN779714 dated 13/042021 on the subject.
The following Ex electrical equipment(s) manufactured by you according to IEC
60079-0: 2011, IEC 60079-15: 2010, standards and covered under CSA Group Test
reports mentioned below is/are approved for use in Zone 2 of Gas IIC hazardous
areas coming under the Petroleum Rules, 2002 administered by this
Organization.
| | | Equipment,| | .
Test Agency|
---|---|---|---|---|---|---
Sr.
No| Description| Safety
Protection
I
reference
Number| Name| Certificate
No.| Certificate
Date| Drawing
no
| |
1| DVC6000 / DVC
6200 DIGITAL
VALVE
CONTROLLERS| Ex NC IIC
T5/T6 Gc,
Ex nA 11C
T4/T5/T6
Gc| P505929/1| CSA
Group| IECEx
CSA
16.0003X
Issue No 3| 10/9/2020| GE 9603
GE
47752
This Approval is granted subject to observance of the following conditions:-
-
The design and construction of the equipment shall be strictly in accordance with the description, condition, and drawings, as mentioned in the CSA Group Test Reports, referred to above.
-
The equipment shall be used only with the approved types of accessories and associated apparatus.
-
Each piece of equipment shall be marked either by raised lettering cast integrally or by a plate attached permanently to the main structure to indicate conspicuously:-
(a) Name of the manufacturer
(b) Name and number by which the equipment is identified.
(c) Number & date of the test report of the CSA Group applicable to the equipment.
(d) Equipment reference number of this letter by which use of apparatus is approved.
(e) Protection level. -
A certificate to the effect that the equipment has been manufactured strictly in accordance with the drawing referred to in the CSA Group Test report and is identical to the one tested and certified at CSA Group shall be furnished with each piece of equipment
-
The customer shall be supplied with a copy of this letter, an extract of the conditions and maintenance schedule, if any, recommended by CSA Group in their test reports, and a copy of the instructions booklet detailing the operation & maintenance of the equipment so as to maintain its Flame Proof characteristics.
-
The After sales service and maintenance of the subject equipment shall be looked after by your representative EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED, 147 RAJIV GANDHI SALAI (OMR) KARAPAKKAM VILLAGE CHENNAI 600097
This approval also covers the permissible variations as approved under the CSA
Group test reports referred above. This approval is liable to be canceled if
any of the conditions of the approval is violated or not complied with. The
approval may also be amended or withdrawn at any time if considered necessary
in the interest of safety.
The field performance report from actual users/your customers of the subject
equipment may please be collected and furnished to this office for
verification and record on annual basis. The Approval is Valid up to
31/12/2025
Yours faithfully,
(K Srinivasa Rao)
Controller of Explosives
For Chief Controller of Explosives
Nagpur
Copy to:
- Jt. Chief Controller of Explosives, South Circle Office, CHENNAI
- EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED,147 RAJIV GANDHI SALAI (OMR) KARAPAKKAM VILLAGE CHENNAI 600097
(For Chief Controller of Explosives Nagpur (For more information regarding
status, fees, and other details please visit our website http://peso.gov.in)
This is System Generated document. A signature is not required.
Ex nA IIC T6/T5/T4/ Gc
Ex NC IIC T5/T6 Gc
Approval No: A/P/HQ/T N/104/5987 ( P505936)
To,
M/s. Fisher Controls International L LC, 205 SOUTH CENT ER ST REET,
Marshalltown IA 50158
christopheranderson@aemerson.com1641-7543747
U.S.A
Sub: Approval of Non-Spaking Type Electrical Equipment under Petroleum
Rules 2002- Regarding.
Sir(s),
Please refer to your letter No. 01N779677 dated 15/04/2021 on the subject. The
following Ex electrical equipment(s) manufactured by you according to EN
60079.0: 2012/A11: 2013, EN 60079-15: 2010, standards and covered under C SA
Group Netherlands B.V. Test reports mentioned below is/are approved for use in
Zone 2 of Gas IIC hazardous areas coming under the Petroleum Rules, 2002
administered by this Organization.
Sr. No| Description| Safety
Protection| Equipment| | Test Agency
Certificate
No.| Certificate
Date| Drawing no
---|---|---|---|---|---|---|---
reference
Number| Name
1| DVC6000 / DVC 6203 DIGITAL VALVE
CONTROLLERS| Ex NAC
T6iT5/1″4/F3Gc,Ex
NC I IC T5/T6 Gc| P505936/1| CSA Group
Netherlands
B.V.| SI RA
19ATEX4242X
Issue No 2| 15/09/2020| GE 9603
GE
47752
This Approval is granted subject to observance of the following conditions:-
-
The design and construction of the equipment shall be strictly in accordance with the description, condition, and drawings, as mentioned in the C SA Group Netherlands B.V. Tint R, reports referred to above.
-
The equipment shall be used only with the approved types of accessories and associated apparatus.
-
Each piece of equipment shall be marked either by raised lettering cast integrally or by a plate attached permanently to the main structure to indicate conspicuously:-
(a) Name of the manufacturer
(b) Name and number by which the equipment is identified.
(c) Number & date of the test report of the CSA Group Netherlands B.V. applicable to the equipment.
(d) Equipment reference number of this letter by which use of apparatus is approved.
(e) Protection level. -
A certificate to the effect that the equipment has been manufactured strictly in accordance with the drawing referred to in the C SA Group Netherlands B.V. Test report and S identical with the one tested and certified at C SA Group Netherlands B.V.s shall be furnished with each equipment.
-
The customer shall be supplied with a copy of this letter, an extract of the conditions and maintenance schedule, if any, recommended by CSA Group Netherlands B.V. in their test reports, and a copy of the instructions booklet detailing the operation& maintenance of the equipment o as to maintain its Flame Proof characteristics.
-
The Alter sales service and maintenance of subject equipment shall be looked after by your representative EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED, 147 RAJIV GANDHI SALA! (OMR) KARAPAII<AM VILLAGE CHENNAI 600007
This approval also covers the permissible variations as approved under the CSA
Group Netherlands B.V. test reports referred above. This approval is liable to
be canceled if any of the conditions of the approval is violated or not
complied with. The approval may also be amended or withdrawn at any time if
considered necessary in the interest of safety.
The field performance report from actual users/your customers of the subject
equipment may please be collected and furnished to this office for
verification and record on annual basis. The Approval is Valid up to
3111212025
Yours faithfully,
(K Srinivasa Rao)
Controller of Explosives
For Chief Controller of Explosives
Nagpur
Copy to: 1. Jt. Chief Controller of Explosives, South Circle Office, CHENNAI
2. EMERSON PROCESS MANAGEMENT CHENNAI PRIVATE LIMITED,147 RAJIV GANDHI SALAI
(OMR) KARAPAKKAM VILLAGE CHENNAI 600097
for Chief Controller of Explosives Nagpur (For more information regarding
status, fees, and other details please visit our website http://peso.gov.in)
This is System Generated document. A signature is not required.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated
entities assume responsibility for the selection, use, or maintenance of any
product. Responsibility for proper selection, use, and maintenance of any
product remains solely with the purchaser and end user. FIELDVUE and Fisher
are marks owned by one of the companies in the Emerson Automation Solutions
business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson,
and the Emerson logo are trademarks and service marks of Emerson Electric Co.
All other marks are the property of their respective owners. The contents of
this publication are presented for informational purposes only, and while
every effort has been made to ensure their accuracy, they are not to be
construed as warranties or guarantees, express or implied, regarding the
products or services described herein or their use or applicability. All sales
are governed by our terms and conditions, which are available upon request. We
reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil ”
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
2017, 2022 Fisher Controls International LLC. All rights reserved.
DVC6200
February 2022
Documents / Resources
|
Emerson PESO India Certificates for Fisher™ FIELDVUE™ DVC6200 Series Digital
Valve
Controllers
[pdf] User Manual
D104293X012 PESO India Certificates for Fisher FIELDVUE DVC6200 Series Digital
Valve Controllers, D104293X012, PESO India Certificates for Fisher FIELDVUE,
DVC6200 Series Digital Valve Controllers, D104293X012 DVC6200 Series Digital
Valve Controllers, D104293X012 Digital Valve Controllers
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>