CROWN Xavier 3KW Solar Inverter User Manual
- June 13, 2024
- CROWN
Table of Contents
Xavier 3KW Solar Inverter
Product Information
Xavier 3KW Inverter/Charger
Version: 1.0
Table Of Contents
-
About This Manual
-
Safety Instructions
-
Introduction
-
Installation
-
Operation
-
Clearance and Maintenance for Anti-Dust Kit
-
Specifications
-
Troubleshooting
-
-
About This Manual
Purpose: This manual describes the assembly,
installation, operation, and troubleshooting of the Xavier 3KW
Inverter/Charger. It is important to read this manual carefully
before installations and operations. Please keep this manual for
future reference.
Scope: This manual provides safety and
installation guidelines, as well as information on tools and
wiring.
Safety Instructions
WARNING: This chapter contains important safety
and operating instructions. It is crucial to read and keep this
manual for future reference.
-
Before using the unit, read all instructions and cautionary
markings on the unit, the batteries, and all appropriate sections
of this manual. -
CAUTION: To reduce the risk of injury, charge
only deep-cycle lead acid type rechargeable batteries. Using other
types of batteries may cause bursting, leading to personal injury
and damage.
Product Usage Instructions
To use the Xavier 3KW Inverter/Charger, follow these
instructions:
-
Read the entire manual carefully before proceeding with
installation and operation. -
Ensure that all safety instructions and cautionary markings are
understood and followed. -
Use only deep-cycle lead acid type rechargeable batteries with
the inverter/charger. Using other battery types can be dangerous
and may cause damage. -
Follow the provided assembly instructions for proper
installation of the unit. -
Connect the appropriate wiring according to the guidelines
provided in the manual. -
Refer to the operation section of the manual for detailed
instructions on how to use the inverter/charger. -
Maintain proper clearance and perform regular maintenance as
described in the manual, especially regarding the anti-dust
kit. -
If any issues or troubleshooting is required, refer to the
troubleshooting section of the manual for guidance. -
Keep the manual for future reference and follow all safety
instructions during use.
USER MANUAL Xavier 3KW
INVERTER / CHARGER
Version: 1.0
Table Of Contents
ABOUT THIS MANUAL …………………………………………………………………………………………………………………….. 1
Purpose………………………………………………………………………………………………………………………………………… 1 Scope
…………………………………………………………………………………………………………………………………………… 1
SAFETY INSTRUCTIONS………………………………………………………………………………………………………………….. 1
INTRODUCTION ………………………………………………………………………………………………………………………………. 2
Features ……………………………………………………………………………………………………………………………………….. 2 Basic System
Architecture ………………………………………………………………………………………………………………. 2 Product
Overview…………………………………………………………………………………………………………………………… 3
INSTALLATION ………………………………………………………………………………………………………………………………… 4
Unpacking and Inspection……………………………………………………………………………………………………………….. 4
Preparation …………………………………………………………………………………………………………………………………… 4 Mounting the
Unit …………………………………………………………………………………………………………………………… 4 Battery Connection
………………………………………………………………………………………………………………………… 5 AC Input/Output Connection
……………………………………………………………………………………………………………. 7 PV Connection
………………………………………………………………………………………………………………………………. 8 Final
Assembly………………………………………………………………………………………………………………………………. 9
OPERATION…………………………………………………………………………………………………………………………………… 10
Power ON/OFF ……………………………………………………………………………………………………………………………. 10 Operation and
Display Panel …………………………………………………………………………………………………………. 10 LCD Display Icons
……………………………………………………………………………………………………………………….. 11 LCD
Setting…………………………………………………………………………………………………………………………………. 13 Display Setting
…………………………………………………………………………………………………………………………….. 17 Operating Mode
Description ………………………………………………………………………………………………………….. 21 Battery Equalization
Description …………………………………………………………………………………………………….. 23 Fault Reference
Code…………………………………………………………………………………………………………………… 25 Warning Indicator
…………………………………………………………………………………………………………………………. 25
CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT…………………………………………………………………. 26
Overview …………………………………………………………………………………………………………………………………….. 26 Clearance and
Maintenance ………………………………………………………………………………………………………….. 26
SPECIFICATIONS …………………………………………………………………………………………………………………………… 27
Table 1 Line Mode Specifications ……………………………………………………………………………………………………. 27
Table 2 Inverter Mode Specifications ………………………………………………………………………………………………. 28
Table 3 Charge Mode Specifications ……………………………………………………………………………………………….. 29
Table 4 General Specifications ……………………………………………………………………………………………………….. 29
TROUBLE SHOOTING ……………………………………………………………………………………………………………………. 30
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and
troubleshooting of this unit. Please read this manual carefully before
installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information
on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions.
Read and keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on
the unit, the batteries and all appropriate sections of this manual.
2. CAUTION –To reduce risk of injury, charge only deep-cycle lead acid type
rechargeable batteries. Other types of batteries may burst, causing personal
injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when
service or repair is required. Incorrect re-assembly may result in a risk of
electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting
any maintenance or cleaning. Turning off the unit will not reduce this risk.
5. CAUTION Only qualified personnel can install this device with battery.
6. NEVER charge a frozen battery. 7. For optimum operation of this
inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger. 8. Be
very cautious when working with metal tools on or around batteries. A
potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could
cause an explosion. 9. Please strictly follow installation procedure when you
want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details. 10. One piece of
150A fuse is provided as over-current protection for the battery supply. 11.
GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a
permanent grounded
wiring system. Be sure to comply with local requirements and regulation to
install this inverter. 12. NEVER cause AC output and DC input short circuited.
Do NOT connect to the mains when DC input
short circuits. 13. Warning!! Only qualified service persons are able to
service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to
local dealer or service center for maintenance. 14. WARNING: Because this
inverter is non-isolated, only three types of PV modules are acceptable:
single crystalline, poly crystalline with class A-rated and CIGS modules. To
avoid any malfunction, do not connect any PV modules with possible current
leakage to the inverter. For example, grounded PV modules will cause current
leakage to the inverter. When using CIGS modules, please be sure NO grounding.
15. CAUTION: It’s requested to use PV junction box with surge protection.
Otherwise, it will cause damage on inverter when lightning occurs on PV
modules.
1
INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter,
solar charger and battery charger to offer uninterruptible power support with
portable size. Its comprehensive LCD display offers user-configurable and
easy-accessible button operation such as battery charging current, AC/solar
charger priority, and acceptable input voltage based on different
applications.
Features
Pure sine wave inverter Inverter running without battery Configurable input
voltage range for home appliances and personal computers via LCD setting
Configurable battery charging current based on applications via LCD setting
Configurable AC/Solar Charger priority via LCD setting Compatible to mains
voltage or generator power Auto restart while AC is recovering Overload/ Over
temperature/ short circuit protection Smart battery charger design for
optimized battery performance Cold start function
Basic System Architecture
The following illustration shows basic application for this inverter/charger.
It also includes following devices to have a complete running system:
Generator or Utility. PV modules Consult with your system integrator for other
possible system architectures depending on your requirements. This inverter
can power all kinds of appliances in home or office environment, including
motor-type appliances such as tube light, fan, refrigerator and air
conditioner.
Figure 1 Hybrid Power System 2
Product Overview
1. LCD display 2. Status indicator 3. Charging indicator 4. Fault indicator
5. Function buttons 6. Power on/off switch 7. AC input 8. AC output 9. PV
input 10. Battery input 11. RS-232 communication port
3
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. You should have received the following items inside of
package:
The unit x 1 User manual x 1 Communication cable x 1
Preparation
Before connecting all wirings, please take off bottom cover by removing screws
as shown below.
Mounting the Unit
Consider the following points before selecting where to install: Do not mount
the inverter on flammable construction
materials. Mount on a solid surface Install this inverter at eye level in
order to allow the LCD
display to be read at all times. For proper air circulation to dissipate heat,
allow a
clearance of approx. 20 cm to the side and approx. 50 cm above and below the
unit. The ambient temperature should be between 0°C and 55°C to ensure optimal
operation. The recommended installation position is to be adhered to the wall
vertically. Be sure to keep other objects and surfaces as shown in the diagram
to guarantee sufficient heat dissipation and to have enough space for removing
wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
4
Install the unit by screwing two screws. It’s recommended to use M4 or M5 screws.
Battery Connection
This model can be operated without battery connection. Connect to battery if
necessary. CAUTION: For safety operation and regulation compliance, it’s
requested to install a separate DC over-current protector or disconnect device
between battery and inverter. It may not be requested to have a disconnect
device in some applications, however, it’s still requested to have over-
current protection installed. Please refer to typical amperage in below table
as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use
the proper recommended cable as below.
Recommended battery cable size:
Model
Wire Size
Xavier 3KW
1 x 2AWG
Cable (mm2) 35
Torque valuemax 2 Nm
Please follow below steps to implement battery connection: 1. For Xavier 3KW
models, assemble battery ring terminal based on recommended battery cable and
terminal
size. Recommended dimensions for ring terminal is D (8.4 mm) and L (39.2 mm).
5
2. Connect all battery packs as below chart. It is recommend to connect at
least 100Ah capacity battery.
3KVA
3. For Xavier 3KW model, apply ring terminals to battery wires and secure it
to the battery terminal block with the bolts properly tightened. Refer to
battery cable size for torque value. Make sure polarity at both the battery
and the inverter is correctly connected and ring terminals are secured to the
battery terminals.
WARNING: Shock Hazard Installation must be performed with care due to high
battery voltage in series. CAUTION!! Do not place anything between inverter
terminals and the ring terminals. Otherwise, overheating may occur. CAUTION!!
Do not apply anti-oxidant substance on the terminals before terminals are
securely tightened. CAUTION!! Before making the final DC connection or closing
DC breaker/disconnector, be sure positive (+) must be connected to positive
(+) and negative (-) must be connected to negative (-).
6
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a
separate AC breaker between inverter and AC input power source. This will
ensure the inverter can be securely disconnected during maintenance and fully
protected from over current of AC input. The recommended spec of AC breaker is
20A. CAUTION!! There are two terminal blocks with “IN” and “OUT” markings.
Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel. WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below. Suggested cable requirement for AC wires
Model
Gauge
Cable (mm2)
Torque Value
Xavier 3KW
14 AWG
2.5
0.6 Nm
Please follow below steps to implement AC input/output connection: 1. Before
making AC input/output connection, be sure to open DC protector or
disconnector first. 2. Remove insulation sleeve 10mm for six conductors. And
shorten phase L and neutral conductor N 3 mm. 3. Insert AC input wires
according to polarities indicated on terminal block and tighten the terminal
screws. Be
sure to connect PE protective conductor ( ) first.
Ground (yellow-green) LLINE (brown or black) NNeutral (blue)
WARNING: Be sure that AC power source is disconnected before attempting to
hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal
block and tighten terminal screws. Be sure to connect PE protective conductor
( ) first. Ground (yellow-green) LLINE (brown or black) NNeutral (blue)
5. Make sure the wires are securely connected. 7
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes
to restart because it’s required to have enough time to balance refrigerant
gas inside of circuits. If a power shortage occurs and recovers in a short
time, it will cause damage to your connected appliances. To prevent this kind
of damage, please check manufacturer of air conditioner if it’s equipped with
time-delay function before installation. Otherwise, this inverter/charger will
trig overload fault and cut off output to protect your appliance but sometimes
it still causes
PiVnteCrnoalndanmeacgetitoo nthe air conditioner.
CAUTION: Before connecting to PV modules, please install separately a DC
circuit breaker between inverter and PV modules.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Wire Size
Cable (mm2)
Torque valuemax
1 x 12AWG
4
1.2 Nm
WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable: single crystalline, poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding.
CAUTION: It’s requested to use PV junction box with surge protection. Otherwise, it will cause damage on inverter when lightning occurs on PV modules.
PV Module Selection: When selecting proper PV modules, please be sure to consider below parameters: 1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter. 2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL
Xavier 3KW
Max. PV Array Open Circuit Voltage
450Vdc
PV Array MPPT Voltage Range
60~400Vdc
Take 325Wp PV module as an example. After considering above two parameters, the recommended module
configurations are listed as below table.
Solar Panel Spec. (reference) – 325Wp – Vmp: 33.6Vdc
SOLAR INPUT (Min in serial: 2 pcs, max. in serial: 10 pcs)
Q’ty of Total input
panels
power
– Imp: 9.68A – Voc: 41.1Vdc – Isc: 10.2A – Cells: 120
2 pcs in serial 4 pcs in serial 8 pcs in serial 10 pcs in serial
2 pcs 4 pcs 8 pcs 10 pcs
650W 1300W 2600W 3000W
PV Module Wire Connection Please follow below steps to implement PV module
connection: 1. Remove insulation sleeve 10 mm for positive and negative
conductors. 2. Suggest to put bootlace ferrules on the end of positive and
negative wires with a
proper crimping tool. 3. Check correct polarity of wire connection from PV
modules and PV input
connectors. Then, connect positive pole (+) of connection wire to positive
pole (+) of PV input connector. Connect negative pole (-) of connection wire
to negative pole (-) of PV input connector. Screw two wires tightly in
clockwise direction. Recommended tool: 4mm blade screwdriver
8
Final Assembly
After connecting all wirings, please put bottom cover back by screwing screws
as shown below.
9
OPERATION
Power ON/OFF
Side view of unit Once the unit has been properly installed and the batteries
are connected well, simply press On/Off switch (located on the button of the
case) to turn on the unit.
Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel
of the inverter. It includes three indicators, four function keys and a LCD
display, indicating the operating status and input/output power information.
LCD display
LED indicators Function keys
Function Keys Function Key ESC UP DOWN ENTER
Description To exit setting mode To go to previous selection To go to next selection To confirm the selection in setting mode or enter setting mode
10
LCD Display Icons
Icon
Input Source Information Indicates the AC input. Indicates the PV input
Function description
Indicate input voltage, input frequency, PV voltage, charger current, charger power, battery voltage.
Configuration Program and Fault Information
Indicates the setting programs.
Indicates the warning and fault codes.
Warning:
flashing with warning code.
Fault: Output Information
lighting with fault code
Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Battery Information
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode.
In AC mode, it will present battery charging status.
Status
Battery voltage
LCD Display
<2V/cell
Constant Current mode / Constant
2 ~ 2.083V/cell 2.083 ~ 2.167V/cell
4 bars will flash in turns. Bottom bar will be on and the other three bars will flash in turns. Bottom two bars will be on and the other two bars will flash in turns.
Voltage mode > 2.167 V/cell
Bottom three bars will be on and the top bar will flash.
Floating mode. Batteries are fully charged.
4 bars will be on.
11
In battery mode, it will present battery capacity.
Load Percentage
Battery Voltage
< 1.85V/cell
Load >50%
1.85V/cell ~ 1.933V/cell 1.933V/cell ~ 2.017V/cell
LCD Display
2.017V/cell
Load < 50%
< 1.892V/cell 1.892V/cell ~ 1.975V/cell 1.975V/cell ~ 2.058V/cell
2.058V/cell
Load Information Indicates overload.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
0%~24%
25%~49%
50%~74%
75%~100%
Mode Operation Information Indicates unit connects to the mains. Indicates
unit connects to the PV panel. Indicates load is supplied by utility power.
Indicates the utility charger circuit is working. Indicates the DC/AC inverter
circuit is working.
Mute Operation Indicates unit alarm is disabled.
12
LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter
setting mode. Press “UP” or “DOWN” button to select setting programs. And
then, press “ENTER” button to confirm the selection or ESC button to exit.
Setting Programs:
Program
Description
00
Exit setting mode
Selectable option Escape
Utility first (default)
Solar first
Output source priority:
01
To configure load power
source priority
SBU priority
Maximum charging current:
To configure total charging current for solar and utility 60A (default)
02
chargers.
(Max. charging current =
utility charging current +
solar charging current)
Appliances (default)
03
AC input voltage range
UPS
05
Battery type
AGM (default)
Utility will provide power to the loads as first priority. Solar and battery
energy will provide power to the loads only when utility power is not
available. Solar energy provides power to the loads as first priority. If
solar energy is not sufficient to power all connected loads, Utility energy
will supply power to the loads at the same time. Solar energy provides power
to the loads as first priority. If solar energy is not sufficient to power all
connected loads, battery energy will supply power to the loads at the same
time. Utility provides power to the loads only when battery voltage drops to
either low-level warning voltage or the setting point in program 12.
Setting range is from 10A to 120A. Increment of each click is 10A.
If selected, acceptable AC input voltage range will be within 90-280VAC. If
selected, acceptable AC input voltage range will be within 170-280VAC. Flooded
13
User-Defined
If “User-Defined” is selected,
battery charge voltage and low DC
cut-off voltage can be set up in
program 26, 27 and 29.
Restart disable (default)
Restart enable
06
Auto restart when overload occurs
07
Auto restart when over temperature occurs
Restart disable (default)
Restart enable
09
Output frequency
50Hz (default)
60Hz
220V
230V (default)
10
Output voltage
240V
Maximum utility charging current
Note: If setting value in
30A (default)
11
program 02 is smaller than
that in program in 11, the
inverter will apply charging
current from program 02 for
utility charger.
23.0V (default)
Setting voltage point back
12
to utility source when selecting “SBU” (SBU
priority) in program 01.
Setting range is 2A, then from 10A to 120A. Increment of each click is 10A.
Setting range is from 22V to 25.5V. Increment of each click is 0.5V.
Battery fully charged
27V (default)
Setting voltage point back to battery mode when 13 selecting “SBU” (SBU priority) in program 01.
Setting range is from 24V to 29V. Increment of each click is 0.5V.
If this inverter/charger is working in Line, Standby or Fault mode,
charger source can be programmed as below:
Charger source priority:
Utility first
Utility will charge battery as first
16
To configure charger
priority.
source priority
Solar energy will charge battery
only when utility power is not
available.
14
Solar first
Solar energy will charge battery as
first priority.
Utility will charge battery only
when solar energy is not available.
Solar and Utility (default) Solar energy and utility will charge
Charger source priority:
battery at the same time.
16
To configure charger
source priority
Only Solar
Solar energy will be the only
charger source no matter utility is
available or not.
If this inverter/charger is working in Battery mode, only solar
energy can charge battery. Solar energy will charge battery if it’s
available and sufficient.
Alarm on (default)
Alarm off
18
Alarm control
19
Auto return to default display screen
20
Backlight control
Return to default display screen (default)
Stay at latest screen Backlight on (default)
If selected, no matter how users switch display screen, it will automatically
return to default display screen (Input voltage /output voltage) after no
button is pressed for 1 minute. If selected, the display screen will stay at
latest screen user finally switches.
Backlight off
Alarm on (default)
22
Beeps while primary source is interrupted
Alarm off
Overload bypass:
Bypass disable (default)
Bypass enable
When enabled, the unit will
23
transfer to line mode if
overload occurs in battery
mode.
Record enable (default)
Record disable
25
Record Fault code
26
Bulk charging voltage (C.V voltage)
Default setting: 28.2V
Default setting: 27.0V
27
Floating charging voltage
15
Default setting: 21.0V
29
Low DC cut-off voltage
30
Battery equalization
If self-defined is selected in program 5, this program can be set
up. Setting range is from 21.0V to 24.0V for Xavier 3KW model.
Increment of each click is 0.1V. Low DC cut-off voltage will be
fixed to setting value no matter what percentage of load is
connected.
Battery equalization
Battery equalization disable
(default)
If “Flooded” or “User-Defined” is selected in program 05, this program can be
set up.
Default setting: 29.2V
31
Battery equalization voltage
33
Battery equalized time
Setting range is from 25.0V to 31.5V for Xavier 3KW model.
Increment of each click is 0.1V.
60min (default)
Setting range is from 5min to
900min. Increment of each click is
5min.
120min (default)
34
Battery equalized timeout
35
Equalization interval
30days (default)
Setting range is from 5min to 900 min. Increment of each click is 5 min.
Setting range is from 0 to 90 days. Increment of each click is 1 day
Enable
Disable (default)
36
Equalization activated immediately
If equalization function is enabled in program 30, this program can be set up.
If “Enable” is selected in this program, it’s to activate battery equalization
immediately and LCD main page will shows
” “. If “Disable” is selected, it will cancel equalization function until next
activated equalization time arrives based on program 35
setting. At this time, ” ” will not be shown in LCD main page.
16
Display Setting
The LCD display information will be switched in turns by pressing “UP” or
“DOWN” key. The selectable information is switched as below order: input
voltage, input frequency, PV voltage, charging current, charging power,
battery voltage, output voltage, output frequency, load percentage, load in
Watt, load in VA, load in Watt, DC discharging current, main CPU Version.
Selectable information
LCD display Input Voltage=230V, output voltage=230V
Input voltage/Output voltage (Default Display Screen)
Input frequency
Input frequency=50Hz
PV voltage
PV voltage=260V
PV current
PV current = 2.5A
PV power
PV power = 500W
17
Charging current Charging power
AC and PV charging current=50A PV charging current=50A AC charging current=50A AC and PV charging power=500W PV charging power=500W AC charging power=500W
18
Battery voltage and output voltage Output frequency Load percentage
Battery voltage=25.5V, output voltage=230V
Output frequency=50Hz
Load percent=70%
When connected load is lower than 1kVA, load in VA will present xxxVA like
below chart.
Load in VA
When load is larger than 1kVA (1KVA), load in VA will present x.xkVA like below chart.
19
When load is lower than 1kW, load in W will present xxxW like below chart.
Load in Watt
When load is larger than 1kW (1KW), load in W will present x.xkW like below chart.
Battery voltage=25.5V, discharging current=1A Battery voltage/DC discharging current
Main CPU version checking
Main CPU version 00014.04
20
Operating Mode Description
Operation mode
Description
LCD display Charging by utility and PV energy.
Standby mode Note: *Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output.
No output is supplied by the unit but it still can charge batteries.
Charging by utility. Charging by PV energy.
No charging. Charging by utility and PV energy.
Fault mode Note: *Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on.
PV energy and utility can charge batteries.
Charging by utility. Charging by PV energy.
No charging.
21
Operation mode
Description
The unit will provide output power from the mains. It will also charge the
battery at line mode.
LCD display Charging by utility and PV energy.
Charging by utility.
Line Mode
If “solar first” is selected as output source priority and solar energy is not
sufficient to
provide the load, solar energy and the utility will provide the loads and
charge the battery at the
same time.
The unit will provide output power from the mains. It will also charge the battery at line mode.
If “solar first” is selected as output source priority and battery is not
connected, solar
energy and the utility will provide the loads.
Power from utility.
Battery Mode
Power from battery and PV energy.
The unit will provide output power from battery and PV power.
PV energy will supply power to the loads and charge battery at the same time.
22
Battery Mode
Power from battery only.
The unit will provide output power from battery and PV power.
Power from PV energy only.
Battery Equalization Description
Equalization function is added into charge controller. It reverses the buildup
of negative chemical effects like stratification, a condition where acid
concentration is greater at the bottom of the battery than at the top.
Equalization also helps to remove sulfate crystals that might have built up on
the plates. If left unchecked, this condition, called sulfation, will reduce
the overall capacity of the battery. Therefore, it’s recommended to equalize
battery periodically.
How to Apply Equalization Function You must enable battery equalization
function in monitoring LCD setting program 30 first. Then, you may apply this
function in device by either one of following methods: 1. Setting equalization
interval in program 35. 2. Active equalization immediately in program 36.
When to Equalize In float stage, when the setting equalization interval
(battery equalization cycle) is arrived, or equalization is active
immediately, the controller will start to enter Equalize stage.
Equalize charging time and timeout In Equalize stage, the controller will
supply power to charge battery as much as possible until battery voltage
raises to battery equalization voltage. Then, constant-voltage regulation is
applied to maintain battery voltage at the battery equalization voltage. The
battery will remain in the Equalize stage until setting battery equalized
23
time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery
voltage doesn’t rise to battery equalization voltage point, the charge
controller will extend the battery equalized time until battery voltage
achieves battery equalization voltage. If battery voltage is still lower than
battery equalization voltage when battery equalized timeout setting is over,
the charge controller will stop equalization and return to float stage.
24
Fault Reference Code
Fault Code 01
Fault Event Fan is locked when inverter is off.
02
Over temperature or NTC is not connected well.
03
Battery voltage is too high
04
Battery voltage is too low
05
Output short circuited or over temperature is detected by internal converter components.
06
Output voltage is too high.
07
Overload time out
08
Bus voltage is too high
09
Bus soft start failed
51
Over current or surge
52
Bus voltage is too low
53
Inverter soft start failed
55
Over DC voltage in AC output
57
Current sensor failed
58
Output voltage is too low
59
PV voltage is over limitation
Warning Indicator
Warning Code
Warning Event
01
Fan is locked when inverter is on.
02
Over temperature
Audible Alarm
Beep three times every second
None
03
Battery is over-charged
Beep once every second
04
Low battery
Beep once every second
Icon on Icon flashing
07
Overload
Beep once every 0.5 second
10
Output power derating
Beep twice every 3 seconds
15
PV energy is low.
Beep twice every 3 seconds
16
High AC input (>280VAC) during BUS soft start
None
Battery equalization
None
Battery is not connected
None 25
CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT
Overview
Every inverter is already installed with anti-dusk kit from factory. Inverter
will automatically detect this kit and activate internal thermal sensor to
adjust internal temperature. This kit also keeps dusk from your inverter and
increases product reliability in harsh environment.
Clearance and Maintenance
Step 1: Please loosen the screw in counterclockwise direction on the top of
the inverter.
Step 2: Then, dustproof case can be removed and take out air filter foam as
shown in below chart.
Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble
the dust-kit back to the inverter. NOTICE: The anti-dust kit should be cleaned
from dust every one month.
26
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL Input Voltage Waveform Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage High Loss Return Voltage Max AC Input Voltage Nominal Input
Frequency Low Loss Frequency Low Loss Return Frequency High Loss Frequency
High Loss Return Frequency Output Short Circuit Protection Efficiency (Line
Mode)
Transfer Time
Xavier 3KW Sinusoidal (utility or generator)
230Vac 170Vac±7V (UPS); 90Vac±7V (Appliances) 180Vac±7V (UPS); 100Vac±7V
(Appliances)
280Vac±7V 270Vac±7V
300Vac 50Hz / 60Hz (Auto detection)
40±1Hz 42±1Hz 65±1Hz 63±1Hz Circuit Breaker >95% ( Rated R load, battery full
charged ) 10ms typical (UPS); 20ms typical (Appliances)
Output Power
Output power derating: When AC input voltage drops to 170V, the output power will be derated.
Rated Power 50% Power
90V
170V
280V Input Voltage
27
Table 2 Inverter Mode Specifications
INVERTER MODEL
Rated Output Power Output Voltage Waveform Output Voltage Regulation Output
Frequency Peak Efficiency Overload Protection Surge Capacity Nominal DC Input
Voltage Cold Start Voltage Low DC Warning Voltage @ load < 50% @ load 50% Low
DC Warning Return Voltage @ load < 50% @ load 50% Low DC Cut-off Voltage @
load < 50% @ load 50% High DC Recovery Voltage High DC Cut-off Voltage No Load
Power Consumption
Xavier 3KW 3KVA/3KW
Pure Sine Wave 230Vac±5% 50Hz 93%
5s@130% load; 10s@105%~130% load 2* rated power for 5 seconds 24Vdc 23.0Vdc
23.0Vdc 22.0Vdc
23.5Vdc 23.0Vdc
21.5Vdc 21.0Vdc
31Vdc 32Vdc <35W
28
Table 3 Charge Mode Specifications
Utility Charging Mode
INVERTER MODEL
Charging Algorithm
AC Charging Current (Max)
Bulk Charging Flooded Battery
Voltage
AGM / Gel Battery
Floating Charging Voltage
Charging Curve
MPPT Solar Charging Mode
INVERTER MODEL Max. PV Array Power Nominal PV Voltage Start-up Voltage PV
Array MPPT Voltage Range Max. PV Array Open Circuit Voltage Max. Input Current
Max Charging Current
Table 4 General Specifications
INVERTER MODEL Safety Certification Operating Temperature Range Storage
temperature Humidity Dimension (DWH), mm Net Weight, kg
Xavier 3KW
3-Step
80Amp (@VI/P=230Vac)
29.2
28.2
Battery Voltage, per cell
27Vdc
2.43Vdc (2.35Vdc) 2.25Vdc
Charging Current, %
Voltage 100%
T0
T1
T1 = 10* T0, minimum 10mins, maximum 8hrs
Bulk (Constant Current)
Absorption (Constant Voltage)
50%
Current
Maintenance (Floating)
Time
Xavier 3KW
3000W 240Vdc 70Vdc +/- 10Vdc 60~400Vdc 450Vdc
13Amp 100Amp
Xavier 3KW CE
-10°C to 50°C -15°C~ 60°C 5% to 95% Relative Humidity (Non-condensing) 100 x 288 x 390
7.5
29
TROUBLE SHOOTING
Problem
Mains exist but the unit works in battery mode.
When the unit is turned on, internal relay is switched on and off repeatedly.
Buzzer beeps continuously and red LED is on.
LCD/LED/Buzzer Input voltage is displayed as 0 on the LCD and green LED is
flashing.
Green LED is flashing.
Green LED is flashing. LCD display and LEDs are flashing
Fault code 07
Fault code 05
Fault code 02
Fault code 03
Fault code 01 Fault code 06/58 Fault code 08/09/53/57 Fault code 51 Fault code
52 Fault code 55 Fault code 59
Explanation / Possible cause
Input protector is tripped
Insufficient quality of AC power. (Shore or Generator)
Set “Solar First” as the priority of output source.
Battery is disconnected.
Overload error. The inverter is overload 105% and time is up. If PV input
voltage is higher than specification, the output power will be derated. At
this time, if connected loads is higher than derated output power, it will
cause overload.
Output short circuited.
Internal temperature of inverter component is beyond spec. (check local agent
for the details.) Battery is over-charged.
The battery voltage is too high.
Fan fault Output abnormal (Inverter voltage below than 190Vac or is higher
than 260Vac) Internal components failed. Over current or surge. Bus voltage is
too low. Output voltage is unbalanced. PV input voltage is beyond the
specification.
What to do
Check if AC breaker is tripped and AC wiring is connected well.
1. Check if AC wires are too thin and/or too long. 2. Check if generator (if
applied) is working well or if input voltage range setting is correct.
(UPSAppliance) Change output source priority to Utility first.
Check if battery wires are connected well.
Reduce the connected load by switching off some equipment.
Reduce the number of PV modules in series or the connected load.
Check if wiring is connected well and remove abnormal load. Check whether the
air flow of the unit is blocked or whether the ambient temperature is too
high. Return to repair center. Check if spec and quantity of batteries are
meet requirements. Replace the fan. 1. Reduce the connected load. 2. Return to
repair center
Return to repair center.
Restart the unit, if the error happens again, please return to repair center.
Reduce the number of PV modules in series.
30
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>