Altronix MaxFit7F8AP Fused Access Power Controller Kits Installation Guide
- June 3, 2024
- Altronix
Table of Contents
MaxFit7F8AP Fused Access Power Controller Kits
Installation Guide
MaxFit7F8AP Fused Access Power Controller Kits
Fused Access Power Controller Kits
Models Include:
MaxFit7F8AP
8 Door Kit with Fused Outputs
The fully assembled kit includes:
– One (1) eFlow104NB – Power Supply/Charger
– One (1) ACM8 – Fuse Protected Access Power Controller
– One (1) PD8UL – Fuse Protected Power Distribution Module
– BC750 enclosure
MaxFit7F16AP
16 Door Kit with Fused Outputs
The fully assembled kit includes:
– One (1) eFlow104NB – Power Supply/Charger
– Two (2) ACM8 – Fuse Protected Access Power Controllers
– One (1) PD16W – Fuse Protected Power Distribution Module
– BC750 enclosure
MaxFit7F8APS
8 Door Kit with Fused Outputs
The fully assembled kit includes:
– One (1) eFlow104NB – Power Supply/Charger
– One (1) ACM8 – Fuse Protected Access Power Controller
– One (1) PDS8 – Dual Input Fuse Protected Power Distribution Module
– One (1) VR6 – Voltage Regulator
– BC750 enclosure
MaxFit7F16APS
16 Door Kit with Fused Outputs
The fully assembled kit includes:
– One (1) eFlow104NB – Power Supply/Charger
– Two (2) ACMS8 – Dual Input Fuse Protected Access Power Controllers
– One (1) VR6 – Voltage Regulator
– One (1) PD16W – Fuse Protected Power Distribution Module.
– BC750 enclosure
Installation Guide
More than just power. TM
Rev. MFKF_083019 Installing Company: ____
Service Rep. Name: __
Address: ____
Phone #: __
Overview:
Altronix fused Access Power Controller kits distribute and switch power to
access control systems and accessories. They convert a 120VAC 60Hz input into
eight (8) or sixteen (16) independently controlled 12VDC or 24VDC fuse-
protected outputs. These Fail-Safe/Fail-Secure power outputs may be converted
to dry-form “C” contacts. Relays are activated by an open collector sink or
normally open (NO) dry trigger input from an Access Control System, Keypad,
Push Button, REX PIR, etc. Units will route power to a variety of access
control hardware devices including Mag Locks, Electric Strikes, Magnetic Door
Holders, etc. The FACP Interface enables Emergency Egress, and Alarm
Monitoring, or may be used to trigger other auxiliary devices. The fire alarm
disconnect feature is individually selectable for any or all of the eight (8)
Fail-Safe/Fail-Secure power outputs. Additional fuse-protected outputs provide
power for connected devices.
Configuration Chart:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA
70/ANSI, and with all local codes and authorities having jurisdiction.
The product is intended for indoor use only.
-
Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level, and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8).
-
Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Fig. 2-5, pg. 3-6). Use 14 AWG or larger for all power connections. Secure green wire leads to earth ground. Keep power-limited wiring separate from non-power-limited wiring. Minimum 0.25″ spacing must be provided (Fig. 2-5, pg. 3-6).
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user-serviceable parts inside. Refer installation and servicing to qualified service personnel. -
Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in Fig. 1 desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2″ from the right side (Fig. 1, pg. 2). Connect the tamper switch wiring to the Access Control Panel input or the appropriate Enclosure UL Listed reporting device. To activate the alarm signal open the door of the enclosure.
-
Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB Edge of Enclosure and corresponding Sub-Assembly Installation Guides for ACM8, ACMS8, PDS8, VR6, PD8UL, and PD16W for further installation instructions.
MaxFit7F8AP: NEC Power-Limited Wiring Requirements
Power-limited and non-power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25″ away from any non-power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non-power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications the use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). The optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to the wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 2a).
Connect the red battery lead to the terminal marked [+ BAT] and to the
[positive (+)] terminal of the battery.
Connect the black battery lead to the terminal marked [BAT ] and to the
[negative ()] terminal of the battery.
Keep power-limited wiring separate from non-power-limited. Use minimum 0.25″
spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this
enclosure.
A UL-listed external battery enclosure must be used if using the 40AH or 65AH
batteries.
MaxFit7F16AP: NEC Power-Limited Wiring Requirements
Power-limited and non-power-limited circuit wiring must remain separated in
the cabinet. All power-limited circuit wiring must remain at least 0.25″ away
from any non-power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non-power-limited circuit wiring must enter and exit the
cabinet through different conduits. One such example of this is shown below.
Your specific application may require different conduit knockouts to be used.
Any conduit knockouts may be used. For power-limited applications use of
conduit is optional. All field wiring connections must be made employing
suitable gauge CM or FPL jacketed wire (or equivalent substitute). The
optional UL Listed battery enclosure must be mounted adjacent to the power
supply via Class 1 wiring methods. For Canadian installations use shielded
wiring for all connections. Note: Refer to wire handling drawing below for the
proper way to install the CM or FPL jacketed wire (Fig. 3a).
Connect the red battery lead to the terminal marked [+ BAT] and to the
[positive (+)] terminal of the battery.
Connect the black battery lead to the terminal marked [BAT ] and to the
[negative ()] terminal of the battery.
Keep power-limited wiring separate from non-power-limited. Use minimum 0.25″
spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this
enclosure.
A UL-listed external battery enclosure must be used if using the 40AH or 65AH
batteries.
MaxFit7F8APS: NEC Power-Limited Wiring Requirements
Power-limited and non-power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25″ away from any non-power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non-power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). The optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 4a).
Connect the red battery lead to the terminal marked [+ BAT] and to the
[positive (+)] terminal of the battery.
Connect the black battery lead to the terminal marked [BAT ] and to the
[negative ()] terminal of the battery.
Keep power-limited wiring separate from non-power-limited. Use minimum 0.25″
spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this
enclosure.
A UL-listed external battery enclosure must be used if using the 40AH or 65AH
batteries.
MaxFit7F16APS: NEC Power-Limited Wiring Requirements
Power-limited and non-power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25″ away from any non-power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications the use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). The optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to the wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 5a).
Connect the red battery lead to the terminal marked [+ BAT] and to the
[positive (+)] terminal of the battery.
Connect the black battery lead to the terminal marked [BAT ] and to the
[negative ()] terminal of the battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25″
spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this
enclosure.
A UL-listed external battery enclosure must be used if using the 40AH or 65AH
batteries.
eFlow Power Supply/Chargers can be Controlled and Monitored while Reporting
Power/Diagnostics from Anywhere over the Network…
LINQ2 – Network Communication Module
LINQ2 provides remote IP access to real-time data from eFlow power
supply/chargers to help keep systems up and running at optimal levels. It
facilitates fast and easy installation and set-up, minimizes system downtime,
and eliminates unnecessary service calls, which helps reduce the Total Cost of
Ownership (TCO) – as well as creates a new source of Recurring Monthly Revenue
(RMR).
Features:
– UL is Listed in the U.S. and Canada.
– Local or remote control of up to (2) two Altronix eFlow power output(s) via
LAN and/or WAN.
– Monitor real-time diagnostics: DC output voltage, output current, AC &
battery status/service, input trigger state change, output state change, and
unit temperature.
– Access control and user management: Restrict read/write, Restrict users to
specific resources
– Two (2) integral network controlled Form “C” Relays.
– Three (3) programmable input triggers: Control relays and power supplies via
external hardware sources.
– Email and Windows Dashboard notifications
– Event log tracks history.
– Secure Socket Layer (SSL).
– Programmable via USB or web browser
– includes operating software and 6 ft. USB cable.
LINQ2 Mounts Inside any MaxFit Enclosure
MaxFit Enclosure Dimensions (H x W x D approximate):
20.5″ x 16.5″ x 6.25″ (520.7mm x 419.1mm x 158.8mm)
Altronix is not responsible for any typographical errors.
Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056
website: www.altronix.com
e-mail: info@altronix.com
Lifetime Warranty
IIMaxFit Kits Fused
K108U
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>