Specifications

  • Product Name: TA-Modulator
  • Model: DN 40-50
  • Max Pressure: 600 kPa = 6 bar (87 psi)
  • Min Pressure: 30 kPa = 0.30 bar (4.35 psi)

Product Usage Instructions

Installation:

  1. Ensure the TA-Modulator is compatible with your system’s specifications.
  2. Mount the TA-Modulator securely in the designated location.
  3. Connect the necessary pipes according to the provided guidelines.

Operation:

  1. Turn on the TA-Modulator by following the manufacturer’s\ instructions.
  2. Adjust the settings based on your desired flow rate using the provided chart.
  3. Monitor the system to ensure it is functioning properly.

Maintenance

  1. Regularly check for leaks or any signs of damage.
  2. Clean the TA-Modulator as per the maintenance schedule provided in the manual.
  3. Replace any worn-out parts promptly to avoid system malfunction.

FAQ

  • Q: What is the maximum pressure the TA-Modulator can handle?
    • A: The TA-Modulator can handle a maximum pressure of 600 kPa = 6 bar (87 psi).
  • Q: How do I adjust the flow rate on the TA-Modulator?
    • A: You can adjust the flow rate by referring to the provided chart and selecting the appropriate setting.
  • Q: Is the TA-Modulator suitable for outdoor use?
    • A: The TA-Modulator is rated IP54, making it suitable for outdoor use as it is protected against dust and water splashes.

Product Information Instructions

  • -20°C – +120°C (-4°F – +248°F)
  • PN 16 (230 psi)
  • ΔpVmax: 600 kPa = 6 bar (87 psi)
  • ΔpVmin: 30 kPa = 0,30 bar (4.35 psi)

Pos

| q max
---|---
DN 40 [l/h]| 1 1/2” [US gpm]| DN 50

[l/h]| 2” [US gpm]
0.8| 1000| 4.40| 2150| 9.46
0.9| 1240| 5.46| 2640| 11.62
1.0| 1530| 6.73| 3220| 14.17
1.1| 1840| 8.10| 3790| 16.68
1.2| 2200| 9.68| 4430| 19.49
1.3| 2570| 11.31| 5150| 22.7
1.4| 3020| 13.29| 5990| 26.4
1.5| 3450| 15.18| 6870| 30.2
1.6| 3960| 17.42| 7800| 34.3
1.7| 4550| 20.0| 8790| 38.7
1.8| 5200| 22.9| 9740| 42.9
1.9| 5800| 25.5| 10600| 46.7
2.0| 6500| 28.6| 11200| 49.3

qmax =

  • l/h (US gpm) at each pre-setting and fully open valve plug.
  • l/h for each preset, with the shutter in the position totally open.

TA-Modulator + TA-Slider 500

IMITA-40-50-Bola-Systems-fig-2

  H [mm]

DN

| TA-Slider 500| TA-Slider 500 Plus
40| 203| 212
50| 206| 215

  H [in]

Size

| TA-Slider 500| TA-Slider 500 Plus
1 1/2″| 7.99| 8.35
2″| 8.11| 8.46

IMITA-40-50-Bola-Systems-fig-1

  • l/h for each stage preset at fully open control cones.
  • l/h with the given preset and fully open regulation skittles.
  • l/h given the preset and fully open valve stem.

Installation Instructions

IMITA-40-50-Bola-Systems-fig-3 IMITA-40-50
-Bola-Systems-fig-5 IMITA-40-50
-Bola-Systems-fig-6 IMITA-40-50
-Bola-Systems-fig-7 IMITA-40-50
-Bola-Systems-fig-8

We reserve the right to introduce technical alterations without prior notice.

www.imi-hydronic.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals