MEDC High Intensity Strobe Warning Lights Owner’s Manual

June 9, 2024
MEDC

MEDC High Intensity Strobe Warning Lights

Introduction

These listed strobes have been designed for use in potentially explosive atmospheres and harsh environmental conditions. The enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance is required. The housings are manufactured completely from a U.V. stable, glass reinforced polyester. Stainless steel screws and mounting bracket are available ensuring a totally corrosion-free product. The model XB15 contains a supervisory diode and four wire lead connection for fire alarm applications. Units can be painted to customer specification and supplied with identification labels.

European and other worldwide approvals are available, refer to main section of catalog.

  • UL listed for USA and Canada
    • Hazardous locations:
  • Class I, Div. 2, Groups A, B, C & D.
  • Class II, Div 2 Groups F & G.
  • Class I, Zone 1, AExd IIC T4/T5/T6.
    • Ordinary locations: Visual-Signal Device.
    • Marine Listed
  • ULC Listed to Canadian Safety Standards.
  • Conforms to ULC regulated a.c. power supplies.
  • CSFM approved.
  • ATEX approved.
  • NEMA 4x and 6, IP66 & 67.
  • Certified temperature
    • 67°F to +158°F.
    • 55°C to +70°C.
  • Pipe mount or direct mount enclosure.
  • Corrosion-free GRP.
  • 520,000 peak candlepower.
  • Four wires and supervisory diode.
  • Optional stainless steel backstrap.
  • Various lens colors.
  • Optional relay initiate.
  • Optional cast or wire lens guard.
  • Up to 3 x ¾” NPT entries.
  • Filament version available (100W max).

Specification

  • Certification: UL Listed for USA and Canada:

    • Hazardous locations
      Class I, Div 2, Groups A, B, C & D.
      Class II, Div 2 Groups F & G
      Class 1, Zone 1, AExd IIC T4/T5/T6.
      UL listing No. E187894.

    • Ordinary locations: Visual Signal Device.

    • Marine listed
      UL listing No. S8128
      ULC Listed: Listing No. CE133
      CENELEC/ATEX approved.
      CENELEC EN50014 & EN50018
      ATEX Cert. No. Baseefa 04ATEX0009X

  • Material:

    • Body: Glass-reinforced polyester.
    • Lens: Glass.
    • Backstrap: stainless steel 316.
    • Wire Guard (optional): Stainless steel wire.
    • Cast Guard (optional): Aluminium LM25M.
  • Finish: Natural black or epoxy painted to customer specification.

  • Voltage: 24, 48V d.c. 110, 120, 230, 240, 254V a.c.

  • Tube Energy: 15 Joules.

  • Tube Life: >1 x 106 flashes.

  • Flash Rate: 60, 80, 120 fpm.

  • Certified Temperature:

    • 67°F to +104°F (-55°C to +40°C) T6.
    • 67°F to +131°F (-55°C to +55°C) T5.
    • 67°F to +158°F (-55°C to +70°C) T4.
  • Weight: Pipe mount: 5¾lb/2.6kg; Direct mount: 6½lb/3.0kg.

  • Ingress Protection: NEMA 4x & 6, IP66 & IP67.

  • Entries:

    • Supplied as 2 x ¾” NPT (direct mount) or ¾” (pipe mount) as standard.
    • Other options available: Up to 3 x ½” NPT or 3 x ¾” NPT (direct mount); ½” NPT (pipe mount) – contact sales office to order.
  • Terminals:

    • Direct mount: 12 x 14AWG.
    • Pipe mount: 8 x 14AWG.
  • Relay Initiate: Available on all versions – operates with 24V d.c. initiate supplies only.

  • Labels: Tag/Duty label option.MEDC-High-Intensity-Strobe-Warning-Lights-1

  • Electrical Ratings: UL/UW/UM versions
     | d.c| a.c
    ---|---|---
    Voltage| 24| 48| 110| 120| 230| 240| 254
    Current (A)| 0.99| 0.73| 0.4| 0.4| 0.2| 0.2| 0.17
    Effective Candlepower –  330 (Effective candlepower is the intensity that would appear to

an observer if the light was burning steadily)

  • Multiplying Factor for Colored Lenses: UL/UW/UM versions
    Red| Blue| Amber| Green| Yellow
    ---|---|---|---|---
    0.15| 0.12| 0.51| 0.49| 0.86
  • Electrical Ratings: ULC versions
     | d.c.| Regulated a.c
    ---|---|---
    Voltage| 24| 48| 120| 240
    Current (A)| 1.24| 0.76| 0.4| 0.2
    Light Output (Cd) No Guard| 60| 50| 30| 30
  • Light output tested to ULC-S526-07 requirements Multiplying Factor for Colored Lenses: ULC versions
    Red| Blue| Amber| Green| Yellow
    ---|---|---|---|---
    0.2| 0.27| 0.36| 0.24| 0.65

Ordering Requirements

The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Standard products available for immediate shipping – contact sales office for details.MEDC-High-Intensity-Strobe-Warning-
Lights-2

All the above specifications, dimensions, weights and tolerances are nominal (typical) and MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.

Cooper MEDC Ltd, Colliery Road,
Pinxton, Nottingham NG16 6JF, UK.
Tel: +44 (0)1773 864100
Fax: +44 (0)1773 582800

Cooper MEDC (USA) 3413 North Sam Houston Parkway,
West, Houston, Texas 77086, USA.
Tel: +1 (713) 937 9772
Fax: +1 (713) 937 9773

Sales Enq. Fax: +44 (0)1773 582830
Sales Orders Fax: +44 (0)1773 582832
E-Mail: medc.sales@cooperindustries.com
Web: www.medc.com

firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals