CHATSWORTH PRODUCTS 350VA LS-Series Lithium Ion Standby UPS User Manual

June 3, 2024
CHATSWORTH PRODUCTS

CHATSWORTH PRODUCTS 350VA LS-Series Lithium Ion Standby UPS

CHATSWORTH PRODUCTS 350VA LS-Series Lithium Ion Standby UPS-
PRO

INTRODUCTION

User Manual for Lithium Ion UPS
This document is the User Manual for CPI 350VA – 600VA Lithium Ion Standby Uninterruptible Power Supplies (UPS) (Sales Models LS350A, LS350B, LS600A, LS600B). ©2022 Chatsworth Products, Inc. All rights reserved. UL Listed for use in U.S. and Canada.

Legal Information
The information contained in this guide is subject to change without notice. Chatsworth Products, Inc. (CPI) shall not be liable for technical or editorial errors or omissions contained herein; nor is it liable for any injury, loss, or incidental or consequential damages resulting from the furnishing, performance or use of this material and equipment.

PACKAGE CONTENTS
You should be receiving the following items inside the package:

  • UPS Unit
  • User Manual
  • Local Monitoring Software CD

PRODUCT INTRODUCTION

Thank you for selecting this Uninterruptible Power Supply (UPS). It provides you with protection for connected equipment. Please read this manual before installing the LS Series UPS as it provides important information that should be followed during installation and maintenance of the UPS and batteries, allowing you to correctly set up your system for maximum safety and performance. Included is information on customer support and service, if it is required. If you experience a problem with the UPS, please refer to the Troubleshooting section in this manual to correct the problem. If the problem is not corrected, please collect information so that the Technical Support personnel can more effectively assist you.

PRODUCT OVERVIEW

The advanced design of the UPS combines the benefits of lithium-powered UPS and advanced surge suppression technology. Slim form factor, wall mounting, and easy access receptacles make this UPS ideal for use with wall-mounted racks and cabinets or for mounting behind thin display screens used in hotels, restaurants, hospitals, campuses, airports and other commercial areas. While the compact design is appealing to the digital signage industry, it is also excellent for providing protection to kiosks, gaming machines, computers, point-of-sale equipment, and small printers.

CHATSWORTH PRODUCTS 350VA LS-Series Lithium Ion Standby
UPS-1

INSTALLATION & INITIAL STARTUP

Note: Before installation, inspect the unit and packaging to make sure that nothing inside has been damaged.

Connect UPS to Utility and Charging
Before the initial use of the UPS, plug the UPS input cord into a wall outlet and turn the UPS on by pressing the Power switch on the back of the UPS. For best results, the batteries in the UPS should be charged for at least 8 hours before use. The UPS charges its
battery while it is connected to AC utility power and powered on.
Connecting the Loads
Plug the loads to be supported by the UPS into the output receptacles on the front of the UPS. Simply turn the power switch on the UPS on and the devices connected to the UPS will be protected by the UPS unit.
Turn UPS ON/OFF
To turn the UPS unit on, press the power button on the UPS and hold for three seconds. To turn the UPS unit off, press the power button and hold for one second.
Connecting Local Monitoring Software (optional)
If it is desired to use the Local Monitoring Software, and if your UPS is equipped with USB communications, connect a USB cable from your computer to the UPS, and install the software from the CD.

INDICATORS & ALARM CONDITIONS

Condition Visual Indicator Alarm
AC mode LED illuminated No Audible Alarm
Battery mode LED flashes every 10 seconds Audible Alarm sounds every 10

seconds
Low battery mode| LED flashes every 1 second| Audible Alarm sounds every 1 second
Fault| LED is illuminated| Audible Alarm is continuous
Alarm for over-temperature protection| LED flashes every 0.5 seconds| No Audible Alarm

This manual contains important instructions for the LS350A, LS350B, LS600A and LS600B that should be followed during the installation and maintenance of the UPS

CAUTION! (UPS having Internal Batteries): Risk of electrical shock – Hazardous live parts inside this unit are energized from the battery supply even when the input AC power is disconnected.
CAUTION! (No User serviceable Parts): Risk of electrical shock, do not remove cover. No user-serviceable parts inside. Refer servicing to qualified service personnel.
CAUTION! (Non-isolated Battery supply): Risk of electric shock, battery circuit is not isolated from AC input, hazardous voltage may exist between battery terminals and ground. Test before touching.
WARNING! Unit intended for installation in a controlled environment.
CAUTION! Do not dispose of batteries in a fire, the battery may explode.
CAUTION! Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes.
CAUTION: A battery can present a risk of electrical shock and high short- circuit current. Contact with any part of a grounded battery can result in electrical shock. The following precautions should be observed

  • When working on batteries:
  • Remove watches, rings, or other metal objects.
  • Use tools with insulated handles.
  • Wear rubber gloves and boots.
  • Do not lay tools or metal parts on top of batteries.
  • Disconnect charging source and load prior to installing or maintaining the battery.
  • Remove battery grounds during installation and maintenance to reduce the likelihood of shock.
  • Remove the connection from the ground if any part of the battery is determined to be grounded.

WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.

FCC

NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
WARNING: Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

To reduce the risk of electric shock, disconnect the UPS from the main supply before installing a computer inter-face signal cable. Reconnect the power cord only after signaling interconnections have been made.
Servicing of batteries should be performed or supervised by personnel with knowledge of batteries and the required precautions. Keep unauthorized personnel away from batteries.
The instructions contained within this safety manual are deemed important and should be closely followed at all times during installation and follow-up maintenance of the UPS and batteries.

TROUBLESHOOTING

Condition Visual Indicator Alarm
No LED display on the front UPS panel Low battery Charge the UPS at least 8

hours
Battery fault| Replace the battery with the same type of battery
The UPS is not turned on| Press the Power Switch on the front of the UPS
Alarm continuously sounds when the AC input is normal| The UPS is overloaded| Remove some of the load from the output of the UPS
UPS fault| Call CPI Technical Support
Alarm continuously sounds when the AC input is normal| Battery defect| Replace the battery with the same type of battery
Charging circuit is damaged| Remove some of the load from the output of the UPS
When power fails, backup time is shorter than expected| The UPS is overload| Remove some of the load from the output of the UPS
Battery Defect| Replace the battery with the same type of battery
Battery voltage is too low| Charge the UPS at least 8 hours Battery defect Replace the battery with the same type of battery
The AC input is normal but

the blue LED is flashing

| Power cord is loose| Reconnect the input power cord properly

SPECIFICATIONS

Model Number LS350A LS350B LS600A LS600B
CAPACITY Power rating 350VA (200W) 350VA (200W 600VA (360W)
INPUT Voltage 120VAC 200 – 240VAC 120VAC
Frequency 50/60Hz
OUTPUT Voltage 120VAC 200 – 240VAC 120VAC
Waveform Sine wave (normal), simulated sine wave (battery mode)
Frequency 50/60Hz
Surge suppression 312 joules
Transfer time 2-6 ms (typical)
BATTERY Battery type Lithium Iron Phosphate (LiFePo4)
Battery quantity and size (8) LiFePO4 18650 cells, 2400mAh (16) LiFePO4

18650 cells, 4400mAh
PHYSICAL| Dimensions (W x D x H)| 6.9 x 8.5 x 1.25 in*

(175 x 216 x 32 mm)

| 7.3 x 10.8 x 1.6 in

(185 x 275 x 40 mm)

Weight| 3.4 lbs (1.5 kg)| 4.9 lbs (2.2 kg)
Line cord| Detachable 5–15P to C13| C14 inlet| Detachable 5–15P to C13| C14 inlet
Receptacles| (3) 5–15R| (2) IEC C13| (3) 5–15R| (2) IEC C13
ENVIRONMENT| Temperature| 32–104°F (0–40°C)
Humidity| 0–90%
Altitude| 11,500 ft above sea level
COMMUNICATIONS INTERFACE| Standard communications| USB Interface including cable and software| RS-232 Interface including cable and software
Web/SNMP card option| N/A| N/A
Environmental monitoring device| N/A| N/A
APPROVALS| UL-1778, cTUVus, FCC,

RoHS and TAA compliance

| CE, RoHS and TAA compliance| UL-1778, cTUVus, FCC,

RoHS and TAA compliance

| CE, RoHS and TAA compliance
WARRANTY| 6 years electronics, 6 years battery warranty (USA & Canada)**
INCLUDED IN BOX| Software CD, user manual, 5–15P to C13 line cord (120VAC units only)

OBTAINING SERVICE

If the UPS requires Service:

  1. Use the TROUBLESHOOTING section in this manual to eliminate obvious causes.
  2. Verify there are no circuit breakers tripped.
  3. Call CPI Technical Support at 800-834-4969. Technical support inquiries can also be made at techsupport@chatsworth.com. Please have the following information available BEFORE calling the Technical Support Department:
    • Ship to address
    • The serial number of the unit.
    • Where and when the unit was purchased.
    • All of the model information about your UPS.
    • Any information on the failure, including LED’s that may or may not be illuminated.
    • A description of the protected equipment, including model numbers if possible.
  4. Technical Support will ask you for the above information and, if possible, help solve your problem over the phone. In the event that the unit requires factory service, the technician will issue you a Return Material Authorization number (RMA).

RETURNS AND REPAIRS
No products or part thereof shall be returned to CPI unless the customer first obtains a Return Material Authorization (RMA) Number from a CPI customer service representative. This number must appear clearly and prominently on all shipping containers. Containers without the labels will not be accepted.
If you are returning the UPS to CPI for service, please follow these procedures:

  1. Pack the UPS in its original packaging. If the original packaging is no longer available, ask the Technical Support Technician about obtaining a replacement set of packaging material. It is important to pack the UPS properly in order to avoid damage in transit.
  2. Never use Styrofoam beads for a packing material.
  3. Mark the RMA number on the outside of all packages. CPI cannot accept any package without the RMA number noted on the outside of the boxes.
  4. Return the UPS by an insured, prepaid carrier to the address provided by the Technician.
  5. Refer to the Warranty statements in this manual for additional details on items covered.

Standard Limited Warranty

Chatsworth Products, Inc. (CPI) warrants all CPI-branded hardware products (LS-Series Uninterruptible Power Supplies) to be free from defects in material and/or workmanship (CPI’s Standard Limited Warranty) for a period of six (6) years (USA & Canada) and three (3) years (outside USA & Canada) following the date of purchase (the Original Warranty Period). The customer must contact CPI in writing or by oral communication confirmed in writing within the Original Warranty Period to report a product that the customer claims is defective. CPI reserves the sole and absolute right to determine whether or not the product or any part thereof is defective. In the event a product (or any part thereof) is determined by CPI to be defective (an Accepted Claim), CPI will provide a re-manufactured or replacement product or part (the Replacement Product) at no cost to the customer and issue a Return Material Authorization (RMA) number.
In the case of an Accepted Claim, the customer shall be responsible for shipping back the defective product to CPI under the provided RMA number within 30 days. Any exceptions to this return policy must be authorized by CPI in writing in advance. Freight charges for the return shipment of the defective product for an Accepted Claim shall be borne by the customer, unless the defect is reported by the customer to CPI in writing within the first 30 days following the customer’s receipt of the original product. Any Replacement Product that has been provided under an Accepted Claim will be subject to CPI’s Standard Limited Warranty for the remaining Warranty Period applicable to the original product or 90 days following the date of replacement, whichever occurs later.
CPI’s Standard Limited Warranty and Extended Limited Warranty do not extend to CPI-branded hardware products that have been subjected to abuse, misuse, neglect, accident, improper use, or improper installation, operation, repair and maintenance (except to the extent provided by CPI authorized personnel), nor to products that have been altered or modified in any way by anyone other than CPI authorized personnel, in which case CPI’s Standard Limited Warranty or Extended Limited Warranty shall be null and void. In no event will CPI be liable for consequential damages, for loss, damage or expense directly or indirectly arising from the use of any of its branded products, for any inability to use materials or from any other cause.

THESE LIMITED WARRANTY PROVISIONS ARE THE EXCLUSIVE WARRANTIES FOR ANY CPI- BRANDED HARDWARE PRODUCTS AND SET FORTH THE EXCLUSIVE REMEDIES AND PROCEDURES FOR CLAIMS UNDER CPI’S STANDARD LIMITED WARRANTY AND EXTENDED LIMITED WARRANTY.
CPI’S STANDARD LIMITED WARRANTY AND EXTENDED LIMITED WARRANTY APPLY TO CPI- BRANDED HARDWARE PRODUCTS ONLY.
DISCLAIMER OF WARRANTY: EXCEPT AS EXPRESSLY SET FORTH HEREIN, CPI MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY WARRANTIES OF FITNESS FOR A PARTICULAR USE OR PURPOSE, MERCHANTABILITY, OR NON-INFRINGEMENT OF ANY INTELLECTUAL PROPERTY RIGHTS.

While every effort has been made to ensure the accuracy of all information, CPI does not accept liability for any errors or omissions and reserves the right to change information and descriptions of listed services and products.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>