AVR45 SERIES – RAILWAY APPLICATION
INSTALLATION AND
OPERATION MANUAL
unity II AVR45 Series Railway Application
California Proposition 65 Warning:
Batteries, battery posts, terminals, and related accessories contain lead and
lead compounds, and other chemicals are known to the state of California to
cause cancer and birth defects or other reproductive harm. Wash hands after
handling.
DANGER Lead Acid Battery Contains Lead, Sulfuric Acid (Electrolyte), and
Lead Compounds.
Harmful if swallowed, inhaled, or in contact with skin.
Acid causes severe skin burns and eye damage.
May damage fertility or the unborn child if ingested or inhaled.
May cause harm to breastfed children.
May cause cancer if ingested or inhaled.
Causes skin irritation, and serious eye damage.
Contact with internal components may cause irritation or severe burns.
Causes damage to the central nervous system, blood, and kidneys through
prolonged or repeated exposure if ingested or inhaled. Irritating to eyes,
respiratory system, and skin. May form an explosive air/gas mixture during
charging. Extremely flammable gas (hydrogen). Explosive, fire, blast or
projection hazard. Obtain special instructions before use. Do not handle until
all safety precautions have been read and understood. Wash thoroughly after
handling.
Do not eat drink or smoke when using this product. Avoid contact during
pregnancy/while nursing.
Wear protective gloves/protective clothing, eye protection/face protection.
Use only outdoors or in a well-ventilated area. Avoid contact with internal
acid.
Do not breathe dust/fume/gas/mist/vapors/spray. Keep away from
heat/sparks/open flames/hot surfaces.
No smoking. IF SWALLOWED OR CONSUMED: rinse mouth.
Do NOT induce vomiting. Call a poison center/doctor if you feel unwell.
IF ON CLOTHING OR SKIN (or hair): Removeltake off immediately all contaminated
clothing and wash it before reuse.
Rinse skin with water/shower.
IF INHALED: Remove the person to fresh air and keep comfortable for breathing.
Immediately call a POISON CENTER or doctor/physician.
IF IN EYES: Rinse cautiously with water for several minutes. Remove contact
lenses, if present, and easy to do. Continue rinsing.
If exposed/concerned, or if you feel unwell seek medical attention/advice.
Store locked up, in a well-ventilated area, in accordance with local and
national regulations.
Dispose of contents/containers in accordance with local and national
regulations.
Keep out of reach of children.
PROPOSITION 65 WARNING: battery posts, terminals, and related accessories
contain lead and lead compounds, chemicals known to the State of California to
cause cancer and reproductive harm. Batteries also contain other chemicals
known to the State of California to cause cancer. WASH HANDS AFTER HANDLING.
WARNING: Risk of fire, explosion, or burns. Do not disassemble or
incinerate. Not recommended for inverted use. Follow product charging
instructions. High Voltage: Risk of shock. Do not touch uninsulated terminals
or connectors.
Do Not Remove the Vent Valve
Manufactured by: East Penn Manufacturing Co.
102 Deka Road, Lyon Station, PA 19536 USA
610-682-6361
BATTERIES
AND OTHER RELATED PARTS
CONTAIN LEAD
WARNING: Battery posts, terminals, and related accessories contain lead and
lead compounds, chemicals are known to the State of California to cause cancer
and reproductive harm.
Batteries also contain other chemicals known to the State of California to
cause cancer. WASH HANDS AFTER HANDLING!
Form No: 1314 Rev. 8108 Must be posted in the workplace near batteries.
IN REFERENCE TO THIS MANUAL
- “Cell” is defined as an individual 2-volt unit.
- “Battery string” is defined as a series connected electrical system comprised of cells (individual 2-volt units).
SAFETY PRECAUTIONS
Although all valve-regulated cells have the electrolyte immobilized within the
cell, the electrical hazard associated with batteries still exists. Work
performed on these batteries should be done with the tools and the protective
equipment listed below. ValveRegulated cell installations should be supervised
by personnel familiar with batteries and battery safety precautions.
WARNING: Risk of fire, explosion, or burns. Do not disassemble, heat
above 40°C, or incinerate.
Protective Equipment
Although VRLA cells can vent or leak small amounts of electrolyte, electrical safety is the principle but not the only concern for safe handling. Per IEEE 1188 recommendations, the following minimum set of equipment for the safe handling of the cells and protection of personnel shall be available:
- Safety glasses with side shields, or goggles, or face shields as appropriate. (Consult application-specific requirements)
- Electrically insulated gloves, appropriate for the installation.
- Protective aprons and safety shoes.
- Portable or stationary water facilities in the battery vicinity for rinsing eyes and skin in case of contact with acid electrolyte.
- Class C fire extinguisher.
- Acid neutralizing agent.
- Adequately insulated tools (as defined by ASTM F1505 “Standard Specification for Insulated and Insulating Hand Tools) 8. Lifting devices of adequate capacity, when required.
Procedures
The following safety procedures should be followed during installation:
Always wear safety glasses or a face shield when working on or near batteries.
- These cells are sealed and contain no free electrolytes. Under normal operating conditions, they do not present any acid danger. However, if the cell jar or cover is damaged, acid could be present. Sulfuric acid is harmful to the skin and eyes. Flush the affected area with water immediately and consult a physician if splashed in the eyes. Consult SDS for additional precautions and first aid measures.SDS sheets can be obtained at www.eastpennmanufacturing.com
- Prohibit smoking and open flames, and avoid arcing in the immediate vicinity of the battery.
- Do not wear metallic objects, such as jewelry, while working on batteries. Do not store un-insulated tools in pockets or tool belts while working in the vicinity of the battery.
- Keep the top of the battery dry and clear of all tools and other foreign objects.
- Provide adequate ventilation (per IEEE standard 1187 and/or local codes) and follow recommended charging voltages.
- Never remove or tamper with the pressure relief valves. Warranty void if vent valve is removed.
- Inspect all flooring and lifting equipment for functional adequacy.
- Adequately secure battery modules, racks, or cabinets to the floor.
- Connect support structures to the ground system in accordance with applicable codes.
- The IEEE Standards contain additional information.
Other standards may be relevant to your specific application.
IEEE 1184 – Guide for Batteries for UPS Systems
IEEE1187 – Recommended Practice for Installation Design of VRLA Batteries.
IEEE 1188 – Recommended Practice for Maintenance, Testing, of VRLA Batteries.
IEEE 1189 – Selection of VRLA Batteries for Stationary Applications
RECEIVING & STORAGE
Receiving Inspection
Upon receipt, and at the time of actual unloading, each package should be
visually inspected for any possible damage or electrolyte leakage. If either
is evident, a more detailed inspection of the entire shipment should be
conducted and noted on the bill of lading. Record receipt date, and inspection
data, and notify the carrier of any damage.
Unpacking
- Always wear eye protection.
- Check all batteries for visible defects such as cracked containers, loose terminal posts, or other unrepairable problems. Batteries with these defects must be replaced.
- Check the contents of the package against the packaging list. Report any missing parts or shipping damage to your East Penn agent or East Penn Mfg. Co. immediately.
- Never lift the batteries by the terminal posts.
- When lifting batteries, the proper equipment is needed such as a forklift or a portable crane. Always check the lifting capacities of the equipment being used and never lift more than one cell at a time by the handles in the metal sleeve.
Storage / Refresh
Cells should be installed, and float charged upon delivery. If cells are to be
stored, the below requirements shall be followed.
-
Cells shall be stored indoors in a clean, level, dry, cool location.
-
Store, charge, and ship in a horizontal position only.
-
Recommended storage temperature is 50°F (10°C) to 77°F (25°C). The acceptable storage temperature is 0°F (-18°C) to 90°F (32°C).
-
The cells shall be given a refresh charge at regular intervals as detailed below:
0°F(-18°C) to 77°F (25°C)
Cells shall be charged by the “battery charge date” marked on a pallet. Successive recharges shall be performed every 6 months.
78°F (26°C) to 90°F (32°C)
Cell voltage readings shall be taken monthly. Cells must be given a refresh charge within 3 months from the date of receipt or if any cell voltage falls below 2.12 vpc, whichever occurs first. Successive refresh charges shall be performed every 3 months. -
Whenever a refresh charge is required, it’s important that all batteries to be installed in the same series string receive a charge at the same time to ensure continuity once placed in their intended application.
-
Each cell shall be charged for 24 hours at a constant voltage equal to 2.40 volts per cell. To ensure the cells are fully charged within 24hrs, the charger used for this refresh charge must have the capacity to provide at least the minimum charge current specification and not exceed the maximum charge current for the given cell type (model), as called out in Appendix C.
-
All requested information on the “Refresh Record Form” in Appendix A should be completed for each refresh charge.
-
Cells shall not be stored beyond 12 months. Storing beyond 12 months will affect the warranty.
-
If the storage/refresh requirements cannot be met, contact East Penn Reserve Power Product Support Department for alternate instructions.
INSTALLATION
General
Caution should be taken when installing batteries to ensure no damage occurs.
The battery string cabinet, tray, rack, etc. shall be inspected for sharp
edges that could cause damage to the battery casing. Batteries shall not be
dropped, slid, or placed on rough or uneven surfaces such as tray lips or
grated flooring. Mishandling of batteries could result in equipment damage or
human injury. East Penn will not be liable for damage or injury as a result of
mishandling or misuse of the product.
Grounding
When grounding the battery string, proper techniques should be applied per
electrical standards, such as NEC and/or local codes as well as the User
Manual of specific applications.
Note: Battery system grounding and/or individual module grounding, if
required, is the installer’s responsibility.
Racks
Assemble racks in accordance with the intended arrangement, align them with a
level and bolt them to the floor. Consult applicable rack assembly
instructions for specifics.
Electric Code for Maintenance Access
Refer to ANSI/NFPA-70 National Electric Code for access and working space
requirements around the battery. A minimum of 36″ aisle space is required in
front of the battery system for service and inspection.
Hardware Torque/Retorque Requirements
Bolt Size | Torque / Re-torque |
---|---|
1/4/2020 | 125 in-lb |
SYSTEM INSTALLATION
Cell Installation
Assemble the system per the following details.
CAUTION: Never lift more than one cell at a time.
- Ensure sufficient space has been allowed for proper and safe battery installation and maintenance.
- If cells are to be installed on a rack or cabinet, follow the rack/ cabinet manufacturer instructions for correct installation.
- Batteries may be installed with posts in a vertical or horizontal position. When installing in a horizontal or vertical position, ensure battery posts are provided with ample clearance from metal parts of the rack/cabinet.
ELECTRICAL CONNECTION
Connector / Cable Assembly
- The contact surfaces of each individual post on every cell have been cleaned and coated with a thin film of NO-OX-ID “A” grease at the factory. Ensure the contact surfaces are free of dust or dirt prior to assembly. Re-application of NO-OX-ID “A” grease may be required if post-cleaning is required.
- Connectors/cable lugs supplied with cells. It is recommended all connectors/cables be coated with a thin film of NO-OX-ID “A” grease.
- Install the cables loosely to allow for final alignment. Spacing between cells should be a minimum of 0.50” (12.7mm) for even airflow around cells.
4. For multipost batteries (17 to 33 plate) a connector is to be installed at the battery system positive and negative end of each multiple-cell configuration. This connector is used to electrically tie all same polarity posts together.![Deka unigy II AVR45 Series Railway Application
-
3](https://manuals.plus/wp-content/uploads/2022/10/Deka-unigy-II-AVR45 -Series-Railway-Application-3.jpg)
-
Charging/load cable(s) should be tin or lead-plated copper lugs able to accept a 1/4 –20 bolt. Cable lugs should be coated with a thin film of NO-OX-ID “A” grease. System connecting cables can be attached to any battery post of the multipost connector. A system connecting cable(s) supplied by others.
Select cable size based on current carrying capability and voltage drop.
-
Reference Appendix D for layout drawings detailing cable and connector quantity and placement.
-
Upon completion of installation, all connectors/cables hardware should be torqued to 125 ± 5-inch pounds (14.1 ± .5 Nm).
-
Final Assembly Check Procedure
Final Assembly Check Procedure
- For future identification of all cells, number individual cells in sequence, beginning with number one (1) at the positive end of the battery. The last cell of the battery string is located at the negative output terminal.
- Read and record the voltages of the cells to assure that they are connected properly. The total battery string voltage should be approximately equal to the number of cells connected in series multiplied by the measured voltage of one cell. If the measurement is less, recheck the connections for proper polarity. Verify that all cell and battery string connections have been properly torqued.
- Measure and record the intercell connection resistance using a micro-ohms meter. This helps determine the adequacy of initial connection installation and can be used as a reference for future maintenance requirements. Refer to the recording forms in the Battery Maintenance Report in Appendix E of this manual. Review the records of each connection and detail resistance measurements. Clean, remake, and re-measure any connection that has a resistance measurement greater than 10% of the average of all the same type connections (i.e. intercell, intermodal, etc.).
- Battery string performance is based on the output at the battery terminals. Therefore, the shortest electrical connection between the battery system and the operating equipment results in maximum total system performance.
Select cable size based on current carrying capability and voltage drop.
Cable size should not provide a greater voltage drop between the battery
string and operating equipment than required. Excessive voltage drop in cables
will reduce the desired reserve time and power from the battery string.
Cable sizing is the responsibility of the site electrical engineer.
SYSTEM OPERATIONS
Charger Voltage
2.25 V per battery ± 0.01 @ 77°F (25°C)
When setting the float voltage on the charger, the battery string should be
set to float at the required cell float voltage times the number of cells per
battery string. The charger must be able to maintain the battery string
voltage within ± 0.5% of the desired level at all times.
Charge Current
Charge current should not exceed the recommended minimum and maximum
requirements as detailed in Appendix C.
Temperature Compensation
Battery voltage should be adjusted for ambient temperature variations.
2mV per °C (1.8°F) per 2V cell.
Consult Voltage Compensation Chart (Appendix C) for temperature compensation
voltage maximum and minimum limits.
Cell Voltage
Although the charger must maintain the battery string voltage within ± 0.5%,
individual cell voltages may vary by ± 0.05 volts of the average cell float
voltage.
Equalizing
Upon installation of the battery string, an optional charge at a constant
voltage equal to 2.40V per cell ± 0.01 @ 77°F (25°C) for a maximum of 24hrs
may be performed. (NOTE: Verify that the higher cell voltage will not
adversely affect any other connected equipment). If this is done, be sure to
reset the charging equipment to the proper
float voltage.
Battery Operation
Battery string operating temperature will affect battery string capacity
and operating life.
Temperatures greater than 77°F (25°C) will reduce the operating life of the
battery. For every 13°F (7°C) increase in operating temperature above 77°F
(25°C), the warranty period will be proportionally reduced by 50% as shown
below:
Operating Temperature| Proportional
Percentage (%) of Life
---|---
ºF| ºC
77º| 25º| 100%
81º| 27º| 80%
87º| 30º| 60%
90º| 32º| 50%
It is not recommended to operate the battery string above 95°F (35°C). If
operating temperatures are expected to be in excess of 95°F (35°C), contact
East Penn for recommendations. Operating a battery string over 105°F (40.5°C)
for more than 8 hours may void the warranty.
Discharging at temperatures less than 77°F (25°C) will reduce the capacity of
the battery and require longer charging time to become fully charged. If
operating temperatures are
expected to be less than 50°F (10°C) contact East Penn for recommendations.
The battery string must be located in a manner that the individual cells do
not vary by more than 5°F (2.8°C) between the lowest and highest individual
cell temperature.
Rectifier Ripple Voltage
FREQUENCY
A ripple that has a frequency greater than 667Hz (duration less than 1.5ms) is
acceptable unless it is causing additional cell heating.
A ripple that has a frequency less than 667Hz (duration greater than 1.5ms),
must meet the following voltage specification to be acceptable.
VOLTAGE
Ripple voltage shall be less than 0.5% peak-to-peak (0.177% RMS) of the
manufacturer’s recommended battery string voltage. Failure to comply can void
the warranty.
RECORD KEEPING
Voltages, Temperatures & Ohmic Readings
Record keeping is an important part of stationary battery maintenance and
warranty coverage. This information will help in establishing a life history
of the battery string and inform the user if and when corrective action needs
to be taken. All measuring equipment should be in good operating condition and
accuracy should be confirmed on an annual basis to NIST traceable standards.
After installation and when the battery string has been on float charge for
one week, the data as detailed in the “Maintenance Section” should be
recorded. Battery Maintenance Report worksheet provided in Appendix E. Failure
to maintain proper records including information as detailed below may result
in voiding any applicable warranty.
Acceptance Testing
Each cell should be at 100% State of Charge prior to performing an acceptance
test on the battery system. To ensure the cells are fully charged the
following charge schedule should be followed.
Cells should be charged at the equalization rate of 2.40 volts per cell for 24
hours. Temperature-compensated charging parameters shall be applied as
detailed in “Temperature Compensation” in Appendix C of this manual.
To ensure the cells are fully charged within 24hrs; the charger used for this
charge must have a current equal to the maximum charge current for the given
cell type (model), as called out in Appendix B
If these requirements cannot be met, contact East Penn Reserve Power’s Product
Support group for alternate instructions.
Upon completion, the charge voltage should be lowered to the float voltage of
2.25 volts per cell for a minimum period of 72 hours. Reference: IEEE
1188-2005 Section 7.2 for additional acceptance test requirements.
Upon completion of the above charge, the desired acceptance test can be
performed.
NOTE: There shall be no discharges of any duration between the start of
the equalization and the completion of the float period. If a discharge does
occur, the charging regime detailed above shall be repeated.
Upon completion of the acceptance test, the battery system should be placed on
float charge at 2.25 volts per cell to restore the battery to its’ rated
capacity.
Batteries should not require an equalization charge once they have passed
their initial acceptance test. Consult with East Penn Reserve Power Product
Support Department before performing additional equalizing charges on
batteries that have successfully passed their initial acceptance test.
MAINTENANCE
Always wear eye protection when working on or near batteries. Keep sparks and
open flames away from batteries at all times. See Safety Precautions on pg. 3.
Annual Inspection¹
- Conduct a visual inspection of each cell.
- Record the battery string voltage.
- Record the charger voltage.
- Record the individual cell voltages. The accuracy of the DMM (Digital Multimeter) must be .05% (on the dc scale) or better. The DMM must be calibrated to NIST traceable standards. Because float readings are affected by dis¬charges and recharge, these readings must be taken when batteries have been on a continuous, uninterrupted float for at least one month. Cells should be within ± 0.05 volts of the average cell float voltage.
- Record the ambient temperatures.
- Record individual cell ohmic readings.
- Record all intercell, interunit, and terminal connection resistances. Micro-ohm readings should be taken during this inspection. If any reading differs by more than 20% from the initial readings taken, retorque the connection. Recheck the micro-ohm reading. If the reading remains high, clean the contact surface according to the installation portion of this manual.
¹Other maintenance inspection intervals follow IEEE 1188
Battery Cleaning
- Disconnect the battery system from the power source.
- Dust accumulation can be removed with a cloth dampened with clean water.
- Corrosion buildup should be neutralized using a mixture of baking soda and water or East Penn Mfg supplied battery cleaner (part # 00321).
- Use a cloth dampened with clean water to remove residue.
Never use solvents to clean the battery.
Capacity Testing
Per IEEE 1188 “Capacity testing is used to trend battery aging. The result of
a capacity test is a calculation of the capacity of the battery. The
calculated capacity is also used to determine if the battery requires
replacement”.
When performing capacity testing and recording data refer to IEEE 1188
recommendations.
NOTE: When discharging at higher rates, extra connectors may be needed to
be added to prevent excessive voltage drop and/or excessive temperature rise.
Should it be determined that and battery(ies) need to be replaced contact your
nearest East Penn agent or East Penn Service Center.
APPENDIX A
| REFRESH RECORD FORM
---|---
EPM Order Number*| Pallet ID Number| Individual Performing Test (Full Name)|
RD: freesia| Refresh Duration
| | | |
Model
Number| Information Prior to Refresh| Information within 1 our 01
Refresh Completion| Notes & Comments
Date
Code| SeriCellal Number| Open Circuit Voltage| Cell
Voltage
Reading| Charging
Current| Cell
Temperature
Cell 1| | | | | | | |
Cell 2| | | | | | | |
Cell 3| | | | | | | |
Cell 4| | | | | | | |
Cell 5| | | | | | | |
Cell 6| | | | | | | |
Cell 7| | | | | | | |
Cell 8| | | | | | | |
Cell 9| | | | | | | |
Cell 10| | | | | | | |
Cell 11| | | | | | | |
Cell 12| | | | | | | |
Cell 13| | | | | | | |
Cell 14| | | | | | | |
Cell 15| | | | | | | |
Cell 16| | | | | | | |
Cell 17| | | | | | | |
Cell 18| | | | | | | |
Cell 19| | | | | | | |
Cell 20| | | | | | | |
Cell 21| | | | | | | |
Cell 22| | | | | | | |
Cell 23| | | | | | | |
Cell 24| | | | | | | |
ALL FIELDS TO THE RIGHT OF THE CELL NUMBER ABOVE MUST BE COMPLETED
EPM ORDER NUMBER WILL APPEAR ON THE SHIPPING LABEL ON THE CARTON COVERING EACH
PALLET OF CELLS
TO ENSURE CONTINUATION OF WARRANTY, SUBMIT FORMS TO: East Penn Mfg. Co, Inc.,
Reserve Power Division, Product Support & Warranty Dept.
(reservepowerwarranty@dekabatteries.com)
APPENDIX B
Unigy II AVR45 Series Battery Weight & Acid Volumes
__**Battery Type| __**Cell Weight| Electrolyte (per
cell)| Pure Acid (per battery
---|---|---|---
Volume| Weight| Weight
lb| kg| gal| liter| lb| kg| lb| kg
AVR45-5| 18| 8| 0.37| 1.40| 4.00| 1.81| 1.60| 0.72
AVR45-7| 25| 11| 0.52| 1.96| 5.60| 2.54| 2.24| 1.02
AVR45-9| 32| 15| 0.67| 2.52| 7.22| 3.28| 2.89| 1.31
AVR45-11| 39| 18| 0.81| 3.08| 8.83| 4.00| 3.53| 1.60
AVR45-13| 46| 21| 0.96| 3.64| 10.43| 4.73| 4.17| 1.89
AVR45-15| 53| 24| 1.11| 4.20| 12.04| 5.46| 4.81| 2.18
AVR45-17| 60| 27| 1.26| 4.76| 13.65| 6.19| 5.46| 2.47
AVR45-19| 67| 30| 1.41| 5.32| 15.26| 6.92| 6.10| 2.77
AVR45-21| 74| 34| 1.55| 5.89| 16.87| 7.65| 6.74| 3.06
AVR45-23| 81| 37| 1.70| 6.45| 18.47| 8.38| 7.39| 3.35
AVR45-25| 88| 40| 1.85| 7.01| 20.08| 9.11| 8.03| 3.64
AVR45-27| 95| 43| 2.00| 7.57| 21.69| 9.84| 8.67| 3.93
AVR45-29| 102| 46| 2.15| 8.13| 23.30| 10.57| 9.31| 4.22
AVR45-31| 109| 49| 2.30| 8.69| 24.91| 11.30| 9.96| 4.52
AVR45-33| 116| 53| 2.44| 9.25| 26.51| 12.03| 10.60| 4.81
**Data is subject to change without notice. MSDS Sheets can be obtained at www.dekabatteries.com
APPENDIX C
VOLTAGE COMPENSATION CHART
°C | Float | Refresh / Equalize | °F |
---|---|---|---|
>35 | 2.230 | 2.380 | >95 |
34 | 2.232 | 2.382 | 93.2 |
33 | 2.234 | 2.384 | 91.4 |
32 | 2.236 | 2.386 | 89.6 |
31 | 2.238 | 2.388 | 87.8 |
30 | 2.240 | 2.390 | 86.0 |
29 | 2.242 | 2.392 | 84.2 |
28 | 2.244 | 2.394 | 82.4 |
27 | 2.246 | 2.396 | 80.6 |
26 | 2.248 | 2.398 | 78.8 |
25 | 2.250 | 2.400 | 77.0 |
24 | 2.252 | 2.402 | 75.2 |
23 | 2.254 | 2.404 | 73.4 |
22 | 2.256 | 2.406 | 71.6 |
21 | 2.258 | 2.408 | 69.8 |
20 | 2.260 | 2.410 | 68.0 |
19 | 2.262 | 2.412 | 66.2 |
18 | 2.264 | 2.414 | 64.4 |
17 | 2.266 | 2.416 | 62.6 |
16 | 2.268 | 2.418 | 60.8 |
15 | 2.270 | 2.420 | 59.0 |
14 | 2.272 | 2.422 | 57.2 |
13 | 2.274 | 2.424 | 55.4 |
12 | 2.276 | 2.426 | 53.6 |
11 | 2.278 | 2.428 | 51.8 |
<10 | 2.280 | 2.430 | <50 |
12mV per ˚C
CHARGE CURRENT LIMITS
__**Cell Type| Max. Charge Current (A)| Min. Charge
Current (A) ****
---|---|---
AVR45-5| 16.1| 4.8
AVR45-7| 24.1| 7.2
AVR45-9| 32.2| 9.6
AVR45-11| 40.2| 12.1
AVR45-13| 48.2| 14.5
AVR45-15| 56.3| 16.9
AVR45-17| 64.3| 19.3
AVR45-19| 72.4| 21.7
AVR45-21| 80.4| 24.1
AVR45-23| 88.4| 26.5
AVR45-25| 96.5| 28.9
AVR45-27| 105| 31.4
AVR45-29| 113| 33.8
AVR45-31| 121| 36.2
AVR45-33| 129| 38.6
** = Using minimum charge current will extend recharge time and increase the risk of the battery being undercharged
APPENDIX D
System Layout Drawings
Drawings are representations of a 12V (6-cell) system
| |
---|---|---
APPENDIX E
e-mail:
reservepowersales@dekabatteries.com
East Penn Manufacturing Co.
Lyon Station, PA 19536-0147
E.P.M. Form No.2400 02/22
© 2022 by EPM Printed in the U.S.A.
Phone:610-682-4231
Fax:610-682-4781
www.dekabatteries.com
All data is subject to change without notice. No part of this document may
be copied or reproduced,
electronically or mechanically, without written permission from the
company.