Miele PRI318 G Rotary Ironer Instruction Manual

June 1, 2024
Miele

Miele PRI318 G Rotary Ironer

Miele PRI318 G Rotary Ironer

Always read the operating instructions before
setting up, installing and commissioning the machine. This prevents both personal injury and damage to the machine.

Installation notes

Installation requirements

The flatwork ironer must only be set up by a Miele authorised and trained service technician or an authorised dealer.

  • This flatwork ironer must be installed in accordance with all relevant regulations and standards. Local energy supplier regulations must also be observed.
  • This flatwork ironer must only be operated in a room that has sufficient ventilation and which is frost-free.

Operating conditions

In general, the operating conditions of DIN 60204 and EN 60204-1 apply.

  • Ambient temperature: +5 °C to +40 °C
  • Humidity: 10 % to 85 %
  • At +21 °C ambient temperature, the maximum permissible relative humidity is 70 %.
  • Maximum height above sea level of location site: 1000 m

The ironer must not be operated in the same room as dry-cleaning equipment using perchloroethylene or solvents containing CFCs.
Collector motor sparking may convert solvent vapours into hydrochloric acid which can lead to consequential damage.
Ensure adequate ventilation is present in the room in which the ironer is installed whilst it is being used.

Floor anchoring

Measures to secure the ironer in place on the floor are essential.

The ironer must be secured to the floor after installation using the plugs and screws supplied.

The fittings supplied are for bolting the machine to a concrete floor. For other types of flooring, please purchase suitable fastening materials separately.

Electrical connection

The electrical connection must be carried out by a qualified electrician who must ensure that all electrical work is carried out in accordance with applicable regulations and standards.

It is recommended to connect the ironer to the electrical supply via a suitably rated plug and socket.

The electrical connection and wiring diagram are located behind the mounting flap of the right-hand side column.

The required voltage, rated load and external fuse rating can be found on the data plate on the flatwork ironer.
Connection to a supply voltage other than the one quoted on the data plate can lead to functional faults and damage to the flatwork ironer.
Before connecting the flatwork ironer to the electricity supply, please ensure that the mains supply voltage complies with the values given on the data plate.

The electrical equipment of the flatwork ironer complies with standards IEC 61000-3-12, IEC/EN 60335-1, IEC/EN 60335-2-44, EN ISO 10472-1 and EN ISO 10472-5.

For ease of servicing and maintenance the ironer should be installed with a suitably rated plug and socket.

In the case of unfavourable electrical conditions, the flatwork ironer may lead to interfering voltage fluctuations. If the mains impedance is greater than 0.265 ohm at the connection point to the public mains network, additional measures may be required before the appliance can be properly operated using this connection. The mains impedance can be requested from the local power supply company if necessary.

The plug connector or isolator switch should be easily accessible at all times.

If the flatwork ironer is disconnected from the electricity supply, the disconnector must be lockable or the point of disconnection must be monitored at all times.

If it is necessary to install a residual current device (RCD) in accordance with the local regulations, a type-A residual current device can be used.

If the machine is hard wired, an all-pole means of deactivation must be installed. Switches with a minimum contact gap greater than 3 mm are suitable disconnectors. These include circuit breakers, fuses and contactors (VDE 0660).

Gas connection

The gas connection may only be carried out by a registered installation technician in accordance with the applicable national regulations. In addition, the regulations of the local gas supply company must be observed.
Service work on gas appliances may only be carried out by suitably qualified persons in accordance with all applicable safety regulations. Before any service work is commenced on the appliance, the machine must immediately be disconnected from the gas mains.

Follow the installation instructions for the gas connection.

The gas heating is set as standard in accordance with the ironer’s gas rating (see the data plate on the rear of the machine).

If the gas type needs to be changed, please request the appropriate conversion kit from the Miele Customer Service Department. When doing so, please have ready the information on the type of ironer, the appliance number, gas type, gas group, gas connection pressure and country in which the appliance is installed.

Danger due to incorrectly carried out service and repair work.
There is a risk of serious damage, injury and even death if service and repair work is carried out incorrectly.
Never carry out repairs on gas appliances yourself.
If repair work is required, immediately contact the Miele Customer Service Department or an authorised dealer.

Waste gas duct

The connector for the waste gas duct (Ø 120 mm) can be found on the back of the ironer next to the right-hand side column.

Follow the installation instructions.

Make sure that a sufficient air quantity is fed to the room in which the ironer is installed (e.g. non-lockable ventilation openings).

Pipe length and pipe diameter

Determining the total pipe lengths and pipe diameters
Prior to execution, a decision must be made as to whether flexible piping or metal piping with a round or square cross-section should be installed.

Tip: Keep the pipeline as short as possible. If feasible, the pipeline should not have any sharp bends as this impairs the air flow rate.

Ensure adequate ventilation of the room in which the ironer is installed whilst it is being used (e.g. by means of ventilation openings that cannot be closed).

Fire hazard due to hot exhaust air.
The hot exhaust air can ignite ducting made from non-heat-resistant materials.
Use only heat-resistant materials for the exhaust ducting.

Model **Maximum exhaust air temperature (approx.)***
PRI318 G 133 °C
PRI418 G 135 °C
PRI421 G 130 °C
  • Data from test diagrams
    In upward exhaust ducting systems, a condensate drain must be fitted at the lowest point.
    The condensate must be drained via a water collection tray or a floor drain.

If the exhaust from multiple appliances is to be ducted into a combined line, a non-return device must be installed in each separate line to prevent backflow.

Tip: To make subsequent cleaning of the pipes easier, cleaning flaps should be fitted to elbows wherever possible.

Fire hazard due to fluff deposits.
Fluff that settles in the ducting may be ignited by the hot exhaust air.
Remove fluff deposits from the ducting and the exit point to the outside on a regular basis.

Substitute pipe lengths

Type of elbow Substitute pipe lengths

PRI318/418/421 G (gas-heated)


| 90° elbow r = 2 d| 1.5 m
45° elbow r = 2 d| 0.85 m


| 90° elbow r = d| 2.55 m
45° elbow r = d| 1.4 m


| 90° corrugated pipe elbow r = 2 d| 2.0 m
45° corrugated pipe elbow r = 2 d|


| 90° segmented bend (3 welded seams) r = 2 d| 1.25 m


| 90° elbow Westfalen ducting
r = 2 d r = 4 d| 0.9 m
1.2 m
45° elbow Westfalen ducting
r = 2 d r = 4 d| 0.6 m
0.75 m

Permissible total pipe lengths

Minimum internal pipe diameter for metal pipes| Maximum permissible total pipe length for exhaust air
---|---
PRI318/418/421 G (gas-heated)
70 mm|
80 mm|
90 mm|
100 mm|
110 mm|
120 mm| 10 m
130 mm| 14.5 m
150 mm| 30 m
180 mm| 75.5 m
200 mm|

Ducting requirements

Important information about ducting:

  • When connecting the ducting to the exhaust connection on an appliance, particular care must be taken to make sure the connection is secure and air-tight.
  • The ducting must not be channelled into a chimney or flue already in use for any gas-, coal- or oil-burning installation.
  • The warm and moist exhaust air is to be conducted to the outside or through suitable ventilation ducting along the shortest path possible.
  • Due to the higher air flow rates, the exhaust ducting must be laid in such a way that air flow is not hindered (few bends, short pipelines, well-made connections and transitions checked for air-tightness). Filters and louvres must not be fitted in the ducting.
  • The end of ducting leading outside should be protected against the elements, e.g. with a downward-facing 90° elbow.

Take these safety precautions if you smell gas

  • Extinguish any open flames and put out any cigarettes immediately.

  • Do not carry out any actions which produce electrical sparks. Do not operate any light switches, device power switches or bells. Do not pull any electrical plugs from sockets.
    Do not use your telephone or mobile phone.

  • Immediately open all windows and doors and ensure adequate ventilation.

  • Close the gas line shut-off valves.

  • If you smell gas in a room, under no circumstances should you enter that room carrying an open flame.

  • Do not strike any matches or ignite a cigarette lighter.

  • Contact the relevant gas supply company

Before completing commissioning, maintenance, conversion and repair work, all gasconducting components – from the manual shut-off valve to the burner jet – must be checked for leaks.

Particular attention must be paid to the measuring stubs on the gas valve and the burner. Checks must be performed when the burner is both switched on and switched off.

During installation, the technical regulations for gas installations as well as national and regional building regulations, fire regulations, and specifications from the relevant gas supply companies must be adhered to.

UK: Gas Safe, and BS 8446:2005
When planning a gas-heated system, contact the relevant gas supply company and a building regulations inspector in good time.

What needs to be observed before commissioning

When ordering gas-heated machines, please specify the gas family, gas group, and connection pressure at the site where the machine is to be set up.

Setup site

Gas-heated machines must not be operated in a room where cleaning machines operate with solvents containing perchloroethylene or CFCs. During combustion, any vapours that are emitted will break down into hydrochloric acid, leading to consequential damage affecting laundry and the machine. Air exchange must not take place if machines are set up in separate rooms.

Rooms with fuel-burning installations must be adequately aerated and ventilated. Any gasheated appliance must be considered to be a fuel-burning installation (regardless of its gas flow rate).

If liquid gas-heated machines are being set up below ground level, the operator must provide the system with the necessary aeration and forced ventilation equipment in accordance with technical regulations for liquid gas.

If no low pressure occurs when a full fire is burning in all fuel-burning installations, this means that the room ventilation is working properly, even if the exhaust gases from the installations are being extracted mechanically. This ensures that the gas is being combusted correctly and that the exhaust gases are being evacuated completely.

It must not be possible to seal off aeration and ventilation openings.

Before completing commissioning, maintenance, conversion, and repair work, all gas-conducting components – from the manual shut-off valve to the burner jet – must be checked for leaks.
Gas may escape from leaks.
Particular attention must be paid to the measurement connections on the gas valve.
Checks must be performed when the burner is both switched on and switched off.

  • Installing thermal shut-off equipment on site is recommended.
  • If gas-heated appliances are publicly accessible, it is also necessary to check whether a gas flow monitor needs to be used.

Required flow rate

Appliance type| Rated heat load (Hi)| Natural gas (LL)| Natural gas (E)| Liquid gas
---|---|---|---|---
PRI318| 22 kW| 2.71 m³/h| 2.33 m³/h| 1.74 kg/h
PRI418| 28 kW| 3.44 m³/h| 2.97 m³/h| 2.21 kg/h
PRI421| 30 kW| 3.69 m³/h| 3.18 m³/h| 2.37 kg/h

The connected load is based on the following calorific values:

  • Natural gas LL (G 25): 29.25 MJ/m³ (Hi)
  • Natural gas E (G 20): 34.02 MJ/m³ (Hi)
  • Liquid gas (G 30): 45.65 MJ/m³ (Hi)

Natural gas

Natural gas Length of gas line
3 m 5 m
Internal dia- meter Maximum flow rate
¾” (20 mm) 4.7 m³/h

m³/h
1″ (25 mm)| 8.6 m³/h| 6.9 m³/h| 4.8 m³/h| 3.1 m³/h| 2.4 m³/h| 1.9 m³/h| 0.9 m³/h
1 ¼” (32 mm)| 16.0 m³/h| 12.4 m³/h| 8.7 m³/h| 6.2 m³/h| 5.0 m³/h| 3.8 m³/h| 2.4 m³/h
1 ½” (40 mm)| 26.5 m³/h| 20.5 m³/h| 14.5 m³/h| 10.3 m³/h| 8.4 m³/h| 6.5 m³/h| 4.0 m³/h
2″ (50 mm)| 60.0 m³/h| 47.0 m³/h| 33.0 m³/h| 23.0 m³/h| 19.0 m³/h| 15.0 m³/h| 10.0 m³/h

Liquid gas

Liquid gas Length of gas line
5 m
Internal dia- meter Maximum flow rate
10 mm
12 mm
16 mm
22 mm
27 mm

Exhaust gas evacuation ducts

The gas-heated flatwork ironers are type B22 gas fuel-burning installations without flow safeguarding equipment, and with a fan behind the heater.

  • The mixtures of exhaust gas and air that are emitted by gas-heated flatwork ironers must be evacuated through a suitable chimney and out into the atmosphere via the roof.
  • Exhaust air/gas evacuation ducts must be kept as short as possible and must rise vertically up to the vent flue.
  • Only materials that are resistant to heat and sooting may be used.
  • A condensate drain must be placed at the lowest point of the exhaust air/exhaust gas line. The condensate must be drained via a water collection tray or a floor drain positioned in an appropriate location. Supports and louvres must not be fitted. The exhaust air/exhaust gas line must be installed in a way that ensures it is leak-tight.

See the guidelines for approving exhaust gas systems containing low- temperature exhaust gases (issued by the German Institute for Structural Engineering in Berlin).

Exceptions

  1. If it is not possible for evacuation to take place through a single duct and multiple exhaust gas/air ducts are in use, appropriate measures must be put in place to ensure that, when an appliance is being operated, the exhaust gas/air mixture is not able to enter the room via the exhaust ducts of other appliances. Examples of appropriate measures include baffles and merged lines with a shape that is favorable for the flow. It is important to ensure that high pressure cannot arise in the exhaust gas/air ducts of the appliances that are not in operation. Appliances with a fan may not be connected to the same vent flue as appliances without a fan.

  2. In exceptional cases, the exhaust gas/air mixture may be evacuated through the exterior wall (in accordance with Section 38, paragraph 4, sentence 3 of Germany’s Model Building Code (MBO)).
    However, doing so must not give rise to any risks or unreasonable inconvenience.

  3. When using a combined line, the exhaust air evacuation ducts of the individual appliances must be directed into the shared line laterally and in a way that is favorable for the flow. The cross-section of the vent flue must not be smaller than the cross-section of the combined line. The combined line must be kept as short as possible and must rise vertically up to the vent flue. A condensate drain must be placed at the lowest point. The condensate must be drained as described above.

All exceptional cases, and particularly those where a combined line is being installed, require special permission from the relevant building regulations inspector supervisor’s office.

Exhaust air and supply air ducting cross-sections

Model Cross-sections of vent outlets
PRI 318/418/421 gas 113 cm²

Exhaust gas values

| PRI318| PRI418| PRI421
---|---|---|---
Exhaust gas emissions| 160 g/s| 101 g/s| 122 g/s
Temperature
| 120 °C| 130 °C| 130 °C
CO2 content*| 0.6 %| 1.0 %| 1.0 %
Fan power**| 530 m³/h| 530 m³/h| 530 m³/h
Maximum permitted counter pressure| 200 Pa| 200 Pa| 200 Pa

  • Example value
    ** At 0 mbar counter pressure

Room ventilation opening for air intake from the setup room

The minimum dimension of the ventilation opening depends on the cross-section of the vent pipe.

Vent pipe Minimum dimension for ventilation opening
A
100 mm
100 mm
120 mm
120 mm
150 mm
150 mm
180 mm
180 mm
200 mm
200 mm
220 mm
220 mm
250 mm
250 mm
300 mm
300 mm

What needs to be observed during commissioning

Check that the points listed in section 1 (“What needs to be observed before commissioning”) have been taken into consideration. The following should be carried out in the given order when commissioning or converting the machine:

  1. Measure the connection pressure. The connection pressure must be within the ranges specified in EN 437 (see section “Country of destination and category”).

  2. Ask the gas supply company what the gas family, gas group and connection pressure are, and compare this information with the data specified on the machine (see the sticker at the rear).

  3. Check the factory-set jet pressure based on the sections “Country of destination and category”, “Settings with natural gas” and “Settings with liquid gas” and correct it if necessary.

  4. If the gas family, gas group or connection pressure is different, it must be converted as instructed in the section entitled “Connection and conversion instructions” and the sticker at the rear of the machine must be replaced.
    Set the jet pressure at the machine’s gas regulating valve (see “Settings with natural gas” or “Settings with liquid gas” section).
    If the gas family needs to be changed, please request the appropriate conversion kit from the Miele Customer Service Department. When doing so, please specify the product name and the machine number, as well as the gas family, gas group, gas connection pressure and country where the machine has been set up.

  5. Switch on all gas consumers that are present, including the installed appliance.

Connection and conversion instructions

Connection and conversion work must be performed by the Miele Customer Service Department or by an authorised dealer’s trained personnel.

The settings for gas-heated flatwork ironers are made at the factory in line with the gas specifications at the rear of the appliance.

Gas hose

The gas appliance must be connected using a corrugated metal hose assembly made from stainless steel in accordance with DIN 3384. Alternatively, a hose that complies with DIN EN 16617 may be used with connections in accordance with DIN 3384. When selecting the hose, the required flow rate must be taken into account. The relevant national regulations must also be observed.

Main connection

Main connection

Checking and adjusting the gas regulating valve

  • Remove the cap screws from the pressure regulators.
  • Loosen the locking bolts on the measuring stubs.
  • Carry out the measurement.
  • Tighten the locking bolts again after the measurement.
  • Check the connection pressure at the gas regulating valve V1 (see “Connection pressure and category” section).
  • Open the pressure regulator on gas regulating valve V1 as far as it will go.
  • Set the jet pressure at gas regulating valve V2 based on the adjustment values for natural gas or liquid gas specified below.

Burner setting

The respective diameters for jets and baffles are specified in the tables below together with the adjustment values.

Jets and baffles are included in the kit for converting natural gas to liquid gas.
Burner setting

  • Change the 2 jets.
  • Change the 2 baffles.

Danger due to gas escaping.
Gas lines and screw connections may leak after connection, adjustment and conversion work.
After connection, adjustment and conversion work, the gas lines, all screw connections (including those on the jets) and the locking bolts on the measuring stubs must be checked to ensure they are leak-tight. This check must be performed both while the appliance is at a standstill and while it is in operation.

Connection pressure and category

The gas-heated flatwork ironers are approved for the following countries, connection pressures and categories:

Country| Category| Connection pressure (natural gas)

DIN EN 437

| Connection pressure (liquid gas)

DIN EN 437

---|---|---|---
n
p| min
p| max
p| n
p| min
p| max
p
Great Britain (GB)| II2H3+| 20 mbar| 17 mbar| 25 mbar| 29 mbar| 20 mbar| 35 mbar (B)
37 mbar| 25 mbar| 45 mbar (P)
Ireland (IE)| II2H3+| 20 mbar| 17 mbar| 25 mbar| 29 mbar| 20 mbar| 35 mbar (B)
37 mbar| 25 mbar| 45 mbar (P)

With natural gas, if the connection pressure is less than 15 mbar, the gas supply company must be informed.

Settings with natural gas

Model| Rated heat load (Hi)| Jet diameter| Baffle Ø| Jet pressure
---|---|---|---|---
E, H| LL, L
PRI318| 22 kW| 2 x 3.0 mm| 30 mm| 8.6 mbar| 12.8 mbar
PRI418| 28 kW| 2 x 3.5 mm| 35 mm| 7.5 mbar| 11.2 mbar
PRI421| 30 kW| 2 x 3.5 mm| 35 mm| 8.6 mbar| 12.8 mbar

Settings with liquid gas 3B/P (30/50 mbar)

Model| Rated heat load (Hi)| Jet diameter| Baffle Ø| Jet pressure
---|---|---|---|---
PRI318| 22 kW| 2 x 1.7 mm| 25 mm| 29 mbar
PRI418| 28 kW| 2 x 1.95 mm| 30 mm| 28.5 mbar
PRI421| 30 kW| 2 x 2.05 mm| 30 mm| 27 mbar

Settings with liquid gas 3+ (without regulator)

Model| Rated heat load (Hi)| Jet diameter| Baffle Ø| Jet pressure
---|---|---|---|---
PRI318| 22 kW| 2 x 1.7 mm| 25 mm| Block regulator
PRI418| 28 kW| 2 x 1.95 mm| 30 mm
PRI421| 30 kW| 2 x 2.05 mm| 30 mm

PRI318 G (gas heating)

Dimensions

Dimensions quoted in millimeters
BWR
Laundry return feed kit
Optional feature which allows the laundry to be removed from the front once it has been ironed.Dimensions

Installation

Dimensions quoted in millimeters

  1. Electrical connection

  2. Electrical conduit
    For laying the electrical connection cable within the building structure.

  3. Vent connection

  4. Gas connection
    Installation
    Dimensions quoted in millimetres

  5. Electrical conduit
    For laying the electrical connection cable within the building structure.

  6. Vent connection

  7. Gas connection

  8. Drill hole/anchor point

Technical data

Voltage variants/electrical data

3 NAC 380–415 V, 50–60 Hz

Supply voltage 3NAC 380-415 V
Frequency 50–60 Hz
Power rating 1.0 kW
Required fuse rating (on site) 3 × 16 A
Connection cable, min. cross-section 5 x 1.5 mm²
Screw thread M25
Rated heat load 22 kW
--- ---
Connector on the appliance as per ISO 7-1 ½” male thread
Natural gas connection pressure (as per DIN EN 437) See installation

instructions
Threaded union required for natural gas (on site)| ½” female thread
Liquid gas connection pressure (as per DIN EN 437)| See installation instructions
Threaded union required for liquid gas (on site)| ½” female thread
Alternative: precision steel tube as per DIN 2391/DIN 2393 with smooth end (on site) Sleeve ½” x ⅜”, screw thread: ⅜” x DN 12| Min. length 40 mm, DN 12
Requirements for the gas hose| Corrugated metal hose assembly made from stainless steel in accordance with DIN 3384 or hose in accordance with DIN EN 16617 with connections as per DIN 3384
Diameter of vent connection| 120 mm
---|---
Maximum exhaust air temperature (approx.)| 133 °C
Fan power| 0.45 kW
Fan air output (0 bar)| 270 m³/h
Maximum permitted pressure loss| 200 Pa

Dimensions/weight

Overall machine width 2469 mm
Overall machine height 1110 mm
Overall machine depth 1377 mm
Height adjustment via screw feet 29 mm
Roller length 1750 mm
Roller diameter 300 mm
Largest removable part Heater plate
Width of largest removable part 440 mm
Height of largest removable part 242 mm
Depth of largest removable part 1096 mm
Packaging width 2576 mm
Packaging height 1388 mm
Packaging depth 1096 mm
Maximum gross volume 3918 l
Maximum gross weigh 501 kg
Maximum net weight 424 kg
Maximum floor load in operation 4160 N

Emissions data

Emission sound pressure level 60 dB(A) re 20 μPa
Heat dissipation rate to installation site 11.5 MJ/h

Floor anchoring

Required anchor points 4
DIN 571 wood screw (diameter x length) 8 mm x 50 mm
Rawl plugs (diameter x length) 10 mm x 50 mm

PRI418 G (gas heating)

Dimensions

Dimensions quoted in millimeter’s
BWR
Laundry return feed kit
Optional feature which allows the laundry to be removed from the front once it has been ironed.
Installation

Installation

Dimensions quoted in millimetres

  1. Electrical connection

  2. Electrical conduit
    For laying the electrical connection cable within the building structure.

  3. Vent connection

  4. Gas connection

    Dimensions quoted in millimetres

  5. Electrical conduit
    For laying the electrical connection cable within the building structure.

  6. Vent connection

  7. Gas connection

  8. Drill hole/anchor point
    Installation

Technical data

Voltage variants/electrical data

3 NAC 380–415 V, 50–60 Hz

Supply voltage 3NAC 380-415 V
Frequency 50–60 Hz
Power rating 1.0 kW
Required fuse rating (on site) 3 × 16 A
Connection cable, min. cross-section 5 x 1.5 mm²
Screw thread M25
Rated heat load 28 kW
--- ---
Connector on the appliance as per ISO 7-1 ½” male thread
Natural gas connection pressure (as per DIN EN 437) See installation

instructions
Threaded union required for natural gas (on site)| ½” female thread
Liquid gas connection pressure (as per DIN EN 437)| See installation instructions
Threaded union required for liquid gas (on site)| ½” female thread
Alternative: precision steel tube as per DIN 2391/DIN 2393 with smooth end (on site) Sleeve ½” x ⅜”, screw thread: ⅜” x DN 12| Min. length 40 mm, DN 12
Requirements for the gas hose| Corrugated metal hose assembly made from stainless steel in accordance with DIN 3384 or hose in accordance with DIN EN 16617 with connections as per DIN 3384
Diameter of vent connection| 120 mm
---|---
Maximum exhaust air temperature (approx.)| 135 °C
Fan power| 0.45 kW
Fan air output (0 bar)| 270 m³/h
Maximum permitted pressure loss| 200 Pa

Dimensions/weight

Overall machine width 2469 mm
Overall machine height 1110 mm
Overall machine depth 1441 mm
Height adjustment via screw feet 29 mm
Roller length 1750 mm
Roller diameter 365 mm
Largest removable part Heater plate
Width of largest removable part 500 mm
Height of largest removable part 270 mm
Depth of largest removable part 1855 mm
Packaging width 2576 mm
Packaging height 1388 mm
Packaging depth 1096 mm
Maximum gross volume 3918 l
Maximum gross weight 530 kg
Maximum net weight 453 kg
Maximum floor load in operation 4444 N

Emissions data

Emission sound pressure level 60 dB(A) re 20 μPa
Heat dissipation rate to installation site 13.7 MJ/h

Floor anchoring

Required anchor points 4
DIN 571 wood screw (diameter x length) 8 mm x 50 mm
Rawl plugs (diameter x length) 10 mm x 50 mm

Dimensions

Dimensions quoted in millimetres

BWR
Laundry return feed kit
Optional feature which allows the laundry to be removed from the front once it has been ironed.
Dimensions

Installation

Dimensions quoted in millimetres

  1. Electrical connection

  2. Electrical conduit
    For laying the electrical connection cable within the building structure.

  3. Vent connection

  4. Gas connection
    Installation
    Dimensions quoted in millimetres

  5. Electrical conduit
    For laying the electrical connection cable within the building structure.

  6. Vent connection

  7. Gas connection

  8. Drill hole/anchor point
    Installation

Technical data

Voltage variants/electrical data

3 NAC 380–415 V, 50–60 Hz

Supply voltage 3NAC 380-415 V
Frequency 50–60 Hz
Power rating 1.0 kW
Required fuse rating (on site) 3 × 16 A
Connection cable, min. cross-section 5 × 1,5 mm²
Screw thread M25
Rated heat load 30 kW
--- ---
Connector on the appliance as per ISO 7-1 ½” male thread
Natural gas connection pressure (as per DIN EN 437) See installation

instructions
Threaded union required for natural gas (on site)| ½” female thread
Liquid gas connection pressure (as per DIN EN 437)| See installation instructions
Threaded union required for liquid gas (on site)| ½” female thread
Alternative: precision steel tube as per DIN 2391/DIN 2393 with smooth end (on site) Sleeve ½” x ⅜”, screw thread: ⅜” x DN 12| Min. length 40 mm, DN 12
Requirements for the gas hose| Corrugated metal hose assembly made from stainless steel in accordance with DIN 3384 or hose in accordance with DIN EN 16617 with connections as per DIN 3384
Diameter of vent connection| 120 mm
---|---
Maximum exhaust air temperature (approx.)| 130 °C
Fan power| 0.45 kW
Fan air output (0 bar)| 270 m³/h
Maximum permitted pressure loss| 200 Pa

Dimensions/weight

Overall machine width 2759 mm
Overall machine height 1110 mm
Overall machine depth 1441 mm
Height adjustment via screw feet 29 mm
Roller length 2040 mm
Roller diameter 365 mm
Largest removable part Heater plate
Width of largest removable part 500 mm
Height of largest removable part 270 mm
Depth of largest removable part 1096 mm
Packaging width 2866 mm
Packaging height 1388 mm
Packaging depth 1096 mm
Maximum gross volume 4359 l
Maximum gross weight 556 kg
Maximum net weight 477 kg
Maximum floor load in operation 4679 N

Emissions data

Emission sound pressure level 60 dB(A) re 20 μPa
Heat dissipation rate to installation site 15.1 MJ/h

Floor anchoring

Required anchor points 4
DIN 571 wood screw (diameter x length) 8 mm x 50 mm
Rawl plugs (diameter x length) 10 mm x 50 mm

CUSTOMER SUPPORT

United Kingdom
Miele Co. Ltd., Fairacres, Marcham Road
Abingdon, Oxon, OX14 1TW
Professional Sales, Tel: 0845 365 6608
E-mail: professional@miele.co.uk
Internet: www.miele.co.uk/professional
Manufacturer: Miele & Cie. KG
Carl-Miele-Straße 29, 33332 Gütersloh, GermanyLogo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals