Safety Instructions

General

These installation and operating instructions are a part of the product, and contain basic information that must be observed during installation, operation and maintenance. For this reason, the installer and specialist personnel or operators must read these instructions prior to set-up.
Please observe both the general safety instructions listed under section 2 and the special safety instructions detailed in the other sections.
A copy of the EC Declaration of Conformity is provided with these instructions. This declaration shall be deemed void in the event of a modification that has not been agreed with us.

Identification of notes in the operating instructions

General hazard symbol
Warning! Danger of personal injury! Observe the relevant accident prevention regulations.

Warning! Danger from electrical voltage! Prevent hazards arising from electrical energy. Observe the instructions in local or general regulations (e.g. IEC, VDE, etc.), and those of the local energy supplier.

Note

This symbol indicates useful information for handling the product. It indicates potential difficulties and aims to ensure safe operation.

Signs attached directly on the product, such as:

  • direction of rotation arrow
  • type plate
  • identification of connections must be strictly observed and kept in an easily legible state.

Personnel qualification

The personnel used for mounting, operation and maintenance must have relevant qualifications. Areas of responsibility and monitoring of personnel must be guaranteed by the owner/operator. If personnel do not have the necessary know- how, they must be trained or instructed accordingly. This device can be used by children at or above the age of 8 years, as well as by persons with reduced physical, sensory or mental capabilities, or who lack experience and knowledge, if they are supervised or have been instructed concerning the safe use of the device and if they understand the hazards arising from its use. Children may not play with the device. Cleaning and maintenance operations may not be carried out by children without supervision.

Danger of not observing safety instructions

Not observing the safety information can endanger persons, the environment and the system. Not observing the safety instructions shall result in the loss of any and all claims to warranty.
Potential dangers include:

  • Hazards to persons through electrical and mechanical effects.
  • Failure of important system functions.
  • Hazard to the environment from escaping fluids resulting from a leak.
  • Failure of prescribed repair and maintenance work.

Safety-conscious working
Observe the safety instructions detailed in this manual, along with the current national accident prevention regulations. Should the system operator also have their own internal regulations, these must also be observed.

Safety instructions for the operator

  • Any existing touch guard protecting moving parts may be neither removed nor shut down while the system is in operation.

  • In the event of a fluid leak, any fluids must be collected or diverted in a way that prevents hazards to persons and the environment from arising.

  • Prevent hazards arising from electrical energy.


  • Observe the instructions in local or general regulations (e.g. IEC, VDE, etc.), and those of the local energy supplier.

  • In the event of hazards arising from the system due to contact with hot or cold parts, these parts must be fitted with a touch guard.

  • Keep flammable substances away from the product.

Safety instructions for installation and maintenance work

The system operator is responsible for ensuring that all installation and maintenance work is carried out by qualified personnel. These persons must also have familiarised themselves in advance with the product using the operating instructions. Conducting work on the pump is only permitted when the system is shut down.
Ensure that the device is securely disconnected from the power supply. Disconnect the device plug to achieve this. Prescribed instructions for shutting down the device can be found in the operating instructions. All protective mechanisms, such as a touch guard, must be correctly reattached after work.

Unauthorised conversion and production of spare parts

Modification or conversion of the product is only permitted after prior consultation with the manufacturer. Only use original spare parts for repairs. Only use accessories that havebeen approved by the manufacturer. The manufacturer shall bear no liability for any consequences resulting from the use of other parts.

Unpermitted operation

If the pump is disconnected from the power supply, wait at least 1 minute before reactivating. Otherwise, the pump’s inrush current limit has no effect, which can lead to functional errors or damage to any connected heating controller. The pump’s operational safety can only be ensured if it is used as intended. Please observe section 4 of these operating instructions here. Ensure compliance with the limit values detailed in the technical data.

Transport and Storage

After receiving the product, inspect it immediately for damage caused in transport. Should you detect any transport damage, assert a claim with the haulier. Incorrect transport and storage can lead to personal injury or damage to the product.

  • Protect the product against frost, moisture and damage during transport and storage.
  • Only carry the pump by the pump housing, and never by the connection cable or terminal box.
  • If the packaging weakens due to moisture, this can lead to the pump falling out and causing severe injury

Intended Use

The WITA Delta Midi high-efficiency pumps are designed for circulating hot water in central heating systems, and are also suitable for conveying thin liquid media in industry and commerce. They can also be used in photovoltaic systems.

Information About the Product

Technical data WITA go.future 2 – 40 LED | 60 LED
Dimension Instruction
Dimension Instruction

Max. pump lift 4.0 m 6.0 m
Max. flow rate 2.800 l/h 3.600 l/h
Power consumption P1 (W) 3 – 23 3 – 41
Supply voltage 1 x 230V 50Hz
Emission sound pressure level < 40 dB(A)
EEI ≤ 0.18 ≤ 0.20
Protection rating IP 42
Heat class TF 110
Ambient temperature 0 °C to 40 °C
Media temperaturer +5 to 110 °C
Max. system pressure 10 bar (1 MPa)
Permitted pumping media Heating water as per VDI 2035
Water/glycol mixture 1 :1

Inlet pressure

fluid temperature Minimum inlet pressure
< 75 °C 0.05 bar 0.005 MPa 0,5 m
75 °C – 90 °C 0.3 bar 0.03 MPa 3,0 m
90 °C – 110 °C 1.1 bar 0.11 MPa 11,0 m

Permissible range of application

Temperature range at maximum temperature ambient| Permissible fluid temperature
---|---
25 °C| 5 °C bis 110 °C
40 °C| 5 °C bis 95 °C

Caution!
Unpermitted pumping media can destroy the pump and cause personal injury. Respect the manufacturer’s information and safety data sheets!

Scope of delivery

  • Original installation and operating instructions
  • Pump
  • 2 flat gaskets
  • Pump plug
  • Insulation

Description of the Pump

In an average household, around 10 to 20% of the energy consumption is caused by common standard pumps. With the Delta Midi series of pumps, we have developed a circulation pump with an energy efficiency index of  0.20. The Delta Midi pump can reduce energy consumption by up to 80% compared to a standard circulation pump, whilst maintaining the same level of hydraulic power. The pump output can be adjusted to the actual needs of the system, as it works according to the proportional pressure process.

Pump settings and output

Description of operating elements

The buttons

All functions of the pump can be controlled with only two buttons. With the lower “Set” button the night setback can be switched on and off and if the pump is in setting mode also the operating level can be changed.

The top button triggers different functions depending on the length of the button press.

  • short press (<1 sec.): Switch the pump to setting mode
  • long press (1 – 3 sec.): Special function automatic air vent on or off
  • long press (3 – 5 sec.): Switch on special function external control (PWM / 0-10V)
  • long press (> 6 sec.): Special function key lock on and off

The display
Display Icon

  • Operating modes

  • Current power consumption

  • Characteristic levels

If the pump is connected to the mains voltage, the firmware version and the type are displayed at intervals of approx. 1 second.
(for example: 01, 04 this means: firmware 01, 4m pump or for example: 01, 06 this means: firmware 01, 6m pump)
Thereafter, the pump switches to the normal operation. Delivered condition is constant speed level 4.

If no change is made to the pump for more than 3 seconds, the display brightness will decrease. As soon as a key is pressed, it automatically increases.

Selection of operating mode and operating level

  1. Constant speed control
    In this operating mode, the pump turns at a constant speed over the entire characteristic curve.

  2. Constant pressure control
    In this type of control, the pressure generated by the pump is kept constant. This control type is particularly suitable for operation in underfloor heating systems.

  3. Proportional pressure control
    The pump is controlled according to the proportional pressure method. Here, the pressure generated by the pump is adapted to the changing flow rate. This operating mode is particularly suitable if the pump is intended for use as a heating circulating pump.

On delivery, the pump is set to the highest constant speed level. After a reset (page 42), the pump also starts at this stage.
By briefly pressing the upper button (<1 sec.), The electronics are signaled that the setting is to be changed. The LEDs flash to indicate the operating mode and operating level. By repeated short pressing of the upper button, the operating modes Constant speed, Constant pressure and Proportional pressure can be continuously switched through. The selected operating mode is indicated by the respective LED next to the characteristic symbols.

LED 4 special function night reduction)
LED 3 proportional pressure levels
LED 2 Constant pressure levels
LED 1 constant speed levels


By briefly pressing the lower “Set” button, the operating levels are continuously switched
through. In the respective operating mode, there is a choice between four different operating levels (characteristic curves). The set level is indicated by the position of the green LED. The further up it lights, the higher the set level.

LED 8 highest level
LED 7
LED 6
LED 5 lowest level

After about 3 seconds without pressing a button, the LEDs light up permanently and the setting is accepted.

The following table shows which LED is lit at which level:

|
---|---
x| | | | x| | | | Constant level I
x| | | | | x| | | Constant level II
x| | | | | | x| | Constant level III
x| | | | | | | x| Constant level IV
| x| | | x| | | | Constant pressure level 1
| x| | | | x| | | Constant pressure level 2
| x| | | | | x| | Constant pressure level 3
| x| | | | | | x| Constant pressure level 4
| | x| | x| | | | Proportional level A
| | x| | | x| | | Proportional level B
| | x| | | | x| | Proportional level C
| | x| | | | | x| Proportional level D
| | | x| | | | | Night reduction level N

Dimension Instruction

Automatic night reduction

Requirements for automatic night reduction: Pumps installed in gas water heaters that have only a small water content should never be set to automatic night reduction.
If the heating system does not supply enough heat to the radiators, check whether the automatic night reduction mode is activated. If necessary, deactivate the automatic night reduction.
In order to ensure the correct function of the night reduction, the following conditions must be met:

  1. The pump must be installed in the flow.
  2. The heating system must be equipped with an automatic flow temperature control

How the automatic night economy function works
To activate the night reduction, press the lower “Set” button. If the top left LED is lit with the sun / moon symbol, the night reduction mode is activated and the pump automatically switches between normal operation and night reduction mode. The changeover depends on the flow temperature.
The pump will automatically switch to night reduction if the flow temperature drops by more than 15 ° -20 ° C within 1 hour. Switching to normal operation takes place without delay as soon as the flow temperature has risen again by 3 ° C. To deactivate the night reduction, press the lower “Set” button again.

Permanent night reduction

The night reduction can also be switched on permanently. After activating the automatic night reduction, the lower “Set” button must be pressed again for 3 seconds. After releasing the key, the upper left LED flashes with the sun / moon symbol. The pump is now running at the lowest possible power. (Minimum operation) The pump remains permanently in lowered operation until

  • to the next print of the lower “Set” button
  • to increase the flow temperature then the automatic night reduction is activated, as well after a power failure

Venting programme

To start the ventilation program, the upper button must be kept pressed until the outer LEDs in the left-hand field of the power display begin to glow in the circle as running light. (about 1-3 seconds).
In order to start the deaeration program, the lower “Set” button must now be pressed within 5 seconds to confirm. In the right display of the power display is now counted down from 9 to 1 and the program goes through 9 stages with different speeds and different durations. When these 9 stages are finished, the pump returns to the level set before starting the deuteration program. The sequence can be ended prematurely by pressing the upper button again for about 3 seconds. The pump then returns to the step back that was set before starting the venting program.

8 Optional special function PWM / 0-10V input

This function allows the speed control of the pump by an external control. In order to use this function, the pump must be equipped with a corresponding input. (Either PWM or 0-10V)
This external input can be recognized by an additionally existing two-pole connection cable, to which a corresponding external control can be connected.
The cable length may not exceed 3m!
A polarity of the PWM signal does not have to be considered. The polarity of the 0-10V line must be BLUE = GND / ground and BROWN = 0-10V signal. The PWM / 0-10V connection cable must be designed for operation at a rated operating voltage of 230V AC. The remote station to be connected:

  • must prevent the direct contact of the cable wires when installed safely. This means that the terminals must be protected against contact and the terminal connections must be protected against accidental contact with a permanently mounted cover.
  • must comply with protection class I (connection with protective conductor). The device may only be put into operation if the PWM / 0-10 V signal has been connected correctly.

The PWM signal is a digital signal in which the speed information is included in the pulse width. The control signal must meet the following requirements:

Dimension Instruction

PWM% = 100 t / T
PWM% = 100
0.4 / 1 = 40%
For T, frequencies between 100 Hz and 1 kHz are permissible

The 0-10 V signal is an analog control signal in which the speed information is included in the voltage level. The control signal must meet the following requirements: The permissible input voltage range is 0 V to +10 V. The input impedance of the measuring circuit is 13.3 kOhm.

Heating characteristic curve P1 (PWM version) or A1 (O-10V version)

To set the heating characteristic curve of the upper button must be pressed until P0 or A0 is displayed. (P0 = PWM control off / A0 = Analog control off) By pressing the lower “Set” button, this value can be changed to P1 or A1.
After 5 seconds without pressing a button, the function is activated and the display alternately shows the current consumption and P1 or A1. If an external control is no longer required, set P0 or A0.
Dimension Instruction

In the delivery state, this is P0 or A0. (If changes have already been made in the settings, the number 1 or 2 can also be listed here)

A < 10% PWM / < 1V (MAX Characteristic)
B 20% PWM / 2V
C 40% PWM / 4V
D 60% PWM / 6V
E 80% PWM / 8V
F 90% PWM / 9V (MIN Characteristic)
100% PWM / 10V Pump is switched off

A < 10% PWM / < 1V (MAX Characteristic)
B 20% PWM / 2V
C 40% PWM / 4V
D 60% PWM / 6V
E 80% PWM / 8V
F 90% PWM / 9V (MIN Characteristic)
100% PWM / 10V Pump is switched off

Solar characteristic P2 (PWM version) or A2 (O-10V version)

To set the solar characteristic, press the upper key until P0 or A0 is displayed. (P0 = PWM control off / A0 = Analog control off) By repeatedly pressing the lower “Set” key, this value can be changed to P2 or A2.
After 5 seconds without pressing a key, the function is activated and the display alternately shows the current consumption and P2 or A2. If an external control is no longer required, set P0 or A0.
In the delivery state, this is P0 or A0. (If changes have already been made in the settings, the number 1 or 2 can also be listed here)

Installation

Assembly Instructions

Install the device with the power supply disconnected and with the pump motor lying horizontally (the arrow on the pump housing shows the direction of flow) (Fig.1). When performing insulation work, ensure that the pump motor and the electronics housing are not covered in insulation. If the installation location changes, you must rotate the motor housing as follows ( Fig. 2a to 2d):

  • Unscrew the socket screw
  • Rotate the motor housing
  • Re-insert the socket screw and tighten

Electrical connection

Warning: Risk of death!
Improper installation and improper electrical connection can present a fatal hazard. Hazards
posed by electrical power must be eliminated.

  • Only have installation and electrical connection work performed by specialist staff and in accordance with the applicable regulations (e.g. IEC, VDE etc.).
  • Incorrect installation and electrical connection can pose a fatal risk. Prevent hazards arising from electrical energy.
  • Only have installation and electrical connection performed by a specialist and in line with the valid regulations (e.g. IEC, VDE, etc.)!
  • The current type and voltage must correspond with the information on the type plate.
  • Observe the specifications of local energy supplier!
  • Observe accident prevention regulations!
  • Never pull on the power cable
  • Do not bend the cable
  • Do not place any objects on the cable
  • When using the pump in systems at temperatures over 90 °C, use a connection line that is  suitably heat resistant.
  • Hazards such as sharp edges and burrs arise during installation.
  • When transporting the pump, never hold it by the power cable.
  • The pump could cause an injury if it falls.

WITA go.future 2 – 40-XX LED | 60-XX LED

Assembling the power plug

          1. Assembly Instructions

Connect the power cable to the pump as shown. Caution: Line voltage! Observe the required protective measures, national body regulations and local provisions at all times. The cable crosssection may be no smaller than 0.75 mm2. Use ferrules if using fine-wire cables

Fill and vent the system correctly. To vent the pump, loosen the indicated screw by turning it anti-clockwise. Caution! Hot water may escape here, depending on the system’s operating state. Afterwards, re-tighten the screw and start the venting programme (see section 7.6 on page 37).
After this process, you can start the pump  inthe desired control mode. Incomplete venting can lead to noises in the pump and system.

Warning! Risk of burns! The entire pump can be very hot, depending on the operating state of the system.

Service and Maintenance

Switch off the power to the system before performing maintenance, cleaning or repair work, and secure it against unauthorised reactivation.
Allow the pump to cool down in the event of high temperatures and system pressures. There is a risk of scalds!

Faults, Causes and Remedies

Maintenance work or repair attempts may only be undertaken by qualified persons. Switch off the power to the system before performing maintenance, cleaning or repair work, and secure it against unauthorised reactivation. Allow the pump to cool down in the event of high temperatures and system pressures. There is a risk of scalds!

Error indication orError code in the display of the pump| Possible causes| Remedy
---|---|---
Pump does not suply;Display does not light up| Error in the power supply| Check the power supply at the pumpif necessary switch on the protective switch again
Pump is running; but doesnot suply water| Air in the system| Vent the pump (see chapter 7.6 and chapter 14 in themanual)
Valve closed| Open the Valve
Noises in the system| Air in the system| Vent the system
Capacity of the pump too high| Check the pump settings
Pump is making noises| Air in the pump| Vent the pump (see chapter 7.6 and chapter 14 in the manual)
Too low system pressure| Increase the supply pressure
Expansion tank is damaged| Check the gas volume in the expansion tank
Building does not get warm| Pumpeneinstellung fehlerhaft| Increase the set point ( see chapter 7.3 in the manual)
Pump settings can not bechanged| Error in the programoperation| Pump reverse into the factory settings (reset )disconnect the pump from the power supply and wait min. 15 minutesrestore the power supply while holding down the button until all LED’s light up.After releasing the button the pump has got back the factory settings.(highest constant characteristic) – the pump can be reset
No automatic regulation of the powerin the proportional pressure stages| One in the system mounted and opened overflow valve ( discharge valve ) prevents the regulation| If possible remove the overflow valve ( discharge valve ) or close it.
Error indication orError code in the display of the pump| Possible causes| Remedy
---|---|---
The consumption displayshows E3| Rotor blocked| Switch the pump off and secure against beingswitched back on. If possible, close the shut-off valve in front of and behind the pump or drain the water.
| Depending on the operating condition of thesystem, hot water can escape! Risk of burns! Depending on the operating condition of the system, hot water can escape! Risk of burns! Unscrew the 4 head cap screws and remove the pump head by loosening the motor head. Pump impeller must be able to rotate easily. Remove any impurities or foreign bodies and reassemble the pump. In case of slightly blocking could it be sufficient if theshaft will be moved manual with a screwdriver The shaft does have a notch for these purpose and is accessible after loosening of the vent screw.ATTENTION ! Hot water could come out !!! Risk ofScalding !!! Is the error still existing the pump must be replaced
The power indicator flashes every second| The pump will not supplied with system voltageThe flashing of the display arises from the fact that the pump rotor itself through the movement if the water turns and the pumps feels likea generator| Check mains voltage at the pump.
The consumption display shows E1| Electronic error / overvoltage| Replace the pump
The consumption display shows E2| Overtemperature| Lower the temperature in the systemPress any key or disconnect the pump for minimum 1 minute from the power supplyIs the error still existing the pump must be replaced
The consumption display shows E4| Overvoltage / undervoltage| Inspect mains voltage (The pump may not beoperated with leading edge, trailing edge or pulse control)
The consumption display shows E5| Electronic error| Replace the pump

Disposal

Do not dispose of the pump and/or individual parts in household waste! Dispose of the pump and/or parts in an environmentally conscious way. To do this, please contact a public or private disposal organisation. A list of the materials used in our products is provided in the download area of our website. (www.wita.de)

WITA – Wilhelm Taake GmbH
Böllingshöfen 85 | D-32549 Bad Oeynhausen
Tel.: +49 5734 512380 | Fax: +49 5734 1752
www.wita.de | info@wita.de
HEL-WITA Sp. z o.o.
Zielonka, ul. Biznesowa 22 | 86-005 Białe Błota
Tel.: + 52 564 09 00 | Fax: + 52 564 09 22
www.wita.pl | info@wita.pl
Stand 06/2019 ·
As of 06/2019 · Production-related deviations in dimensions and configurations are reserved, as are technical alterations and errors.