EMERSON MU1-FLS MU1 Aventics Standard Filter Instruction Manual
- June 4, 2024
- Emerson
Table of Contents
- About this documentation
- Notes on safety
- Scope of delivery
- Assembly, commissioning, and operation
- Maintenance and repairs
- Decommissioning, disassembly, exchange
- Disposal
- Troubleshooting
- Key Technical Information
- Appendix
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AVENTICS™ MU1
Filter
Condensate separator
R412021818-BAL-001-AC
2022-04; Replaces 2014-05
DE/EN/FR/IT/ES/SV
Operating instructions
About this documentation
These instructions contain important information for the safe and appropriate assembly and commissioning of the product.
- Read these instructions carefully, especially chapter g 2. Notes on safety before you start working with the product.
1.1 Additional documentation
- Read and follow the operating instructions for the MU1 series maintenance unit.
- Also, follow the instructions for the other system components.
- Please also observe the generally relevant, statutory, and other binding regulations of European and national legislation and the national regulations for accident prevention and environmental protection in your country.
1.2 Presentation of information
1.2.1 Warnings
In this document, there are warning notes before the steps whenever there is a
danger of personal injury or damage to equipment. The measures described to
avoid these hazards must be followed.
Structure of warnings
SIGNAL WORD
Hazard type and source
Consequences of non-observance
- Precautions
Meaning of the signal words
CAUTION
A possible dangerous situation.
Failure to observe these notices may result in minor injuries or damage to
property.
1.2.2 Symbols
Recommendation for the optimum use of our products.
Observe this information to ensure the smoothest possible operation.
Notes on safety
The product has been manufactured according to the accepted rules of current technology. Even so, there is a risk of injury or damage if the following general safety instructions and the specific warnings given in this instruction manual are not observed.
- Please read all these instructions carefully before working with the product.
- Keep these instructions in a location where they are accessible to all users at all times.
- Always include the operating instructions when you pass the product on to third parties.
2.1 Intended use
The product is exclusively intended for installation in a machine or system,
or for combination with other components to form a machine or system. The
product may only be commissioned after it has been installed in the
machine/system for which it is intended.
Use is permitted only under the operating conditions and within the
performance limits listed in the technical data. Only use compressed air as
the medium.
The product is technical equipment and is intended for professional use only.
Intended use includes having fully read and understood these instructions,
especially chapter g 2. Notes on safety.
2.2 Improper use
It is considered improper use when the product
- is used for any application not stated in these instructions or
- is used under operating conditions that deviate from those described in these instructions.
2.3 Personnel qualifications
All tasks associated with the product require basic mechanical, pneumatic, and
electrical knowledge, as well as knowledge of the respective technical terms.
In order to ensure operational safety, these tasks may only be carried out by
qualified personnel or an instructed person under the direction of qualified
personnel.
Qualified personnel is those who can recognize possible dangers and institute
the appropriate safety measures, due to their professional training,
knowledge, and experience, as well as their understanding of the relevant
regulations pertaining to the work to be done. Qualified personnel must
observe the rules relevant to the subject area.
2.4 General safety instructions
- Observe the valid local regulations to protect the environment in the country of use and to avoid workplace accidents.
- Only use AVENTICS products that are in perfect working order.
- Examine the product for obvious defects, such as cracks in the housing or missing screws, caps, or seals.
- The warranty will not apply if the product is incorrectly assembled.
- Do not place any improper mechanical loads on the product under any circumstances.
- Product warnings and information must be legible, i.e. not covered by paint, etc.
2.5 Safety instructions related to the product and technology
- Lay cables and lines so that they cannot be damaged and no one can trip over them.
- Do not operate the product in aggressive ambient air (e.g., solvent vapors).
- No soiling may be allowed to collect on or in the filters, reservoirs or windows.
Replace reservoirs if soiling cannot be removed from the drain (drain may become clogged).
Scope of delivery
The scope of delivery includes:
- 1x filter (FLS) (according to the order)
- 1x condensate separator (according to the order)
- 1 set of operating instructions
Assembly, commissioning, and operation
CAUTION
The danger of injury if assembled under pressure or voltage!
Assembling when under pressure or electrical voltage can lead to injuries and
damage to the product or system components.
- Make sure that the relevant system component is without pressure and voltage before you assemble the product.
- Protect the system against being restarted.
CAUTION
Sudden pressure increases during commissioning!
If no SSU filling valve is used, the system will suddenly be under pressure
during commissioning! This may result in dangerous erratic cylinder motions.
- When commissioning a system, make sure that the cylinders are in their end position. For cylinders not in the end position, make sure they do not present any danger.
CAUTION
The system is operating under pressure!
Incorrect installation may damage the maintenance unit/maintenance equipment
and cause serious injury.
- Before commissioning, check that all connections, ports, and maintenance equipment have been correctly installed.
4.1 Filter
The FLS filter is a maintenance unit component:
The passing compressed air will be roughly freed of solid contaminants and
condensation water via centrifugal force and the filtration effect.
Steps at a glance
- Mounting fastening elements. See → Fig. 7.
- Connect the filter to the tubing system. See → Fig. 9.
- Operating the condensate drain. See → Fig. 1, → Fig. 2, → Fig. 3.
4.1.1 Semi-automatic condensate drain
CAUTION
Potential impairment of compressed air system by condensate!
In the case of the semi-automatic condensate drain, condensate is only
discharged when the reservoir is without pressure. If in operation for an
extended period, the condensate may exceed the maximum filling level and find
its way into the compressed air system. This may result in damage to the
compressed air system.
- Regularly check the filling level in the reservoir.
- Drain condensate manually once it reaches the maximum filling level.
- Do not let the condensate run off into the surroundings.
See → Fig. 1.
The semi-automatic condensate drain closes at a pressure > 1.5 bar and opens
at an operating pressure < 1.5 bar.
Setting the automatic mode:
If the drain screw is screwed in completely, the automatic drainage is blocked.
- Open the drain screw by turning it all the way to the left.
You may leave the screw one turn deep in the thread or remove it completely.
4.1.2 Fully automatic condensate drain
See → Fig. 2.
“Normally open” configuration
In the “normally open” configuration, the condensate drain closes at a
pressure > 1.5 bar and opens at an operating pressure < 1.5 bar.
The valve opens automatically as soon as the floater reaches the highest point
and closes again when the floater reaches the lowest point.
Setting the automatic mode:
If the drain screw is screwed in completely, the automatic drainage is blocked.
- Turn the drain screw to the right as far as it will go.
You may leave the screw one turn deep in the thread or remove it completely.
“Normally closed” configuration
The condensate drain is closed regardless of the operating pressure. The valve
opens automatically as soon as the floater reaches the highest point and
closes again when the floater reaches the lowest point.
4.1.3 Manual condensate drain
See g Fig. 3.
The condensate (b = max. fill level) can be drained manually.
- Turn drain screw (a) to the left a few times until the condensate runs out.
- Turn drain screw (a) all the way to the right (closed position).
Draining condensate via a tubing
- Turn the drain screw (a) to the left and remove it.
- Attach one end of the tubing to the reservoir and insert the other end into a receptacle.
4.2 Condensate separator
See → Fig. 6.
The condensate separator discharges condensate and oil from the compressed air
network.
4.2.1 Connecting the condensate separator to the tubing system or maintenance
unit
The ideal mounting position is at the lowest point of the compressed air
network.
- Connect the condensate separator. See → Fig. 8.
- Screw the tube into the selected G 1/2 connection.
4.2.2 Semi-automatic condensate drain
The semi-automatic condensate drain closes at a pressure > 1.5 bar and opens
at an operating pressure < 1.5 bar.
Setting the automatic mode:
If the drain screw is screwed in completely, the automatic drainage is blocked.
- Turn the locking wheel (b) all the way to the left.
You may leave the screw one turn deep in the thread or remove it completely.
4.2.3 Connecting the tubing
A tubing (a) can be plugged onto the oil drain at the bottom for controlled
oil drainage.
- Turn the locking wheel (b) to the left and remove it.
- Attach one end of the tubing to the reservoir (a) and insert the other end into a receptacle.
Maintenance and repairs
5.1 Cleaning and servicing
- Close all openings with suitable safety devices so that no cleaning agent can enter the system.
- Never use solvents or aggressive detergents. Only clean the product using a slightly damp cloth. Only use water and, if necessary, a mild detergent.
- Do not use high-pressure cleaners for cleaning.
- Do not use compressed air for cleaning (blowing off) the maintenance unit or equipment.
Decommissioning, disassembly, exchange
CAUTION
The danger of injury in case of disassembly or replacement under pressure or
voltage!
Disassembling or replacement when under pressure or electrical voltage may
lead to injuries and damage to the product or system components.
- Make sure that the relevant system part is not under pressure or voltage before disassembling the product or exchanging parts.
- Protect the system against being restarted.
6.1 Filter
Exchanging the filter element
CAUTION
The system is operating under pressure!
Opening the system when it is under pressure can result in personal injury and
cause damage to the maintenance unit/device.
- Please ensure that the system is not under pressure before you open the reservoir.
Filters become contaminated with use and must be changed annually. This,
however, is only a recommendation, since the change intervals depend on the
quality of the compressed air and the amount of air throughput.
Please use the material numbers listed below to order. The addresses of the
AVENTICS GmbH international agencies can be found on the back.
Wearing parts | MU1 |
---|---|
Filter elements: | |
8 µm | R961400124 |
40 µm | 1.83E+09 |
60 µm | R961400125 |
Procedure
See → Fig. 4, → Fig. 5.
- Release the ring (a) and pull it off downwards (b).
- Release the protective guard (c), if present, and pull it off downwards.
- Pull off the reservoir (d) and the seal (e) downwards.
- Remove the filter seat (f, g).
- Exchange the filter piece (h).
- Slide the filter unit (filter seat and filter piece) back together.
- Connect the filter unit to the filter and tighten it slightly by hand (i).
- Remount the reservoir in the reverse order shown in g Fig. 4.
Disposal
Dispose of the product and fluid in accordance with the national regulations in your country.
Troubleshooting
Malfunction | Possible cause | Remedy |
---|---|---|
No flow | Soiled filter | Clean or replace the filter |
Pressure/flow level is not reached or drops off slowly. | Soiled filter | Clean |
or replace the filter
The selected filter is too small| Select larger filter
Key Technical Information
Maximum permissible pressure and thread connection are indicated on the products.
General data
Mounting orientation | Vertical |
---|
Further technical data can be found in the online catalog.
Appendix
Figures: View varies according to the series.
Fig. 1: Semi-automatic condensate drain
Fig. 2: The fully automatic condensate drain
Fig. 3: Draining condensate manually
Fig. 4: Assembling/disassembling the reservoir and protective guard
Fig. 5: Replacing the filter
Fig. 6: Condensate separator
Fig. 7: Mounting fastening elements
Fig. 8: Connecting the condensate separator
Fig. 9: Connecting the filter
The data specified above only serve to describe the product. No statements
concerning a certain condition or suitability for a certain application can be
derived from our information.
The given information does not release the user from the obligation of own
judgment and verification. It must be remembered that our products are subject
to a natural process of wear and aging.
An example configuration is depicted on the title page. The delivered product
may thus vary from that in the illustration.
Translation of the original operating instructions. The original operating
instructions were created in the German language.
Subject to modifications. © All rights reserved by AVENTICS GmbH, even and
especially in cases of proprietary rights applications. This document may not
be reproduced or given to third parties without our consent.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
AVENTICS a mark of one of the Emerson Automation Solutions family of business
units. All other marks are property of their respective owners.
Emerson Automation Solutions
AVENTICS GmbH
Ulmer Straße 4
30880 Laatzen, GERMANY
phone +49 511 2136-0
fax +49 511 2136-269
www.emerson.com/aventics
aventics@emerson.com
Further addresses:
www.emerson.com/contactus
References
- AVENTICS – Smart, reliable solutions for pneumatic automation | Emerson US
- Contact Us | Emerson US
- Contact Us | Emerson US
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>