TD-4000
Tank Monitor
Ver 9.6
Installation Manual
TD-4000 Master Display Unit (MDU)
Provides the following functions:
- visual indication of tank level (bar graph or lts / gals & percentage)
- visual indication of battery voltage
- turn water pump on or off
- disable toilet when black tank full
- all tanks are name programmable e.g. (Aft-Grey) (Port Fuel) (Water)
- backlight
- audible alarm
Electrical Specifications TD-4000
Supply Voltage | 10 to 30 Volts DC (Auto-Sensing) |
---|---|
Quiescent Current | 0.03 Amps |
Data Retention | 50 years (without power) |
Outputs
The TD-4000 has two (open collector) outputs, which can be used to turn a
relay ON or OFF.
These outputs can be used to control pumps e.g. Black discharge pump, or
output 2 (only) can be programmed to activate a relay when the Black tank
reaches the set alarm point to disable the toilet.
Wiring Diagram for TD-4000
Pump Circuit Connection
To Blue or White wire on the TD-4000
Disable Toilet Circuit Connection NOTE: Output 2 ONLY
To White wire on the TD-4000
Part # RJ-STD
RJ-11 to three core cable
(Pressure sensor – phone cable connector to plug in green connector)
Connector Wiring
Connector Wiring For Ultra-Sonic Sender
Gnd = Black on Ultra-Sonic Sensor
Signal In = Green on Ultra-Sonic Sensor
+ 12 vdc Out = Red on Ultra-Sonic Sensor
+ 5 vdc Out = NOT USED on Ultra-Sonic
Connector Wiring For Pressure Sender
Gnd = Black on Pressure Sensor
Signal In = Green on Pressure Sensor
+ 5 vdc Out = Red on Pressure Sensor
+ 12 vdc Out = NOT USED on Pressure Sensor
WARNING: DO NOT CONNECT TO + 12 vdc
Connector Wiring For RJ-11 Adaptor
Gnd = Black
Signal In = White
+ 5 vdc Out = Red
+ 12 vdc Out = NOT USED on Pressure Sensor
WARNING: DO NOT CONNECT TO + 12 vdcThis system has 2 display modes.
See point 3 on page 10 – Operating Instructions to change.
Programming Instructions
NOTE: Program Input & Calibrate must be performed for each tank
Step 1: Placing the unit in Program Mode
Press and hold down the Backlight key now press and hold the Scroll key. Hold
together for 3 seconds. This will bring you to the
Set-Up Menu.
Press the Scroll or Backlight key to scroll through the Set-Up Menu or Press
the Pump key to program an Input.
Step 2: Selecting an Input to program
Once in program mode each Input can be individually programmed.
The display will now show:
Use the Scroll or Backlight key to scroll to the Input requiring programming.
Press the Pump key once the input to be programmed has been found.
Step 3: Selecting Tank or Battery Name
The display will now show: Select Input 1
GREY TANK Select Name
NOTE: There is a list of pre-programmed names for you to choose from, if
you want to change a name see step 3a below. Once a name has been used DO NOT
use the same name again when programming another tank choose another name from
the list to either use or change.
Use the Scroll or Backlight key to scroll through the pre-programmed tank
names. Press the Pump key once the required tank name has been found. If you
want the name selected press the Pump key again, otherwise if you want to
change the name see next Step 3a.
Step 3a: Changing Tank Name Text
The tank name text may be changed. After selecting the Tank (name), as above,
use the Backlight key to move the cursor to each individual letter and the
Scroll key to scroll through the alphabet. When finished, press the Pump key
to enter.
Step 4: Selecting Type
The display will now show:
Use the Scroll or Backlight key to scroll through the various Input Type’s
e.g. Grey Water, Black Water, Fresh Water, Fuel etc. Press the Pump key once
the appropriate tank type has been found. Note: The tank type only sets where
the alarm point starts and the pump default start or stop points.
If the Battery is selected see Step 5a. If Transfer is selected see page 12
Step 5: Setting the Alarm point for Tank The display will now show: The alarm
point is the point where the tank will alarm you. E.g. almost or empty, almost
or full Use the Scroll or Backlight key to move the alarm point to the desired
level. Press the Pump key to set this as your alarm point.
Step 5a: Setting the Alarm point for Low Battery
The display will now show:
The alarm point is the point where the battery will alarm you when it’s low.
This can be set at any level.
Use the Scroll or Backlight key to move the alarm point to the desired level.
Press the Pump key to set this as your alarm point.
Set Alarm Point
Set Alarm = 10
Step 6: Audible Alarm
The display will now show:
Press the Scroll key to select “Yes” or the Backlight key to select “No”.
If Yes is selected the audible alarm will sound based on the alarm point set,
as above.
If No is selected there will be no audible alarm, associated with that input,
only a visual bell.
Note: If this is a battery, the system will now return you to the Set-Up
Menu. If this is a tank go to Step 7.
Tank Volume
The display will now show: This allows for displaying the tank volume in
either Litres or Gallons. If this feature is required press the Scroll key to
select “Yes”. Next select “Lts” for Litres or “Gals” for Gallons.
The display will now show “ Set Volume 00000 ”. Use the Backlight and Scroll
keys to change the value and the Pump key to enter and move to the next digit.
When the last digit is reached and the Pump key is pressed the system will
return to the Set-Up Menu.
Otherwise press the Backlight key to select ”No”.
If No is selected the system will return to the Set-Up Menu. Once back at the
Set-Up Menu repeat this process for all additional Inputs.
Note: After a tank has been programmed individual settings may be
changed. From the Set-Up Menu scroll to the option you wish to change and
press the Pump key. You can now change that particular setting as per the
instructions.
Set Outputs
The TD-4000 has two outputs and can be associated with any of the inputs.
To set up this feature, scroll down to “Set Output” (in the Set-Up Menu) and
press the Pump key.
The display will now show: Press the Scroll or Backlight key to scroll to the
Input you want to select and press the Pump key.
The display will now show:
This allows you to exit in the event that you have made a mistake with regards
to which Input you would like to attach an Output. If you would like to escape
then press the Backlight key. This will return you to the SetUp Menu.
Otherwise press the Scroll key to continue.
The display will now show:
Press the Scroll or Backlight key to move between Output 1 & 2. Once the
desired Output is displayed, press the Pump key. This has now been set and the
system will return to the Set-Up Menu.
This setting can be changed at any time by selecting this option from the menu
and following the on screen directions.
Pump Output: (also see Pump Start / Stop: page 10 )
The TD-4000 has two Pump Output controls and works as follows:
If used for Black or Grey you can turn it ON and OFF manually. If the pump is
ON will turn OFF automatically when the tank is empty or at the programmed
Pump Stop Point.
If used for Water you can turn it ON and OFF manually. If the pump is ON it
will turn OFF automatically when the tank reaches the programmed low alarm
point or at the programmed Pump Stop Point.
If used for Fuel you can turn ON and OFF manually. If the pump is ON it will
turn OFF automatically when the tank is full or at the programmed Pump Stop
Point.
If a tank type has been programmed as a Day Fuel (see Step 4) the Output will
automatically turn ON at the programmed Pump Start Point and turn OFF when the
tank is full or at the programmed Pump Stop Point. If the Pump key is pushed
during the automatic pumping the pump will stop and the Day Tank feature will
be placed into manual mode Pushing the pump key again will start the pump
again and place it back into automatic mode.
Special Pump:
If the Black tank has a charcoal filter fitted and you are using a pressure
sensor you will need to use this feature.
Explanation: When the pump is turned on liquid is removed from the tank
quicker than air can replace it due to the constrictive nature of the air
filter. This will cause a pressure drop, the system will think the tank is
empty and turn the pump off.
The Special Pump feature will allow the pump to run for a pre-set time without
looking at the tank level (which will be wrong due to the above reason), the
pump will then turn Off for 20 seconds allowing the tank to equalize its
pressure. The system will then look at the tank level and turn the pump back
On for a time period. This time will be based on the tank level e.g. If the
tank level is low, the time period will be short. This will continue until the
tank is empty.
If this feature is selected then, when the pump is On, the display will show
——PUMPING——.
When the pump is Off, during the equalizing time, the display will show
——EQUALIZING——.
Scroll down to “Special Pump” and press the Pump key.
The display will now show:
Special PumpOut
Pump Start / Stop
Day Tank:
If a tank has been set as a Day Tank in the Tank TYPE set-up then this feature
allows you to set when the transfer pump will automatically be turned On and
Off.
This can be set up by selecting the “Pump Start/ Stop” option from the Set-Up
Menu and selecting the tank you wish to set this up on. Use the Scroll or
Backlight keys to set the pump Start and Stop point. Once this is complete
press the Pump Key and you will return to the Set-Up Menu.
Grey, Black, Fresh or Fuel:
If a tank has been set as either a Grey, Black or Fresh Tank in the Tank TYPE
set-up then this feature allows you to set when the pump will automatically be
turned Off.
This can be set up by selecting the “Pump Start/ Stop” option from the Set-Up
Menu and selecting the tank you wish to set this up on. Use the Scroll or
Backlight keys to set the pump stop point. Once this is complete press the
Pump Key and you will return to the Set-Up Menu.
Note: Set the stop point for Grey, Black or Water at a very low setting and
Fuel at a top setting.
Transfer:
If a tank has been set as a Transfer in the Tank TYPE set-up then this feature
allows for both low and high pump stop points see page 12.
Disable Toilet:
From the Set-Up Menu scroll down to “DISABLE TOILET” then press the Pump
key.
The display will now show:
If “Yes” is selected (by pressing the Scroll key) this will set Output two
(white wire) to short to GND when the Black Tank reaches the alarm point and
turn Off 12 displays bars below this point.
If No is selected you will return to the main MENU.
Copy Calibrate:
This function allows you to copy the calibrations setting from one input to
another.
NOTE: please ensure you have calibrated the input you are coping FROM.
From the Set-Up Menu scroll down to “COPY CALIBRATE” then press the Pump key.
The display will now show: Use the Scroll key to scroll to the input you want
to copy FROM and press the Pump Key to enter.
The display will now show: Use the Scroll key to scroll to the input you
want to copy TO and press the Pump Key to enter, you will now be returned to
the main MENU.
External Alarm : Using Output 2 (white ) for external alarm:
Note: External alarm can be used for both low and high or just high.
Step 1:
From the Set-Up Menu scroll down to “External Alarm” then press the Pump key.
The display will now show:
Use the Scroll or Backlight key to find the Input to associate with the
external alarm (only one input may be associated), when the input is found
press the Pump key to except.
Step 2:
The display will now show: Both low and high alarm points OR just the high
alarm point can be set.
If “Yes” is selected (by pressing the Pump key) this will activate and allow
the low alarm points to be set
If No is selected goto Step 5
Step 3:
The display will now show: Use the Scroll or Backlight key to set the point
where the Low alarm comes on (trigger point).
Step 4:
The display will now show:
Use the Scroll or Backlight key to set the point where the Low alarm comes off
(alarm reset point).
Note: this point MUST be greater than the Start point.
Step 5:
The display will now show: Use the Scroll or Backlight key to set the point
where the High alarm comes on (trigger point).
Step 6:
The display will now show: Use the Scroll or Backlight key to set the point
where the High alarm comes off (alarm reset point).
Note: this point MUST be smaller than the Start point.
Transfer Fuel Feature:
This feature allows for the pump output to have both low and high stop points.
Step 1:
When programming a tank and the INPUT TYPE screen is displayed.
The display will now show: Use the Scroll or Backlight key to scroll to the
option “Transfer Fuel” and press the Pump key to except.
Set the alarm ( Step 5) and Tank Vol (Step 7) settings.
Step 2:
At the main menu scroll down to the “PUMP START/STOP” option
The display will now show:
Use the Scroll or Backlight key to find the Input to associate with the
output, when the input is found press the Pump key to except.
Step 3:
The display will now show: Use the Scroll or Backlight key to set the low
point where the pump will turn OFF and press the Pump key to except.
Step 4:
The display will now show: Use the Scroll or Backlight key to set the high
point where the pump will turn OFF and press the Pump key to except.
Erasing Inputs:
From the Set-Up Menu scroll down to “ERASE INPUT” then press the Pump key.
The display will now show:
If “Yes” is selected (by pressing the Scroll key) –
The display will now show:
Use the Scroll or Backlight key to find the Input to erase, and then press the
Pump key to erase that Inputs data, the system will then return back to the
Set-Up Menu.
If “No” is selected (by pressing the Backlight key) the inputs data will NOT
be erased and the system will return back to the Set-Up Menu.
Exit Menu
Once all required inputs have been calibrated and programmed, you can exit
from the Set-Up Menu by pressing the Scroll key until “Exit Menu” is
displayed, then press the Pump key. This will save all associated data that
has been set and take the system out of Set-Up mode and into Monitoring mode.
The TD-4000 is now ready for use!
Operating Instructions
- Pressing the Backlight key will turn the backlight ON, press again to turn OFF.
- Press the Scroll key to alternate between tanks.
- Press and hold the Scroll for 4 seconds to alternate between display modes.
- Pressing the Pump key will turn the pump (power) ON, press again to turn OFF.
If a pump is turned ON a “P” will be displayed in the top right section of the
display.
The Pump key will also act as the Mute key if an alarm is on. E.g. if the
alarm is ON the first press will mute the alarm, the second press will turn
the pump ON or OFF.
Audio Alarm:
The audio alarm can be turned ON or OFF by holding down the Backlight key
for 3 seconds, you will hear a bleep after every second. After 3 bleeps you
may release the key. If the audible alarm is turned off there will still be a
visual alarm (bell icon).
The bell icon will flash when the tank with the alarm is scrolled to otherwise
it will remain on solid. A solid bell indicates there is an alarm, but not for
the tank being displayed.
Sensor Installation
! WARNING !
PLEASE NOTE: For sensor Model SEN-50 The Maximum Tank Height is .5 Meter
PLEASE NOTE: For sensor Model SEN-100 The Maximum Tank Height is 1 Meter
PLEASE NOTE: For sensor Model SEN-250 The Maximum Tank Height is 2.5 Meter
The maximum surge and safe pressure is 28psi.
For more information see “Calibration Tips & Tricks” on our web site
www.smartswitch.co.nz
Mounting Adaptors Available:
A range of mounting adaptors are available which includes flat sidewall,
top mount, 1.5” pipe, 2” pipe, 3” pipe and drain valve. Ask your dealer for
details.
Sensor Installation:
The sensor should be mounted as low in the sidewall as possible using a ¾”
spin-in or the flat sensor adaptor. If the sensor adaptor is used it will
require drilling a 5/8” hole in the sidewall. Apply silicon glue liberally to
the bottom of the adaptor. Using #10 x ½” stainless steel self-tapping screws
attach the adaptor to the sidewall. Once the adaptor is attached make sure
that the hole in the adaptor is clear of any excess glue. Allow drying as per
the instructions for the glue. Wrap the threads of the sensor using Teflon
plumbers tape and install the sensor. Tighten by hand. It is not recommended
to install the sensor in the bottom of the tank. Although the sensor will
operate correctly it will provide an area for debris to collect which would be
difficult to flush out.The top-mounting adaptor requires 3/4″ ABS
or PVC pipe cut to the proper length so that the pipe is about 1/2″ from the
bottom of the tank. This pipe glues into the adaptor and the sensor screws
into the top of the adaptor. It is held on with 2 self-tapping screws. Care
must be taken that the sensor threads are sealed with Teflon tape and screwed
in tight to ensure no air leaks, as the tube must remain pressurized.
The
sensor will be damaged if subject to over pressure during installation, caused
by compressing the small air gap between the sensor and the ball valve.
DO NOT PRESSURIZE TANK WITH SENSOR FITTED
Sensor Programming Instructions
Placing the unit in Calibrate Mode
Press and hold down the Backlight key now press and hold the Scroll key.
Hold together for 3 seconds. This will bring you to the Set-Up Menu.
Use the Scroll or Backlight key to scroll to “Calibrate” and press the Pump
Key.
This will bring you to the Calibrate Menu.
The display will now show: Use the Scroll or Backlight key to scroll to the
tank input requiring calibration. Press the Pump key once the input to be
calibrated has been found.
The display will now show: Use the Scroll or Backlight key to scroll
through the list of sensor options. Once you have found the appropriate sensor
type, press the Pump key.
If Pressure is selected the display will now show: Two different methods of
tank programming are available if using the pressure sensor:
2 Point Calibration: sets tank low and high points which can only be used if
the tank is a regular shape.
5 Point Calibration: sets tank low, tank quarter, tank half, tank three
quarters and tank full points, offering more accuracy if the tank is an
irregular shape.
Press the Scroll or Backlight key to select either 2 or 5 Point Calibration.
2 Point Calibration: (Bottom & Top) The display will now
show: Fill the tank to the required TANK LOW LEVEL,
minimum suggested is liquid just covering the sensor. Wait for approx. 60
seconds for the fluid to settle and press the Pump key. The display will show
“Setting Empty Please Wait”.
The display will now show:
Fill the tank to the TANK HIGH LEVEL. Wait for approx. 60 seconds for the
fluid to settle and press the Pump key. The display will show “Setting Full
Please Wait”. When the system has finished calculating, (could take a few
moments) the display will show “ Calibration Finished “ and the system will
return you to the Set-Up Menu.
Once back at the Set-Up Menu repeat this process. This must be repeated for
all additional Inputs.
If no fluid is added the display will show:
For more information see “Calibration Tips & Tricks” on our web site
www.smartswitch.co.nz
5 Point Calibration: (Bottom, ¼, ½, ¾ & Top) The display will show:
Fill the
tank to the required TANK LOW LEVEL, minimum suggested is liquid just covering
the sensor. Wait for approx. 60 seconds for the fluid to settle and press the
Pump key. The display will show “Setting Empty Please Wait”.
The display will now show:
Fill the tank to the 1/4 LEVEL. Wait for approx. 60 seconds for the fluid to
settle and press the Pump key. The display will show “Setting 1/4 Please
Wait”.
The display will now show: Fill the tank to the 1/2 LEVEL. Wait for approx. 60
seconds for the fluid to settle and press the Pump key.
The display will show “Setting 1/2 Please Wait”.
The display will now show: Fill the tank to the 3/4 LEVEL.
Wait for approx. 60 seconds for the fluid to settle and press the Pump key.
The display will show “Setting 3/4 Please Wait”.
The display will now show:
Fill the tank to the FULL LEVEL. Wait for approx. 60 seconds for the fluid to
settle and press the Pump key.
The display will show “Setting Full Please Wait”. When the system has finished
calculating, (could take a few moments) the display will show “ Calibration
Finished “ and the system will return to the Set-Up Menu.
Once back at the Set-Up Menu repeat this process. This must be repeated for
all additional Inputs.
If no fluid is added between each step the display will show: For more
information see “Calibration Tips & Tricks” on our web site
www.smartswitch.co.nz
If Ultra-Sonic is selected: the display will show “ Calibration Finished “ and
the system will return to the SetUp Menu. This is because the Ultra-Sonic
sensor is to be pre-calibrated with its own hardware/software.
NOTE – Please see Programming Instructions for Ultra-Sonic sensor in the
manual supplied with the sensor.
If 10-180 Ohm is selected: the display will show “ Calibrating Please Wait
“.When the system has finished calculating, (could take a few moments) the
display will show “ Calibration Finished “ and the system will return to the
Set-Up Menu.
If 33-240 Ohm is selected: the display will show “ Calibrating Please Wait
“.When the system has finished calculating, (could take a few moments) the
display will show “ Calibration Finished “ and the system will return to the
Set-Up Menu. If Other Sender is selected: this is the same as selecting
Pressure – see instructions for Pressure on page 15. After calibrating the
bottom and top settings of a tank you may wish to go back and change either of
these settings individually.
If Top Only is selected: the system will read the current level of the tank
and calibrate this as the top level for that particular tank.
The system will then return to the Set-Up Menu.
If Bottom Only is selected: the system will read the current level of the tank
and calibrate this as the bottom level for that particular tank. The system
will then return to the Set-Up Menu. To Exit from the Calibrate Menu: scroll
down to “Exit Menu” and press the Pump key. This will take you out of the
Calibrate Menu and return you to the Set-Up Menu.
Table 1:
Smart Switch strongly recommends that Table 1 be filled out at time of tank
calibration when a Pressure sender is being used.
These voltages will be displayed during the calibration setup.
Reason: Should the TD-4000 ever need to be replaced all tanks will need to be
re-calibrated, but if table 1 has been filled out then creating these input
voltages can be done without even the tank sender connected,making the process
very simple.
Table 1
Inputs| Tank Name| Empty| 4-Jan| 2-Jan| 4-Mar|
Full
---|---|---|---|---|---|---
Input 1| | | | | |
Input 2| | | | | |
Input 3| | | | | |
Input 4| | | | | |