Altronix T3M77XK3 /Mercury Wired Kits Installation Guide
- June 3, 2024
- Altronix
Table of Contents
Access & Power Integration
Altronix/Mercury Wired Kits
T3M77XK3 /Mercury Wired Kits
Models Include:
16 Door Kits with Fused Outputs:
T3M77XK1
Accommodates one (1) Intelligent Dual Reader Controller and seven (7) Dual
Reader Interface Modules.
T3M77XK2
Accommodates one (1) Intelligent Dual Reader Controller and seven (7) Dual
Reader Interface Modules.
T3M77XK3
Accommodates up to eight (8) Dual Reader Interface Modules.
Each fully assembled kit includes:
– Trove3 enclosure with TM3 Altronix/Mercury/LenelS2 backplane
– Two (2) eFlow104NB – Power Supply/Chargers
– Two (2) ACMS8 – Dual Input/Output Fuse Protected
Access Power Controllers
– Two (2) VR6 – Voltage Regulators
– Two (2) PDS8 – Dual Input/Output Fuse Protected Power Distribution Modules
– One (1) Rocker Switch Bracket with Two (2) Rocker Switches (Not evaluated by
UL)
– Wire harnesses and finger duct
16 Door Kits with PTC Outputs:
T3M77XK1D
Accommodates one (1) Intelligent Dual Reader Controller and seven (7) Dual
Reader Interface Modules.
T3M77XK2D
Accommodates one (1) Intelligent Dual Reader Controller and seven (7) Dual
Reader Interface Modules.
T3M77XK3D
Accommodates up to eight (8) Dual Reader Interface Modules.
Each fully assembled kit includes:
– Trove3 enclosure with TM3 Altronix/Mercury/LenelS2 backplane
– Two (2) eFlow104NB – Power Supply/Chargers
– Two (2) ACMS8CB – Dual Input/Output PTC Protected
Access Power Controllers
– Two (2) VR6 – Voltage Regulators
– Two (2) PDS8CB – Dual Input/Output PTC Protected Power Distribution Modules
– One (1) Rocker Switch Bracket with Two (2) Rocker Switches (Not evaluated by
UL)
– Wire harnesses and finger duct
All components of this Trove kit are UL Listed as sub-assemblies.
Please refer to the included corresponding Sub-Assembly Installation Guides
for further information.
Installation Guide
All registered trademarks are property of their respective owners.
Rev. T3M77XK012121
Installing Company: _____ Service Rep. Name:
Address: __ Phone #:
Overview:
Altronix Trove Plus kits are pre-wired and pre-assembled and consist of Trove3M3 enclosure/backplane with factory-installed Altronix power supply/charger(s) and sub-assemblies, wire harnesses, and finger duct.
Configuration Chart:
Hardware and Accessories:
- Two (2) tamper switches (Altronix Model TS112 or equivalent).
- Cam lock.
- Battery leads.
Mechanical:
- 16 Gauge enclosure with ample knockouts for convenient access.
- Enclosure Dimensions (H x W x D): 36.12” x 30.125” x 7.06” (917.5mm x 768.1mm x 179.3mm).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA
70/ANSI, and with all local codes and authorities having jurisdiction.
The product is intended for indoor use only.
-
Remove the backplane from the enclosure. Do not discard hardware.
-
Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level, and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.
-
Mount included UL Listed tamper switches (Altronix Model TS112 or equivalent) in the desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect the tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate the alarm signal open the door of the enclosure.
-
Mount Mercury boards to the backplane, refer to pg. 3, 4.
-
Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB and corresponding Sub-Assembly Installation Guides for PDS8(CB) and ACMS8(CB) for
further installation instructions. -
Position Lenel/Mercury access controller module over corresponding spacers and depress it onto snap-on spacers (Fig. 2-4, pg. 3-5).
-
Mount the backplane to the enclosure with hardware.
T3M77XK1 (T3M77XK1D) Configuration:
- Position the access controller module over the corresponding spacers and depress it onto snap-on spacers (Fig. 2, pg. 3).
- Mount the backplane to the enclosure with hardware.
Access Controller Position Chart for the Following Models:
LenelS2 / Mercury Access Controller | Pem Mounting |
---|---|
LNL-2220 / LP1502 | A |
LNL-1320 / MR52 | B C D E F G H |
T3M77XK2 (T3M77XK2D) Configuration:
- Position the access controller module over the corresponding spacers and depress it onto snap-on spacers (Fig. 3, pg. 4).
- Mount the backplane to the enclosure with hardware.
Access Controller Position Chart for the Following Models:
LenelS2 / Mercury Access Controller | Pem Mounting |
---|---|
LNL-3300 / LP2500 | A |
LNL-1320 / MR52 | B C D E F G H |
T3M77XK3 (T3M77XK3D) Configuration:
- Position the access controller module over the corresponding spacers and depress it onto snap-on spacers (Fig. 4, pg. 5).
- Mount the backplane to the enclosure with hardware.
Access Controller Position Chart for the Following Models:
LenelS2 / Mercury Access Controller | Pem Mounting |
---|---|
LNL-1320 / MR52 | A B C D E F G |
eFlow Power Supply/Chargers can be Controlled and Monitored while Reporting Power/Diagnostics from Anywhere over the Network…
LINQ2 – Network Communication Module
LINQ2 provides remote IP access to real-time data from eFlow power
supply/chargers to help keep systems up and running at optimal levels. It
facilitates fast and easy installation and set-up, minimizes system downtime,
and eliminates unnecessary service calls, which helps reduce the Total Cost of
Ownership (TCO) – as well as creates a new source of Recurring Monthly Revenue
(RMR).
Features:
- UL is Listed in the U.S. and Canada.
- Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN.
- Monitor real-time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change, and unit temperature.
- Access control and user management: Restrict read/write, Restrict users to specific resources
- Two (2) integral network controlled Form “C” Relays.
- Three (3) programmable input triggers: Control relays and power supplies via external hardware sources.
- Email and Windows Dashboard notifications
- The event log tracks history.
- Secure Socket Layer (SSL).
- Programmable via USB or web browser – includes operating software and 6 ft. USB cable.
LINQ2 Mounts Inside any Trove Enclosure
Altronix is not responsible for any typographical errors.