Honeywell HBT-BMS-TC300 Thermostat Connected Device Commercial Instruction Manual

June 1, 2024
Honeywell

Honeywell HBT-BMS-TC300 Thermostat Connected Device Commercial

Honeywell-HBT-BMS-TC300-Thermostat-Connected-Device-Commercial-
PRODUCT

Product Usage Instructions

Terminal Identification

  • Refer to the terminal identification chart for connecting various components to the thermostat.

Supported Sensors and Functions

  • The thermostat supports various sensors like Occupancy Sensor, Air Flow Sensor, Temperature Sensors, Pipe Sensor, Changeover Switch, and Drain Pan Detector.

FAQ

  • Q: What is the maximum load the thermostat can handle?
  • A: The thermostat can handle a maximum load of 96VA when all relay outputs are ON.
  • Q: What communication protocols does the thermostat support?
  • A: The thermostat supports SylkTM, BACnet MS/TP over RS485, and Modbus RTU communication technologies.

TC300 Thermostat is an advanced, highly configurable device providing building automation connectivity well-suited for indoor commercial building applications. The product has flexible I/O that will satisfy the needs of most 2-pipe or 4-pipe fan coil applications. Supported functions include dehumidification w/reheat using an embedded humidity sensor, auxiliary heat functions, and more rapid transitional 2-pipe system seasonal changeover.
This device supports BACnet MS/TP and Modbus communications via RS485 bus as is needed for typical HVAC building control systems. This same bus is used to facilitate future firmware updates and enhanced functionality as they are released to the market.
The integral intelligent control algorithms plus scheduling help to achieve the perfect balance between Energy Efficiency and Comfort. The thermostat utilizes an attractive, color, capacitive-touch screen interface providing an intuitive configuration process with minimal installer training. This functionality is enhanced through the usage of embedded help screens reducing reliance on technical manuals for complex installation.

FEATURES AND BENEFITS

  • Colour, capacitive-touch screen display for intuitive, fast commissioning and exceptional user experience.
  • Multiple, configurable user types with customizable privileges to prevent unauthorized usage.
  • Embedded system monitoring screen for equipment and I/O status.
  • Customizable daily schedule for Occupancy set points, up to “X” Holidays including floating, and up to 3 special events.
  • Advanced commercial control algorithms such as auto changeover.
  • Customizable inactive display modes, Auto dim display, always on, or dark mode.
  • An LED ring indicator to show the operational status.
  • Real-time clock timekeeping accuracy with 72-hour retention during power loss.
  • A thermostat can be configured via HMI or BACnet.

EQUIPMENT CONTROL FEATURES

  • Fan coil, On/Off Valve, Floating Valve, Modulating Valve, and 6-Way Modulating Valve.
  • Discharge Air Control
  • 1-3 or variable speed fan
  • Dehumidification with and without reheat.
  • Enhanced 2-pipe fan coil functionality during seasonal or system changeover providing heating or cooling functionality before CW/HW has reached optimal operating temperature.
  • Service mode for manually enabling outputs for faster diagnostics and equipment testing.
  • Auxiliary heating options supporting peripheral or supplemental types
  • Auto mode to switch between heating and cooling according to the current space temperature
  • Staging control, PID Tuning, DAT Lockout, Modulating control
  • System Switch and Ventilation options.
  • Integration with a variety of external wired sensor types including Discharge air, Drain pan, occupancy, Proof or airflow, Space temp, CO2, and Humidity.
  • Complies with ASHRAE guideline 36- 2021, Section 5.22 sequence of operations for high-performance operation when using floating/modulating valves and multi-speed/variable speed fan.

TECHNICAL SPECIFICATION

POWER CHARACTERISTICS

Power Supply| Rated voltage: 24VAC 50/60Hz,

Working voltage range: 20- 30VAC, UL listed class-2 transformer or IEC 61558 listed transformer.

Power Consumption (Display ON)| Max. 8.5VA @ 24VAC (355mA @ 24VAC)
Min. Load| 4VA (all DOs OFF, No Sylk sensor)
Max. Load| 96VA (all DOs ON)
DISPLAY

Display Type| 16 BPP TFT display with CTP
Resolutions| 320*240 pixel
Active Display Area| 2.4” diagonally
Backlight| LCD (Dimmable)
LED Color Ring| Blue (cooling) Orange (heating)
IO CHARACTERISTICS

UIO x 3| •      Resistive Temperature Sensor Input

—        NTC10K Type II, C7021 series

—        NTC10K Type III (Space Temperature Sensor only), C7023 series

—        NTC20K, TR21, and C7041 series

•      Voltage Input, SELV

—        0-10V, ±5% of full scale

•      Digital Input

—        Dry contact closure

—        Open circuit (≥ 100Kohms)

—        Closed circuit (≤100ohms)

•      Voltage Output

—        0-10V, ±3% of full scale @2K ohms

AI (DIO1 DIO2) x 2| •      Resistive Temperature Sensor Input

—        NTC10K Type II, C7021 series

—        NTC10K Type III (Space Temperature Sensor only), C7023 series

—        NTC20K, TR21, and C7041 series

•      Digital Input

—        Dry contact closure

—        Open circuit (≥ 100Kohms)

—        Closed circuit (≤100ohms)

DO1-3, DIO1-2| •      Relay Output

•      Rated Average Current

—        1A Resistive at 24VAC

•      Rated Pulse Current

—        3.5A Resistive at 24VAC

OPERATING ENVIRONMENT

Ambient Operating Temperature| 32 to 122 °F (0 to 50°C)
Ambient Operating Humidity| 10 to 90% relative humidity (non-condensing)
Storage Temperature| -40 to 150 °F(-40 to 65.5°C)
Protection Class| IP20
ONBOARD SENSOR

Temperature| Heat: 40 to 100°F (4.5 to 37.7°C)

Cool: 50 to 99°F (10 to 37°C) Resolution: 1 °F (0.5°C)

Control Accuracy: ±1.5°F (0.8°C) at Room Temperature

Humidity| Range: 20~90% RH Resolution: 1%RH

Control Accuracy: ±5%RH at Room Temperature and 20~90%RH

COMPLIANCES

Certificates| •      CE

•      FCC

•      ICES

•      UL/cUL

•      RoHs

•      REACH

•      Prop65

•      UK

Standards| •      EN 60730-1

•      EN 60730-2-9

 | •      BS EN 60730-1
 | •      BS EN 60730-2-9
 | •      UL60730-1
 | •      UL60730-2-9
 | •      Title 47 part 15 subpart B
 | •      ICES-003
COMMUNICATION TECHNOLOGIES

SylkTM| Honeywell SylkTM
BACnet MS/TP| Over RS485

(9.6, 19.2, 38.4, 76.8, 115.2 Kbps)

Modbus RTU| 0.3 to 115.2 Kbps
ELECTRICAL CHARATERISTICS

Rated Impulse Voltage| 500 V
Construction of Control| Independently Mounted Control
ELECTRICAL CHARATERISTICS

Operation Method| Type 1. B Action
Pollution Degree| 2
Purpose of Control| Operating Control
SUPPORTED SENSORS AND FUNCTIONS

SENSORS| OPTIONS| PART NUMBERS
Occupancy Sensor| Direct (Normally Open) Reverse (Normally Closed)| Dry contact occupancy sensor
Proof Of Air Flow Sensor| Direct (Normally Open) Reverse (Normally Closed)| DPS200 DPS400 DPS1000 MCS, CS, CSP

current switches (Dry contact switches)

Discharge Air Temperature Sensor| NTC 20K

NTC 10K Type II NTC 10K Type III

Sylk

| C7250A C7041 C7021 C7023 C7400S
Space Temperature Sensors| NTC 20K

NTC 10K Type II NTC 10K Type III

Sylk

| TR21

C7041, C7772A, C7021, C7772F, C7023, C7772G, TR40,

TR40-H, TR40-CO2, TR40-H-CO2, TR120 (max 1)

Pipe Sensor| NTC 20K

NTC 10K Type II NTC 10K Type III

| C7250A C7041 C7021 C7023
Changeover Switch| Closed with heat Closed with cool| Digital input
Drain Pan / Leak Detector| Direct (Normally Open) Reverse (Normally Closed| Dry contact float switch or water sensor

TERMINAL IDENTIFICATION

Honeywell-HBT-BMS-TC300-Thermostat-Connected-Device-Commercial-
FIG-1

TERMINAL IDENTIFICATION

TERMINAL NAME| TERMINAL LABEL| DESCRIPTION
UIO1| UIO1| Universal input/output
COM| COM| Common
UIO2| UIO2| Universal input/output
COM| COM| Common
UIO3| UIO3| Universal input/output
RS485 SLAVE| –| BACnet/Modbus Communications
RS485 SLAVE| +| BACnet/Modbus Communications
SYLK MASTER| | Sylk bus
SYLK MASTER|
| Sylk bus
DO1| DO1| Configurable relay output
DO2| DO2| Configurable relay output
TERMINAL IDENTIFICATION

TERMINAL NAME| TERMINAL LABEL| DESCRIPTION
DO3| DO3| Configurable relay output
DIO1| DIO1| Configurable relay output, configurable analog/relay input
DIO2| DIO2| Configurable relay output, configurable analog/relay input
24VAC POWER| R| 24VAC power from Class2 transformer
24VAC POWER| C| 24VAC common (Neutral) from Class2 transformer
COM| COM| Common

NOTE: Other terminals except R and C can be wired by 14-26AWG, Cu (type).

TERMINAL WIRE GUAGE NORMAL LOAD WIRE TYPE
R, C 14-18AWG 0-4A, 0-96VA Cu
20-22AWG 0-3A, 0-72VA
24-26AWG 0-2A, 0-48VA
PART NUMBER COM PROTOCOL POWER
--- --- ---
TC300B-G RS485 BACnet MS/TP

and Modbus

| 24VAC

NOTE: These accessories are available in a separate order.

ACCESSORIES

TRTC-DECOPLATE-1| TC300 decorative wall plate

TYPE

|

TERMINAL

|

LABEL

|

DEFAULT

| TERMINAL ASSIGNMENTS

INPUTS OUTPUTS

---|---|---|---|---
Digital Output| DO1| DO1| On/Off Heat| NA| Heating On/Off, Heating Floating Open, Cooling Floating Open, Valve On/Off, Valve Floating Open, Changeover Valve, Fan Command, High-Speed Fan, Medium Speed Fan, Low-Speed Fan, Auxiliary Heat, Heat Stage1, Valve Stage1
DO2| DO2| On/Off Cool| NA| Heating Floating Close, Cooling Floating Close, Cooling On/Off, Valve Floating Close, Changeover Valve, Fan Command, High- Speed Fan, Medium Speed Fan, Low-Speed Fan, Auxiliary Heat, Cool Stage1
D03| DO3| NA| NA| Cooling Floating Open, Changeover Valve, Fan Command, High- Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Heat Stage1, Cool Stage1
DIO1| DIO1| NA| Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Airflow, Pipe Sensor, Space Temp Sensor, Changeover Switch| Cooling Floating Close, Changeover Valve, Fan Command, High-Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat
DIO2| DIO2| NA| Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Airflow, Pipe Sensor, Space Temp Sensor, Changeover Switch| Changeover Valve, Fan Command, High-Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat

TYPE

|

TERMINAL

|

LABEL

|

DEFAULT

| TERMINAL ASSIGNMENTS

INPUTS OUTPUTS

---|---|---|---|---
Universal Input/ Output| UIO1| UIO1| NA| Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Airflow, Pipe Sensor, Space Temp Sensor, Changeover Switch| 6-Way Valve, Modulating Cool, Modulating Heat,Modulating Valve, UIO2 UIO2 NA Variable Speed Fan
UIO2| UIO2| NA
UIO3| UIO3| NA

DIMENSIONS

DIMENSIONS THERMOSTAT

Honeywell-HBT-BMS-TC300-Thermostat-Connected-Device-Commercial-
FIG-3

TRTC-DECOPLATE-1

Honeywell-HBT-BMS-TC300-Thermostat-Connected-Device-Commercial-
FIG-4

GENERAL SAFETY INFORMATION

  • When performing any work (installation, mounting, startup), all manufacturer instructions and in particular the Mounting and Installation Instructions guide (31- 00642) and the user guide (31-00644) are to be observed.
  • TC300 Thermostat may be installed and mounted only by authorized and trained personnel.
  • Rules regarding electrostatic discharge should be followed.
  • If TC300 Thermostat is modified in any way, except by the manufacturer, all warranties concerning operation and safety are invalidated.
  • Make sure that the local standards and regulations are observed at all times.
  • Use only accessory equipment which comes from or has been approved by Honeywell.
  • It is recommended that out-of-the-box devices be kept at room temperature for at least 24 hours before applying power. This is to allow any condensation resulting from low shipping/storage temperatures to evaporate.
  • Investigated according to United States Standard UL- 60730-1, and UL60730-2-9.
  • Investigated according to Canadian National Standard(s) C22.2, No. 205-M1983 (CNL-listed).
  • Do not open TC300 Thermostat, as it contains no userserviceable parts inside!
  • CE declarations according to EMC Directive 2014/30/EU.
  • UK declarations according to Electromagnetic Compatibility Regulations 2016.
  • Product standards are EN 60730-1 and EN 60730-2-9.
  • TC300 Thermostat is Class B digital apparatus and complies with Canadian ICES-003.

FCC STATEMENT

This device complies with part 15 of the FCC Rules.

Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation.

Caution: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Limited by local law regulations, version for North America does not have region selection option.

SAFETY INFORMATION AS PER EN60730-1

  • TC300 Thermostat is intended for residential and commercial environments.
  • TC300 Thermostat is an independently mounted electronic control system with fixed wiring.
  • TC300 Thermostat is used for the purpose of building HVAC control and is suitable for use only in non-safety controls for installation on or in appliances.

Note
All images used in this document are for illustrative purposes only and may not match the actual product.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.

CONTACT

Honeywell Building Technologies

U.S. Registered Trademark © 2023 Honeywell International Inc. 31-00645-01 | Rev. 10-23