GEBERIT 33269 Mapress Stainless Steel Ball Valve Installation Guide

June 1, 2024
GEBERIT

GEBERIT logo

GEBERIT MAPRESS

GEBERIT 33269 Mapress Stainless Steel Ball Valve

INSTALLATION MANUAL

GEBERIT - KNOW HOW INSTALLED  GEBERIT -
Maintenance

Safety

About this document

This document describes the correct installation of the Geberit Mapress ball valve with actuator lever, flanged.

Target group
  • Geberit Mapress ball valves may be mounted only by skilled persons qualified in pipe installations.
  • Skilled persons must be conversant with and apply country-specific safety regulations.
Following information and instructions

Failure to observe the safety notes and instructions can lead to injuries.

  • Before commissioning, read through and take note of all safety notes and instructions in the installation manual.
  • Retain all safety notes and instructions for future use.
Intended use

Geberit Mapress ball valves may be used only as follows:

Table 1: Application purposes

| CrNiMo
EN 1.4401 / AISI-SAE 316
| CrNiMo
EN 1.4401 / AISI-SAE 316
| CuNi10Fe1.6Mn
EN 2.1972

---|---|---|---
Seal ring| CIIR, black| FKM, blue| CIIR, black
Heating water| | |
Cooling water without antifreeze agent| | |
Cooling water with antifreeze agent| | |
Remote network heating water ≤ 120°C| | |
Service water| | |
For treated water|

| |
Grey and black water with pH value 6.0| | |
Seawater| | |
Extinguishing water (wet)| | |
Compressed air (oil purity class 0-3)| | |
Compressed air (oil purity class 0-X)| | |

  Suitable
Not suitable

  1. Application range according to TI ‘Treated waters’

Any other use or a use extending beyond this is deemed to be improper. Geberit will not accept any liability for any resulting damage.

Symbols in the instructions
Symbol Meaning
CAUTION

Indicates a hazard which, if not avoided, can lead to injury.
| Refers to additional information.
| Indicates that a visual check must be carried out.
| Refers to correct usage.

Product description

Structure

Figure 1: Structure of Geberit Mapress ball valve

1 Actuator lever
2 Ball valve

Function

The Geberit Mapress ball valves close in a clockwise direction and open the opposite way. The rotation angle is 90°.

Figure 2: Geberit Mapress ball valve open

Figure 3: Geberit Mapress ball valve close

Technical data

Table 2: Dimensions

DNV| d
[mm]| L
[cm]| L1
[cm]| L2
[cm]| Z
[cm]
---|---|---|---|---|---
15| 15| 12.2| 5| 9.3| 4.1
15| 18| 12.2| 5| 9.3| 4.1
20| 22| 13.3| 5.6| 10.3 | 4.5
25| 28| 14.2| 6.6| 12.8| 4.8
32| 35| 17| 7.5| 12.8| 5.9
40| 42| 19.4| 8.5| 15.8| 6.7
50| 54| 22.1| 9.6| 15.8| 7.5
65| 76.1| 29.1| 13.5| 22.3| 9.2
80| 88.9| 33.3| 14.5| 35.8| 10.6
100| 108| 41.2| 17.7| 50| 13.1

Installation dimensions

It is essential to ensure that the minimum space requirements L2 are available for actuating the actuator lever before installing the Geberit Mapress ball valve. → See figure.

Table 3: Installation dimensions

d
[
mm]| Minimum space requirements L2
[
cm]
---|---
15| 9.3
18| 9.3
22| 10.3
28| 12.8
35| 12.8
42| 15.8
54| 15.8
76.1| 22.3
88.9| 35.8
108| 50

Installation

Pressing the Geberit Mapress ball valve

The Geberit Mapress ball valve does not influence the direction of flow of the medium. The ball valve can be installed in any direction of flow and in any installation position.

Prerequisite

– Minimum space requirements L2 are ensured.


1 Ensure that the Geberit Mapress ball valve is free of dust and foreign bodies. Clean with water or steam if required.


2 Press the connections. → See installation manual 965.739.00.0 ‘Processing Geberit Mapress system pipes’ and operating instructions of the pressing tools used.

Commissioning

Checking the function

The force may be much stronger when the actuator lever is actuated for the first time or if it has not been used for some time.


▶ Open and close the actuator lever (3x).


Result

✓ Ball valve is ready for operation

Checking the Geberit Mapress ball valve for tightness

CAUTION
Risk of scalding from leaking medium (hot water)
▶ Maintain safety distance.
▶ Wear protective equipment.


▶ Test the ball valve for tightness at the gland.


Result

✓ If the ball valve is leaky, tighten the gland more securely. → See “Tightening the gland”, page 18.

Tightening the gland

1 Close the ball valve.


2 Demount the actuator lever.


A gland that is tightened too securely will cause the actuator lever to be stiff.


3 Tighten gland to torque specified in Table 4.


4 Mount the actuator lever.


5 Check function and ball valve for tightness.
→ See “Checking the Geberit Mapress ball valve for tightness”, page 17.


Table 4: Gland torque

d
[
mm]| |
---|---|---
15|

13

|

10

22|

13

|

10

28|

17

|

10

35|

17

|

10

42|

19

|

10

54|

19

|

10

76.1|

32

|

30

88.9|

32

|

30

108|

32

|

30

Operation

Operate the ball valve only when it is completely open or completely closed.


Geberit International AG
Schachenstrasse 77, CH-8645 Jona
documentation@geberit.com
www.geberit.com


GEBERIT logo 54043197998521995 © 01-2024
967.965.00.0(03)