Presence detectors 360° KNX/KLR RA/EA for ceiling flush-mounting
The family of Swiss Garde 360 Presence KNX/KLR RA/EA presence detectors is
characterised by the following outstanding features:
-
2 -channel constant light control The in-built 2-channel constant light control can be easily adjusted to meet any customer’s needs. The two light channels can be controlled via a parametrizable offset. (-50%, synchronous, +50%) using different light values.
-
1 light output for switching, dimming or scenery selection.
-
Standby light
If the light channel is set to dimming absolute, an emergency standby light can be programmed using the standby value [%] and standby duration [min/h]. Two value pairs can be read out from the KNX bus. -
1 HVAC-channel controls heating, ventilation and air conditioning. This output can be used for presence detection. Additionally, alarm systems with parametrizable switch-on delay can be implemented.
-
1 Threshold switch in lux with hysteresis setting
-
1 brightness output in lux (2 Byte)
-
3 Pyro detectors
Three PIR sensors with an 360° detection area can be activated individually or in pairs.
Important notice
The presence detectors Swiss Garde 360 Presence
KNX/KLR RA/EA/EB is suitable for ceiling mounting indoors only. In case of
errors such as continuous light, uncontrolled switching, etc., please consult
page 7 „troubleshooting“.
Function
The presence detector Swiss Garde 360 Presence KNX/KLR RA/EA/EB reacts to heat radiation of moving bodies. A person approaching the monitored area automatically trig-gers the connected light. If no motion is detected again, the light will automatically switch off after a delay time configured in ETS. In case of activated standby, the light will stay on at reduced intensity during the set time period (mode dimming complete/ constant light control).
Installation
Connect the presence detector as follows: red wire (+) to be connected to red terminal black wire (-) to be connected to grey terminal
Application notes
A detailed description of the communication objects and all parametrizable functions can be found in the following separate document:
Frontal view
Rear view
PIR sensors num bering
The PIR sensors 1 2 3 can be activated via ETS individually or in groups,
using the above numbering scheme.
After KNX/EIB bus connection: the detector takes approx. 1 min. to reach as
table working condition!
Detection range
The 360° omnidirectional detection range as well as the dense detection area allow for an optimal function. The range depends on the mounting height as well as the angle of approach (high sensitivity when crossing a switching segment). Since the device registers the temperature differences between the source of heat and the ambient temperature, the detection range may vary depending on site conditions (floor heating, etc.).
Troubleshooting
Error /Cause/remedies
- load doesn`t switch ON
- twilight value set to high
- check light/luminaire/fuses
- Detector triggers ON and OFF without reason or light never turns
- check detection area for potential causes of false OFF: triggering: animals, heating, etc. may all doing faulty switching
- check distances to lamps (heat- reflection or direct light influence)
- detector is to sensitive, reduce the detection range sensitivity (1…10) via ETS.
- Turns the ON during day time:
- twilight adjustment set to high: set to a lower value via ETS (menu light)
Device dimensions
Technical data
- nominal voltage : 24V DC (21 – 30V DC)
- power consumption: 0,4 W
- PIR- sensors : 3 Pyro detectors
- sensitivity: adjustable via ETS in 10 steps light measuring: brightness sensor with linear output
- lux value: value readable (5 – 2000lux, 2 Byte)
- switiching criteria: motion and brightness
- detection range: 360°, ceiling mounted
- range height= 3m/ RA 16m: Ø6m presence, Ø14m motion
- range height= 3m/ RA 30m: Ø7m presence, Ø26m motion
- recom. mounting height: 2m – 6m (25032, 25034) 2m – 8m (25036)
- mounting: ceiling or false- ceiling mounting
- available accessory: AP/UP- housing, IP55 -housing
- protection rating: IP 20, indoor mounting, class II
- temperature range: -20°C bis +40 °C
- dimensions:
- RA 16 m : Ø105 x 44 mm
- RA 30 m : Ø105 x 51mm
- RA 16 m EB : Ø105 x 51 mm