Autonics ATS11-21D W 38 X H 42 mm Analog Timers Instruction Manual
- June 10, 2024
- Autonics
Table of Contents
- Autonics ATS11-21D W 38 X H 42 mm Analog Timers
- Product Information
- Model Number
- Safety Considerations
- Cautions during Use
- Product Components
- Ordering Information
- Dimensions
- Product Usage Instructions
- Safety Considerations
- ATS
- Dimensions
- Unit Descriptions
- Connections
- Specifications
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Autonics ATS11-21D W 38 X H 42 mm Analog Timers
Product Information
Transparent Guide ATS Series
Model Number
TCD210139AB
The Transparent Guide ATS Series is a timing device that can be used in various applications including nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc. The device comes with a fail-safe feature that needs to be installed when using it with machinery that may cause serious injury or substantial economic loss. The device has multiple output operation modes that differ depending on each model.
Safety Considerations
-
Warning: Failure to follow instructions may
result in serious injury or death. -
A fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss.
-
Do not use the unit in a place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
-
Install on a device panel to use.
-
Do not connect, repair, or inspect the unit while connected to a power source.
-
Check ‘Connections’ before wiring.
-
Do not disassemble or modify the unit.
Cautions during Use
- Use the unit within the rated specifications.
- Use a dry cloth to clean the unit, and do not use water or organic solvent.
- Keep the product away from the metal chip, dust, and wire residue which flow into the unit.
Product Components
The product components are sold separately and include a bracket, panel cut- out, and a dial for time setting.
Ordering Information
For selecting the specified model, follow the Autonics website. The actual product does not support all combinations. The ordering information includes plug type (8 or 11-pin plug), time range (0.1 to 1 or 0.3 to 3), power supply (12 VDC, 24 VAC 50/60 Hz, 24 VDC, or 100-240 VAC 50/60 Hz, 24-240 VDC), and output (Time limit DPDT (2c), Time limit SPDT (1c) + Instantaneous SPDT (1c), Time limit DPDT (2c), or Time limit SPDT (1c) + Instantaneous SPDT (1c)).
Dimensions
The device dimensions are 70mm x 13.5mm x 38.5mm.
Product Usage Instructions
- Install the fail-safe device when using the unit with machinery that may cause serious injury or substantial economic loss.
- Do not use the unit in a place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
- Install the device on a device panel.
- Do not connect, repair, or inspect the unit while connected to a power source.
- Check ‘Connections’ before wiring.
- Do not disassemble or modify the unit.
- Use the unit within the rated specifications.
- Use a dry cloth to clean the unit, and do not use water or organic solvent.
- Keep the product away from the metal chips, dust, and wire residue which flow into the unit.
- Follow the Autonics website to select the specified model.
- Install the product components including the bracket, panel cut-out, and dial for the time setting.
- Refer to the manual for the detailed timing chart for operation output mode as it differs depending on each model.
Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before using
the product. For your safety, read and follow the below safety considerations
before using. For your safety, read and follow the considerations written in
the instruction manual, other manuals, and the Autonics website. Keep this
instruction manual in a place where you can find it easily. The
specifications, dimensions, etc. are subject to change without notice for
product improvement. Some models may be discontinued without notice. Follow
the Autonics website for the latest information.
Safety Considerations
- Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
- The symbol indicates caution due to special circumstances in which hazards may occur.
Warning Failure to follow instructions may result in serious injury or death.
- A fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.) Failure to follow this instruction may result in personal injury, economic loss or fire.
- Do not use the unit in a place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present. Failure to follow this instruction may result in an explosion or fire.
- Install on a device panel to use. Failure to follow this instruction may result in fire or electric shock.
- Do not connect, repair, or inspect the unit while connected to a power source. Failure to follow this instruction may result in fire or electric shock.
- Check ‘Connections’ before wiring. Failure to follow this instruction may result in fire.
- Do not disassemble or modify the unit. Failure to follow this instruction may result in fire or electric shock.
Caution Failure to follow instructions may result in injury or product damage.
- Use the unit within the rated specifications. Failure to follow this instruction may result in fire or product damage.
- Use a dry cloth to clean the unit, and do not use water or organic solvent. Failure to follow this instruction may result in fire or electric shock.
- Keep the product away from the metal chips, dust, and wire residue which flow into the unit. Failure to follow this instruction may result in fire or product damage.
Cautions during Use
- Follow instructions in ‘Cautions during Use’.
- Otherwise, it may cause unexpected accidents.
- In the case of DC power input, connect it to the designated power input terminals considering the polarity.
- The power supply should be insulated and limited voltage/current or Class2, SELV power supply device.
- When applying the power to the timer, apply the rated power at the moment by switch and relay, etc. Otherwise, it may cause malfunction.
- When supplying or turning off the power, use a switch or etc. to avoid chattering.
- Install a power switch or circuit breaker in an easily accessible place for supplying or disconnecting the power.
- In order to block peripheral current, use an isolation transformer in which of the second part is not grounded to supply power to the external input device.
- In order to avoid leakage current flowing, connect resistance and condenser like below Otherwise, it may cause malfunction.
- Do not connect two or more timers with only one input contact or transistor simultaneously.
- After turning off the power, changing the time range, etc.
- Keep away from high voltage lines or power lines to prevent inductive noise. In the case of installing the power line and input signal line closely, use line filter or varistor at the power line and shielded wire at the input signal line. Do not use equipment that generates strong magnetic force or high-frequency noise.
- This unit may be used in the following environments.
- Indoors (in the environment condition rated in ‘Specifications’)
- Altitude max. 2,000 m
- Pollution degree 2
- Installation category II
Ordering Information
This is only for reference, the actual product does not support all
combinations.
For selecting the specified model, follow the Autonics website
ATS
-
Plug type
8: 8-pin plug 11: 11-pin plug -
Power supply
1: 12 VDC
2: 24 VAC 50 / 60 Hz, 24 VDC
4: 100 – 240 VAC 50 / 60 Hz, 24 – 240 VDC -
Time range
1: 0.1 to 1
3: 0.3 to 3 -
Output
No mark: Time limit DPDT (2c),
Time limit SPDT (1c) + Instantaneous SPDT (1c)
D: Time limit DPDT (2c)
E: Time limit SPDT (1c) + Instantaneous SPDT (1c)
Product Components
- Product (+ bracket)
- Instruction manual
Sold Separately
- 8-pin socket: PG-08, PS-08(N), PS-M8
- 11-pin socket: PG-11, PS-11(N)
Dimensions
- Unit: mm, For the detailed drawings, follow the Autonics website.
Bracket
Panel cut-out
Unit Descriptions
No. | Name |
---|---|
1 | Power indicator |
2 | Time limit output indicator |
3 | Output operation mode display part |
4 | Output operation mode setting switch |
5 | Time range display part |
6 | Time range setting switch |
7 | Dial for the time setting |
Output Operation Mode
For the detailed timing chart for operation output mode, refer to the manual.
The output operation mode differs depending on each model.
ATS8
A | Power ON Delay |
---|---|
A1 | Power ON Delay 1 (One-shot output) |
B | Power ON Delay 2 |
F | Flicker (OFF Start) |
F1 | Flicker 1 (ON Start) |
I | Interval |
ATS11
A | Signal ON Delay |
---|---|
F | Flicker (OFF Start) |
F1 | Flicker 1 (ON Start) |
C | Signal OFF Delay |
D | Signal ON/OFF Delay |
I | Interval |
Time Range
Display part
| ****
Unit
| Range
---|---|---
ATS□-□1□| ATS□-□3□
1S| ****
SEC
| 0.1 to 1| 0.3 to 3
10S| 1 to 10| 3 to 30
1M| ****
MIN
| 0.1 to 1| 0.3 to 3
10M| 1 to 10| 3 to 30
1H| ****
HOUR
| 0.1 to 1| 0.3 to 3
10H| 1 to 10| 3 to 30
Connections
Caution
- Refer to the ‘specifications’ for checking the power supply and control output.
- The ATS11 model: Be sure to use terminal No. 2 as the common terminal to connect terminals No. 5, 6, and 7. Failure to follow this instruction may result in product malfunction.
ATS8
- Output operation mode: A, F
- Output operation mode: A1, B, F1, I
ATS11-□□D
ATS11-□□E
Specifications
Model | ATS8-□□□ | ATS11-□□D | ATS11-□□E |
---|---|---|---|
Function | Multi-Function Timer | ||
Return time | ≤ 100 ms | ||
Time operation | Power ON Start | Signal ON Start | |
Input | – | START, INHIBIT, RESET | |
Min. signal width | – | ≈ 50ms |
No-voltage input
| ****
–
| Short-circuit impedance: ≤ 1 kΩ
Short-circuit residual voltage: ≤ 0.5 VDCᜡ Open-circuit impedance: ≥ 100 kΩ
Control output| Relay
Contact type
| Time limit DPDT (2c), Instantaneous SPDT (1c) + Time limit SPDT (1c)| ****
Time limit DPDT (2c)
| Instantaneous SPDT (1c) + Time limit SPDT (1c)
Contact capacity
| 250 VACᜠ 3 A,
30 VDCᜡ 3 A
resistive load
| ****
250 VACᜠ 3 A, 24 VDCᜡ 3 A resistive load
Error
| Repeat: ≤ ± 0.2% ± 10 ms SET: ≤ ± 5% ± 50 ms
Voltage: ≤ ± 0.5%
Temp.: ≤ ± 2%
Approval| ᜢ ᜧ ᜫ
Unit weight (packaged)| ≈ 70 g (≈ 95 g)
Power supply
| ****
12 VDCᜡ ±10%
| 24 VACᜠ ±10%
50 / 60 Hz,
24 VDCᜡ ±10%
| 100 – 240 VACᜠ ±10%
50 / 60 Hz,
24 – 240 VDCᜡ ±10%
---|---|---|---
Power consumption| It depends on the plug type and output.
ATS8-□□□| DC: ≤ 1.5 W| AC: ≤ 4.5 VA DC: ≤ 2 W| AC: ≤ 4.2 VA DC: ≤ 2 W
ATS11-□□D| DC: ≤ 1 W| AC: ≤ 4 VA DC: ≤ 1.5 W| AC: ≤ 3.5 VA DC: ≤ 2 W
ATS11-□□E| DC: ≤ 1.5 W| AC: ≤ 4.5 VA DC: ≤ 2 W| AC: ≤ 4.2 VA DC: ≤ 2 W
Insulation resistive| ≥ 100 MΩ (500 VDCᜡ megger)
Dielectric strength| 2,000 VACᜠ at 50 / 60 Hz for 1 min
Noise immunity| It depends on the power supply.
ATS□-1□□| ****
± 500 V square-wave noise by noise simulator (pulse width 1 ㎲)
ATS□-2□□
ATS□-4□□| ± 2kV square-wave noise by noise simulator (pulse width 1 ㎲)
Vibration| 0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1
min) in each X, Y, Z direction for 1 hour
Vibration (malfunction)| 0.5 mm double amplitude at a frequency of 10 to
55 Hz (for 1 min) in each X,
Y, Z direction for 10 min
Shock| 300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)| 100 m/s2 (≈ 10 G) In each X, Y, Z direction for 3
times
Relay life cycle| Mechanical: ≥ 10,000,000 operations
Electrical:≥ 100,000 operations (250 VACᜠ 3 A resistive load)
Ambient temperature| -10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or
condensation)
Ambient humidity| 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or
condensation)
18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002 www.autonics.com | +82-2-2048-1577 | sales@autonics.com