MEDC DB4 25W Loudspeaker Instruction Manual
- June 13, 2024
- MEDC
Table of Contents
MEDC DB4 25W Loudspeaker
Product Information
The Speaker DB4 is a speaker unit designed for use in potentially explosive atmospheres and harsh environmental conditions. It is suitable for both offshore and onshore use where light weight and corrosion resistance are required. The speaker is available in 3 standard wattage ratings ranging from 8 watts to 25 watts. Different sound levels can be obtained by selecting the transformer tappings in the unit. The speaker is UL listed for use in the USA and Canada and complies with UL and CSA standards.
The DB4 Speaker is designed to provide an audible warning sound when required. It has been assessed for functional safety and is intended for use in a safety system conforming to the requirements of IEC61508. The speaker is classified as a Type A device and has a proven in-use summary table that indicates its safety function, architectural constraints, and hardware safety integrity compliance.
Product Usage Instructions
- Verify the operating voltage of the speaker by checking the unit label.
- Select the desired wattage rating by choosing the appropriate transformer tapping. Refer to the table provided in the user manual for details.
- Install the speaker in a location that requires an audible warning sound when necessary.
- Ensure that the installation, operation, and maintenance of the speaker comply with the specified conditions of safe use mentioned in the user manual. Failure to observe these conditions may compromise the safety integrity of the equipment.
Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, however, accept responsibility for damage, loss or expense resulting from any error or omission. We reserve the right to make alterations in line with technical advances and industry standards.
INTRODUCTION
This range of loudspeakers, intended for use in potentially explosive gas and
dust atmospheres, has a power rating of up to 25 watts and is suitable for use
in all gas groups including hydrogen.
The flamepaths, flare and the body are manufactured completely from a UV
stable glass reinforced polyester. Stainless steel screws and sinter are
incorporated thus ensuring a corrosion free product. A tapered Flamepath is
used to overcome the problems of assembly of parallel spigot flamepaths.
INSTALLATION
General
-
When installing and operating explosion-protected equipment, requirements for selection, installation and operation should be referred to eg. IEC60079-14 worldwide and the ‘National Electrical Code’ in North America. Additional national and/or local requirements may apply.
-
Ensure that all nuts, bolts and fixings are secure.
-
Ensure that only the correct listed or certified stopping plugs are used to blank off unused gland entry points and that the NEMA/IP rating of the unit is maintained. MEDC recommend the use of a sealing compound such as HYLOMAR PL32 on the threads of glands and stopping plugs in order to maintain the IP rating of the unit.
-
The unit mounts via 2 off ∅23/64” (∅9mm) mounting holes in the ‘U’ shaped stirrup / mounting bracket. The holes have been designed to accept an M8 screw or bolt. If required the unit can be initially placed using
the ∅½” (∅13mm) central hole in the mounting bracket. The unit can then be rotated into the correct orientation and fixed via the other two holes. -
When the unit is fixed in the required position, it’s alignment can be adjusted by loosening the two M6 screws which fasten the mounting bracket to the speaker. The speaker can then be adjusted to the required position and the screws tightened. The unit should be positioned such that dust/debris or water cannot settle in the re-entrant horn.
-
MEDC recommend the use of stainless steel screws.
Cable Termination
CAUTION : Before removing the cover assembly, ensure that the power to
the unit is isolated.
General
- The cover is secured with 6 off M5 cover screws (4.0mm A/F hexagon key). Once the cover fixings are unscrewed, twist the cover assembly gently clockwise and anti-clockwise, whilst pulling it away from the base. Remove to gain access to the interior.
- Ensure all non-captive fixings are kept in a safe accessible location during cable termination.
- Cable termination should be in accordance with specifications applying to the required application. MEDC recommends that all cables and cores should be correctly identified. Please refer to the wiring diagram provided with the product.
- Ensure that only the correct listed or certified cable glands are used and that the assembly is shrouded and correctly earthed.
- All cable glands should be of an equivalent NEMA/IP rating to that of the speaker and integrated with the unit such that this rating is maintained.
- The internal earth terminal, where fitted, must be used for the equipment grounding connection and the external terminal is for a supplementary bonding connection where local codes or authorities permit or require such a connection.
- Once termination is complete, carefully replace the cover assembly back onto the body, avoiding damage to the mating surfaces. Replace the cover screws into the holes in the cover assembly and tighten evenly. Ensure the O-ring is seated correctly on the cover during re-assembly. Ensure the required maximum gap of 0.15mm is maintained between the cover and the base once assembled.
OPERATION
The operating voltage of the unit is stated on the unit label. The speaker is available in 3 standard wattage ratings from 8 watts to 25 watts. Different sound levels can be obtained by selecting the transformer tappings in the unit. See table below for details.
Transformer Tappings | Power (W) |
---|---|
25W | 15W |
1:2 | 25.0 |
2:3 | 12.5 |
3:4 | 6.0 |
1:3 | 4.0 |
2:4 | 2.0 |
1:4 | 1.0 |
GENERAL ARRANGEMENT
MAINTENANCE
During the working life of the unit, it should require little or no maintenance. GRP will resist attack by most acids, alkalis and chemicals and is as resistant to concentrated acids and alkalis as most metal products. However, if abnormal or unusual environmental conditions occur due to plant damage or accident etc., then visual inspection is recommended. If the unit requires cleaning, then only clean exterior with a damp cloth to avoid electro-static charge build up. Repairs should be undertaken by returning the unit to MEDC or by an authorised repairer of Ex equipment. If a unit fault should occur, then the unit can be repaired by MEDC.
CERTIFICATION/APPROVALS
Please refer to the marking on the unit for specific approval details
UL listed for use in USA (USL) and Canada (CNL ) Class I, Zone 1, AExd IIC T4 Class 1, Div. 2, Groups A, B, C & D Class II, Div. 2, Groups F & G
UL Standards UL 1480, UL60079-0, UL60079-1, CSA E60079-0, CSA E60079-1
FUNCTIONAL SAFETY
Introduction
- The DB4 Speaker has been designed for use in potentially explosive atmospheres and harsh environmental conditions. The glass reinforced polyester enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance is required.
- The FMEDA has considered the worst case scenario which includes the Exe Chamber on the rear.
- The safety function of the Speaker is to provide an audible warning when required.
- Under No fault (Normal) Operating conditions the DB4 Speaker will provide an audible warning when required.
- Under fault conditions the failure mode of the Speaker is a failure to provide an audible warning sound. For the failure rate associated with this failure mode please refer to the table below.
Assessment of Functional Safety
- The DB4 Speaker is intended for use in a safety system conforming to the requirements of IEC61508.
- Sira Test & certification Ltd has conducted a Failure Modes Effect and Diagnostic Analysis (FMEDA) of the DB4 Speaker unit against the requirements of IEC61508-2 using a proof test interval of 8760hrs.
- The DB4 Speaker is classed as a Type A device.
PROVEN IN USE SUMMARY TABLE
DB4 SPEAKER
Safety Function of the DB4 Speaker:
To provide an audible warning sound when required ’
Architectural constraints:
| Type A HFT=0
SFF = 85.00%
| Proof Test Interval
=8760Hrs MTTR = 8 Hrs
| SIL2
Random hardware failures:| ‘ADD = 0
‘ADU = 4.70E-07
| ‘ASD = 0
‘ASU = 2.86E-06
Probability of failure on demand:| PFDAVG=2.06E-03
(Low Demand Mode)
| SIL2
Probability of Dangerous failure on safety function:| PFH = 4.70E-07
(High Demand Mode)
| SIL2
Hardware safety integrity compliance| Route 1H
Systematic safety integrity compliance| Route 1S
Systematic Capability| SC2
Overall SIL-capability achieved| SIL 2 (Low Demand) SIL 2 (High Demand)
Conditions of Safe Use
The following conditions apply to the installation, operation and maintenance of the assessed equipment. Failure to observe these may compromise the safety integrity of the assessed equipment:
- The user shall comply with the requirements given in the manufacturer’s user documentation (This Safety Manual and Technical manual) in regard to all relevant functional safety aspects such as application of use, installation, operation, maintenance, proof tests, maximum ratings, environmental conditions, repair, etc;
- Selection of this equipment for use in safety functions and the installation, configuration, overall validation, maintenance and repair shall only be carried out by competent personnel, observing all the manufacturer’s conditions and recommendations in the user documentation.
- All information associated with any field failures of this product should be collected under a dependability management process (e.g., IEC 60300-3-2) and reported to the manufacturer.
- The unit should be tested at regular intervals to identify any malfunctions; in accordance with this safety manual.
Cooper MEDC Ltd, Colliery Road, Pinxton, Nottingham NG16 6JF, United Kingdom.
Tel: +44 (0)1773 864100
E-Mail:
medc.sales@cooperindustries.com •
medc.orders@cooperindustries.com
Web: www.coopermedc.com
MEDC Stock No: TM105-ISS.B
© Cooper MEDC 2011