Altronix AL600X220 Series Power Supply Charger Installation Guide

June 2, 2024
Altronix

AL600X220 Series
Power Supply/Charger

AL600X220 Series Power Supply Charger

Models Include:
AL600X220
– Single Output.
AL600PD4220
– Four (4) Fuse Protected Outputs.
AL600PD8220
– Eight (8) Fuse Protected Outputs.
AL600XPD16220
– Sixteen (16) Fuse Protected Outputs.
AL600X220
– Single Output.
AL600PD4220
– Four (4) Fuse Protected Outputs.
AL600PD8220
– Eight (8) Fuse Protected Outputs.
AL600XPD16220
– Sixteen (16) Fuse Protected Outputs.

For a red enclosure add an “R” suffix to the part #, e.g. AL600PD8R220
For a larger enclosure add an “X” suffix to the part #, e.g. AL600XPD8220
Installation Guide


Rev. 111612
Installing Company: ____Service Rep. Name:
Address: ____
Phone #: __

Overview:

Altronix AL600X220 is a power supply that converts a nominal 220VAC (working range 198VAC-256VAC), 50/60Hz input to a 12VDC or 24VDC regulating output (see specifications below). The AL600X220 is the base power supply unit for the multi-output power supply/charger series: AL600PD4220, AL600PD4CB220, AL600PD8220, AL600PD8CB220, AL600XPD16220, AL600XPD16CB220 (Refer to AL600X220 Series Power Supply Configuration Reference Chart below).

AL600X220 Series Power Supply Configuration Reference Chart:

Altronix Model Number| Accessory Power Distribution Module(s)| Number of Outputs| Fused Outputs| PTC Outputs (auto-resettable)| 12VDC or 24VDC Total Output Current (A)| Individual Output Rating (A)| Power Supply Input Fuse Rating| Accomodates Stand-by Batteries
---|---|---|---|---|---|---|---|---
AL600X220| –| 1| –| –| 6A| 6A| 5A/250V| Two (2) 12VDC/7AH
AL600XX220| Two (2) 12VDC/12AH
AL600PD4220| PD4| 4| | –| 3.5A| Two (2) 12VDC/7AH
AL600XPD4220| Two (2) 12VDC/12AH
AL600PD4CB220| PD4CB| –| | 2.5A| Two (2) 12VDC/7AH
AL600XPD4CB220| Two (2) 12VDC/12AH
AL600PD8220| PD8| 8| | –| 3.5A| Two (2) 12VDC/7AH
AL600XPD8220| Two (2) 12VDC/12AH
AL600PD8CB220| PD8CB| –| | 2.5A| Two (2) 12VDC/7AH
AL600XPD8CB220| Two (2) 12VDC/12AH
AL600XPD16220| Two (2) PD8| 16| | –| 3.5A| Two (2) 12VDC/12AH
AL600XPD16CB220| Two (2) PD8CB| –| | 2.5A| Two (2) 12VDC/12AH

Specifications:

Agency Listing:

  • CE European Conformity.

Input:

  • Input 220VAC (working range 198VAC-256VAC), 50/60Hz, 1.5A.

Output:

  • 12VDC or 24VDC selectable output(s).
  • 6A continuous supply current at 12VDC or 24VDC.
  • Filtered and electronically regulated outputs.
  • Short circuit and thermal overload protection.

Supervision:

  • AC fail supervision (form “C” contacts).
  • Low battery supervision (form “C” contacts).
  • Battery presence supervision (form “C” contacts).

Battery Backup:

  • Built-in charger for sealed lead acid or gel type batteries.
  • Automatic switch over to stand-by battery when AC fails.
  • Maximum charge current 0.7A.
  • Zero voltage drop when switched over to battery backup.

Additional Features:

  • AC input, DC output, and BAT trouble LED indicators.
  • Power supply, enclosure, cam lock, and battery leads.
  • All models are available in a red enclosure (add an “R” suffix to the part # e.g. AL600PD8R220).

Power Supply Output Specifications:

Output Switch Position
12VDC SW1 – ON (Fig. 1b, pg. 3)
24VDC SW1 – OFF (Fig. 1b, pg. 3)

Stand-by Specifications (total current shown):

Output| 4 hr. of Stand-by and 5 Minutes of Alarm| 24 hr. of Stand-by and 5 Minutes of Alarm| 60 hr. of Stand-by and 5 Minutes of Alarm
---|---|---|---
12VDC / 40AH Battery| Stand-by = 6.0A
Alarm = 6.0A| Stand-by = 1.0A
Alarm = 6.0A| Stand-by = 300mA
Alarm = 6.0A
24VDC / 12AH Battery| –| Stand-by = 200mA Alarm = 6.0A| –
24VDC / 40AH Battery| Stand-by = 6.0A
Alarm = 6.0A| Stand-by = 1.0A
Alarm = 6.0A| Stand-by = 300mA
Alarm = 6.0A

Fig. 1 – AL600X220 Series
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.Altronix AL600X220 Series
Power Supply Charger - Fig CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery. Keep power-limited wiring separate from non power-limited. Use minimum 0.25″ spacing.

Installation Instructions:

Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.

  1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7-8).

  2. Connect AC circuit (220VAC, 50/60H2) as follows: Green branch wire connects to earth (safety) ground lug . Line and Neutral to the connector on power supply board marked [L, N] respectively (Fig. 1, pg. 3).
    Use 14 AWG or larger for all power connections (Battery, DC output, AC input).
    Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
    Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input,
    Battery Wires). Minimum 0.25” spacing must be provided.
    CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

  3. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1c, pg. 3) to the appropriate position Power Supply Voltage Output Specifications Chart, pg. 2).

  4. Measure output voltage before connecting any devices to ensure proper operation. Improper or high voltage will damage these devices. When servicing the unit, AC mains should be removed.

  5. Connect devices to be powered:
    a. For AL600X(R)220 Power Supply: connect devices to the terminals marked [+ DC -] (Fig. 1, pg. 3.
    b. For other Power Distribution Models: connect devices to be powered to the terminal pairs 1 to 4 marked [1P & 1N] through [4P & 4N) (Fig. 2a & 2b, pg. 6) or 1 to 8 marked [1P & 1N] through [8P & 8N] Fig. 3a & 3b, pg. 6), carefully observing correct polarity.

  6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

  7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1a, og. 3) supervisory relay outputs.
    Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper (Fig. 1b, pg. 3).

  8. Please ensure that the cover is secured with the provided key lock.

Wiring:

Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power- limited wiring (220VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for the proper voltage level (Power Supply Voltage Output Specifications Chart, pg. 3).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the battery terminal and at the board terminals marked [+ BAT -] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 0.7A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Power Supply Board

Red (DC) Green (AC) Red (BAT) Status
ON ON ON Normal operating condition.
ON OFF ON Loss of AC. Stand-by battery supplying power.
OFF ON OFF No DC output, Battery Trouble
OFF OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
ON ON OFF Battery missing / Low

Power Distribution Module

Green Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.

Terminal Identification:

Power Supply Board

Terminal Legend Function/Description
L, G, N Connect 220VAC (working range 198VAC – 256VAC), 50/60Hz to these

terminals: L to Hot, N to Neutral. Do not use the [G] terminal.
+ DC –| 12VDC @ 4A or 24VDC @ 3A continuous power-limited output.
AC Fail NC, C, NO| Indicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. AC Fail condition will report approxi- mately within one (1) minute after loss of AC. To delay report for 6 hours cut jumper J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected, the Power Supply Board must be reset by removing all power to it for 30 seconds.
Bat Fail NC, C, NO| Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. Low battery conditions will report approxi- mately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output setting).
Battery presence detection will report approximately 1 minute after battery remains undetected (missing or removed).
+ BAT –| Stand-by battery connections. Maximum charge current 0.7A.

Power Distribution Module

Terminal Legend Function/Description
PD4/PD4CB PD8/PD8CB
1P to 4P 1P to 8P
1N to 4N 1N to 8N

Power Distribution Module(s):

Altronix AL600X220 Series Power Supply Charger - Fig 1

Enclosure Dimensions (BC300):
AL600X220, AL600XR220, AL600PD4220, AL600PD4CB220, AL600PD8220, AL600PD8CB220
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)Altronix AL600X220 Series
Power Supply Charger - Fig 2

Enclosure Dimensions (BC400):
AL600XX220, AL600XXR220, AL600XPD4220, AL600XPD4CB220, AL600XPD8220, AL600XPD8CB220, AL600XPD16220, AL600XPD16CB220
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)Altronix AL600X220 Series
Power Supply Charger - Fig 3

Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA
phone: 718-567-8181
fax: 718-567-9056
website: www.altronix.com
e-mail: info@altronix.com
Lifetime Warranty
IIAL600X220 Series
G07U
AL600X220 Series Installation Guide