MULTI-MAGIC CW-H10 Cooler Models Indirect Evaporative Cooler Instruction Manual
- May 15, 2024
- MULTI-MAGIC
Table of Contents
- MULTI-MAGIC CW-H10 Cooler Models Indirect Evaporative Cooler
- Product Information
- Operation Instructions
- FAQs
- IMPORTANT SAFETY INSTRUCTIONS
- COOLER VIEWS
- TECHNICAL DESCRIPTION
- INSTALLATION
- WATER REQUIREMENTS
- COOLER CONTROL COMPONENTS
- SETTING
- FAULT CODE DESCRIPTIONS
- COMMISSIONING
- TYPE OF INSTALLATION
- MAINTENANCE INSTRUCTIONS
- PATTERN CHANGES
- SUGGESTED REMEDY
- WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
MULTI-MAGIC CW-H10 Cooler Models Indirect Evaporative Cooler
Product Information
Specifications
- Models: CW-H10, CW-H15, CW-H15S, CW-H15S Plus
- Multi-Magic Models
- Language: English
Installation Instructions
1. Unpacking and Moving
Ensure to carefully unpack the cooler and follow the guidelines for moving it to the desired location.
2. Installation Components
Identify and assemble all installation components as per the provided list.
3. Cooler Location
Select an appropriate location for the cooler ensuring access for servicing and maintenance.
4. Mounting and Support
Securely mount the cooler with proper support and consider vibration isolation techniques.
5. Water Supply Installation
Follow the guidelines for water supply installation including pressure regulation, isolation, filtration, and drainage.
6. Electrical Supply Installation
Adhere to electrical requirements and ensure safe installation of the electrical supply with necessary protections.
7. Control Components Setup
Set up the control components including water management system, input/output terminals, and follow specific control method options provided.
Operation Instructions
1. Changing Cooler Settings
Utilize the provided controls to adjust settings such as fan start delay, run output relay, and more.
2. Maintenance Schedule
Follow the maintenance schedule outlined in the manual including quarterly inspection procedures and specific maintenance instructions for various components.
3. Troubleshooting
Refer to the troubleshooting section in case of any issues with the cooler operation.
FAQs
- Q: What should I do if the cooler displays a fault code?
- A: Refer to the fault code descriptions in the manual to identify the issue and follow instructions to reset if necessary.
- Q: How often should I perform maintenance on the cooler?
- A: Follow the maintenance schedule provided in the manual, typically including quarterly inspections and specific maintenance tasks.
“`
IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE.
FOR EUROPE This appliance can be used by children aged from 8 years and above
and persons with reduced physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given supervision or instruction
concerning use of the appliance in a safe way and understand the hazards
involved. Children shall not play with the appliance. Cleaning and user
maintenance shall not be made by children without supervision.
FOR AUSTRALIA, NEW ZEALAND & OTHER NON-EUROPEAN COUNTRIES This appliance is
not intended for use by persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.
Means for all pole disconnection must be incorporated in the fixed wiring in
accordance with the wiring rules, adjacent to or on the cooler cabinet. If
mounting on the cooler cabinet, take care not to puncture the water reservoir.
The following specifications for the cooler water supply are required:
Water Connection ½” BSP (Aus/Eur), ½” NPT (USA)
Min Water Pressure 100kPa (15psi)
Max Water Pressure 800kPa (115psi)
Max Water Flow 20 L/min (5.3 gallons/min)
Max Water Temperature 40°C (104°F)
This cooler is intended to be permanently connected to the water mains and not
connected by a hose set.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
CAUTION: In order to avoid a hazard due to inadvertent resetting of the
thermal cut-out, this appliance must not be supplied through an external
switching device, such as a timer, or connected to a circuit that is regularly
switched on and off by the utility.
4 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
FOR AUSTRALIAN BUSHFIRE PRONE AREAS
WARNING If this evaporative cooler is installed in a BAL-12.5 to 29 area the
evaporative cooler dropper duct and flashings shall be adequately sealed at
the roof to prevent gaps greater than 3mm. The dropper duct and flashings
shall be non-combustible.
WARNING: This cooler is NOT APPROVED for installation in any bushfire zoned
area/ property (BAL-12.5 to BAL-FZ).
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have
questions, contact the manufacturer.
b) Before servicing or cleaning unit, switch power off at service panel and
lock the service disconnecting means to prevent power from being switched on
accidentally. When the service disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag, to the service panel.
c) Installation work and electrical wiring must be done by qualified person(s)
in accordance with all applicable codes and standards, including fire-rated
construction.
d) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
e) Do not use this fan with any solid-state speed control device.
f) Ducted fans must always be vented to the outdoors.
EMPLOYER AND EMPLOYEE RESPONSIBILITIES
The installation and maintenance of evaporative coolers at height has the
potential to create Occupational Health and Safety issues for those involved.
Installers are advised to ensure they are familiar with the relevant State and
Federal legislation, such as Acts, Regulations, approved Codes of Practice and
Australian Standards, which offer practical guidance on these health and
safety issues. Compliance with these regulations will require appropriate work
practices, equipment, training and qualifications of workers.
Seeley International provides the following information as a guide to
contractors and employees to assist in minimising risk whilst working at
height.
IMPORTANT SAFETY INSTRUCTIONS
INSTALLER AND MAINTENANCE CONTRACTORS – RISK ASSESSMENT
Installer and Maintenance Contractors
A risk assessment of all hazardous tasks is required under legislation. A risk
assessment is an essential element that should be conducted before the
commencement of work, to identify and eliminate the risk of falls or to
minimise these risks by implementing control measures. There is no need for
this to be a complicated process, it just is a matter of looking at the job to
be done and considering what action(s) are necessary so the person doing the
job does not injure themselves.
This should be considered in terms of:
· What are the chances of an incident happening?
· What could the possible consequence be?
· What can you do to reduce, or better still, completely get rid of the risk?
SOME POINTS TO CONSIDER
· What is the best and safest access to the roof and working areas?
· If a worker is alone, who knows they are there and if they get into
difficulty, how can they summon help?
· (Call someone on the ground? Mobile phone? etc.)
· What condition is the roof in? Should the trusses, underside or surface be
checked?
· Does the worker have appropriate foot wear? (Flat sole jogger type is
advisable)
· Are all power cables / extension leads safe and appropriately rated?
· Are all ladders, tools and equipment suitable in good condition?
· Where ladders are to be used, is there a firm, stable base for them to stand
on? Can they be tied or secured in some way at the top? Is the top of the
ladder clear of electricity supply cables?
· Is there a roof anchor to attach a harness and lanyard to? If so,
instruction should be issued for the use of an approved harness or only
suitably trained people used.
· Are all tools and materials being used, prevented from slipping and falling
onto a person at ground level? Is the area below the work area suitably
protected to prevent persons walking in this area?
· Does the work schedule take into account weather conditions, allowing for
work to be
suspended in high winds, thunder storms/ lightning or other types of weather
giving wet, slippery surfaces?
· Is there an on-going safety check system of harnesses, ropes, ladders and
access/lifting equipment and where they exist on roofs, anchor points before
the commencement of work?
· Is there a system which prevents employees from working on roofs if they are
unwell or under the influence of drugs or alcohol?
· Are there any special conditions to consider i.e. excessive roof pitch,
limited ground area, fragile roof, electrical power lines?
OTHER IMPORTANT REQUIREMENTS · Never force parts to fit because all parts are
designed to fit together easily without undue force.
· Never drill holes in the tank of the cooler.
· Check the proposed cooler location, to ensure that it is structurally
capable of supporting the weight of the cooler, or provide an adequate
alternate load bearing structure.
· Ensure the installation complies with all local and national regulations
with regards to electrical, plumbing and bushfire construction requirements.
MAINTENANCE NOTE
As with any product that has moving parts or is subject to wear and tear, it
is VERY IMPORTANT that you maintain your cooler and have it regularly
serviced. It is a condition of warranty cover for your cooler that you comply
with all of the maintenance and service requirements set out in this Manual.
Compliance with these requirements will prolong the life of your cooler.
Further, it is also a condition of warranty cover that each item in the
Maintenance Schedule in the Manual is filled out (by signing and dating it in
the places indicated) when the item is completed.
Any failure to carry out the required maintenance and servicing, and any
failure to fill out the maintenance schedule, will void your warranty.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 5
COOLER VIEWS
CW-H10 MODELS
TOP
REAR
ILL3156-A
SIDE
FRONT
ILL3158-A
BOTTOM
ILL3157-A ILL3159-A
ILL3160-A
Dimensions are in mm (inches in brackets). 6 | CW-H INSTALLATION, OPERATION &
MAINTENANCE MANUAL 859749-I
ILL3161-A
COOLER VIEWS
CW-H15 MODELS
TOP
2290 [90.2]
1969 [77.5]
1500 [59.1]
1825 [71.9]
REAR
ILL1916-C
REAR COWLING PANEL AND TWO RIGHT FILTERS HIDDEN FOR CLARITY
SIDE
323 [12,7] 908 [35,7]
40
250
[1,6] [9,8]
DRAIN
107 [4,2]
FRONT
EXHAUST DUCT 1822 [71.7]
WATER ENTRY
660 [26,0]
192 [7,6] ILL1917-C
EXHAUST DUCT 217 [8.6]
481 [18.9] BOTTOM
50
[2.0]
50
[2.0]
ILL1918-C
650 [25.6] MOUNTING BASE
1300 [51.2]
482 [19.0] 150 [5.9]
SUPPLY DUCT
500×500 (19.7×19.7)
419 [16.5]
668 [26.3]
509 [20.0]
ILL1919-C
400 [15.7]
800 [31.5]
1200 [47.2]
MOUNTING BASE 1800 [70.9]
EXHAUST C/L 1171 [46.1] 1283 [50.5] ILL2422-C
550 [21.7] 1150 [45.3] 1700 [66.9]
MOUNTING HOLES 10 [0.394] TYP 16 PL
BASE FRAME UNDERSIDE ILL1920-C
Dimensions are in mm (inches in brackets).
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 7
COOLER VIEWS
8 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
INDEX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
DESCRIPTION
COWLING ASSEMBLY ELECTRONICS BOX AIR FILTER ASSEMBLY FRONT PANELS MOTOR AND
FAN ASSEMBLY INLET TRANSITION ASSEMBLY PUMP, DRAIN VALVE AND WATER PROBE
PUMPS, INLET SOLENOID AND CHLORINATOR TANK ASSEMBLY BASE FRAME ASSEMBLY OUTER
PANELS (RHS) OUTLET TRANSITION ASSEMBLY DAMPER ASSEMBLY CORE AND SPREADER
ASSEMBLY EXHAUST GRILLE ASSEMBLY EXHAUST LID ASSEMBLY
1
2
4
6 5
9
16 15 14
7 8
13 12
3
4
10
11
ILL2423-D
COOLER CONTENTS
INSTALLATION COMPONENTS
Item
1A 1B
2
3
4
5A 5B
6A 6B 6C 6D 6E 6F 6G
7
8A 8B
9
Seeley Part
859749 862801
861883
866216
834798
637994 637393
805597 804446 804422 864341 864385 864372 804579
931685
834789 834790
637999
Description
Cooler Installation, Operation, Maintenance Manual Supercool Conversion
Instructions (CW-H15S only)
Adaptor Drain Elbow
40mm Flexible Coupling
Key, Control Box
Exhaust Centre Post CW-H15 or Exhaust Centre Post CW-H10
Screw 8AB x ½” Pan Phill Stainless Steel Screw SEMS HX 14×3/4″ Plastic Grommet
Size 14 Screw Set SHCS Stainless Steel M6x35mm Washer Flat Stainless Steel
M6x12.5×1.2mm Washer Flat Nylon M8x16mm Blanking Grommet 12.7×17.5mm
Exhaust Side Rails (1176mm Long)
Exhaust Grille (869×205) CW-H15 or Exhaust Grille (571×247) CW-H10
Exhaust Cap (CW-H15S Plus only)
QTY
1
1 1 1
1
10 5 5 4 4 4 2 2
1
2
ITEM 1A ITEM 1B ITEM 10
ITEM 2
ITEM 3
ITEITMEM44 ITEM 5 ITEM 6A ITEM 6B ITEM 6C
ITEM 7
ITEM 6D ITEM 6E/F ITEM 6G ITEM 8
ITEM 9
OPTIONAL COMPONENTS
Item
1 2A 2B 3 4
Seeley Part
121956
134192 134215
121963
121932
Description
Wall Control Kit Roofstand 0-10O (CW-H10) Roofstand 0-10O (CW-H15, H15S, H15S
Plus) Room Air Sensor Kit Ambient Air Sensor Kit
ITEM 1
ITEM 2
ITEM 3
ITEM 4
ILL3709-A
ILL3803-A
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 9
TECHNICAL DESCRIPTION
AIRFLOW
The cooler has a single fan which draws hot outside air through the rear-
mounted air filters, through the dry channels of the airto-air indirect
evaporative heat exchangers and into the plenum at the front of the cooler.
Inside the plenum, the air is split into an exhaust flow and a supply flow.
The exhaust air passes through the wet channels of the air-toair indirect
evaporative heat exchangers and out through the upper exhaust grille back to
atmosphere.
The supply air passes over a secondary direct evaporative cooling stage
(Supercool cooler only), before entering the customer’s ductwork.
HEAT EXCHANGERS
Indirect Evaporative Cooling (IEC) Stage
All coolers have air-to-air indirect evaporative heat exchangers, composed of
alternating dry and wet channels separated by a membrane. CW-H10 has 2 and
CW-H15 has 3.
Through evaporation and conduction, heat is transferred from the air in the
dry channels, across the membrane, and into the air in the wet channels.
The air in the dry channels is progressively cooled, but gains no additional
moisture.
Direct Evaporative Cooling (DEC) Stage
Supercool coolers are fitted with a secondary direct evaporative cooling
stage.
The cooled air from the IEC stage passes over saturated Chillcel® media,
where, through evaporation, it is cooled further with an increase in moisture
content.
EXHAUST AIR
IEC STAGE
FAN
FILTERS
SUPPLY AIR
DEC STAGE (SUPERCOOL
COOLERS)
10 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
TRANSPORT
MOVING THE COOLER
The cooler can be moved by forklift truck. Only use the openings on the
cooler. Do not lift through the pallet.
Min. forklift tyne gap 460mm (18.2″)
ILL1916-A
LIFTING THE COOLER
The cooler may be lifted by crane with slings through the cooler base forklift
truck tyne openings. Do not attempt to lift using any cabinet features or by
retrofitting lifting lugs. The cabinet may be damaged and/or lift safety
compromised. It is recommended to use a spreader bar on the straps or slings
to protect the upper edges of the cooler with a corner protector beneath the
lifting straps to avoid any damage to the cabinet during the lift.
UNPACKING THE COOLER
The cooler will be delivered on a dedicated pallet and will be wrapped in
plastic film which will need to be removed before installation. A small bag of
installation components along with the exhaust transition side rails and
grilles can be found under the lid of the main cabinet of the cooler. The
exhaust transition will need to be raised into place before operation.
WARNING: Once unwrapped, the exhaust transition assembly should be fitted
together as soon as practicable to avoid loose components becoming
lost/damaged and/or a hazard.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 11
INSTALLATION
COOLER LOCATION
Check the proposed cooler location, to ensure that it is structurally capable of supporting the weight of the cooler, or provide an adequate alternate load bearing structure.
Model
Shipping Weight
Operating Weight
CW-H10 CW-H15 CW-H15S, H15S Plus
250KG (550 LB) 340KG (750 LB) 355KG (783 LB)
255KG (560 LB) 330KG (728 LB) 345KG (761 LB)
Always locate the cooler where it will receive a plentiful supply of fresh
air, NOT in a recess where it may be starved for air or where the air is
polluted. Provision must be made for access to electricity, water supplies and
drains.
Air exiting the cooler exhaust is warm and heavily laden with moisture. Ensure
the cooler’s exhaust air will not cause corrosion or damage to other nearby
items. Do not allow exhaust air to re-circulate into the air intake of the
cooler.
Ensure the cooler location is a minimum of:
· 3.0m (10′) from a solid fuel heater flue
· 1.5m (5′) from a gas flue
· 1.0m (3.5′) away from adjacent solar panels or similar roof mounted fixtures
· 6.0m (20′) from a sewer vent
· 3.0m (10′) (preferably 5.0m (17′)) away from any TV antenna or antenna
cables. Make sure the cooler is not between the antenna and the transmission
tower that is providing the television signal to the home.
ACCESS FOR SERVICING AND MAINTENANCE
The cooler should be installed in a position that allows adequate access for
installation, and future maintenance and servicing activities. This should
comply with installation guidelines and any local, State and National
regulations.
Consider the following for installation location:-
· Which has clear access to and around the cooler
· Which is clear of fixtures in line with below clearances
· Which is clear of fall edges (> 3m (10′) away)
· Which is structurally capable of supporting the weight of the cooler and
service technicians
Required clearances around the cooler for future maintenance and servicing are
shown below.
MOUNTING/SUPPORT
Roofstands, accommodating 0-10 roof pitches, are available for order via
Seeley International. See Optional Components List.
ILL2426-A
The cooler base has a series of mounting holes for securing the cooler.
Dimensions and locations of the mounting holes are shown in the cooler views
at the beginning of this manual. Where necessary, installers should use a
sufficient number of suitably rated vibration isolation mounts to support the
operating mass of the cooler.
DRIP-TRAY
When coolers are installed indoors, or anywhere that water leakage could cause
damage, install a corrosion resistant drip tray under the whole unit.
Recommended sizes: CW-H10: 1500 x 1300 x 50mm (59″ x 51″ x 2″) CW-H15, H15S,
H15S PLUS: 1500 x 1900 x 50mm (59″ x 75″ x 2″) Apply silicone sealant between
drip-tray and cooler base at every fixing.
SUPPLY AIR DUCT CONNECTIONS
Dimensions for the supply air duct interface are shown in the cooler views at
the beginning of this manual. Vibration absorbing flexible connections are
recommended for all duct connections to the cooler. All ducts must be
independently supported. All duct direction changes must utilise a generous
radial turn with internal air directors to minimise turbulence and maximise
efficiency. All ducts are to be suitably insulated to minimise temperature
losses.
ILL1925-A
Extra service or warranty charges may apply for the cost of any equipment or
additional labour involved in accessing the cooler if these guidelines are not
met.
Note! Do you need to discuss the installation of items like safety anchor
points with the customer?
12 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
INSTALLATION
EXHAUST TRANSITION ASSEMBLY
The exhaust transition is supplied in knock-down form and it’s components are
to be found beneath the lid of the cooler and inside the component kit. 1.
Unscrew the 6 x SCREW SEMS HEX 14 x 3/4″ securing
the large top panel to the cooler body.
7. Slip the 2 x EXHAUST GRILLE and 1 x EXHAUST CENTRE POST into position,
retained inside the top panel front u-channel.
CW-H15S Plus ONLY: Before fitting to the cooler, slide an EXHAUST CAP over the
back of each EXHAUST GRILLE. The EXHAUST CAP covers the top portion of the
EXHAUST GRILLE, and is designed to optimise the CW-H15S Plus performance.
2. Lift the large top panel and locate; · 2 x EXHAUST SIDE RAILS (1176mm
Long) · 2 x EXHAUST GRILLE · 2 x EXHAUST CAPS (CW-H15S Plus Only)
3. Fit the EXHAUST SIDE RAILS to the inside vertical faces of the large top
panel with the supplied 10 x SCREW PAN PHILLIPS 8AB*1/2″ SS. Ensure the foam
seal faces down.
ILL2427-A
4. Fit the supplied 3 x PLASTIC GROMMET SIZE 14 to the rear lid panel upstand
square holes.
ILL2431-A
8. Screw the exhaust transition assembly to the cooler body with the supplied
11 x SCREW SEMS HEX 14 x 3/4″ . (3 x Rear, 3 x Left, 3 x Right, 2 x Centre
Post.)
9. Fit the supplied 4 x M6 x 35MM SET SCREW, STAINLESS STEEL FLAT WASHER,
NYLON FLAT WASHER to the tops of both core access doors (2 each side). Apply a
liberal coat of anti-seize paste to the screw thread prior to fitment.
10. Fit the supplied 2x BLANKING GROMMETS to the open holes in the lid sides
(1 each side).
BLANKING GROMMET
14 x 3/4″ BODY SCREWS
ILL2428-A
5. Fit the supplied 2 x PLASTIC GROMMET SIZE 14 to the EXHAUST CENTRE POST.
ILL2429-A
6. Position the large top panel over the top of the cooler, with the rear
u-channel over the top of the upstand, the side rails sitting on the tops of
the cooler side walls and the end posts sitting on the outside of the front
tray.
M6 x 35MM DOOR SCREWS
& WASHERS
ILL2432-B
EXHAUST DUCT CONNECTION REQUIREMENTS
If required for indoor installations the exhaust air may be ducted away from
the cooler.
Dimensions for the exhaust outlet are shown in the cooler views at the
beginning of this manual.
When designing the exhaust duct please note the following;
· Access to the heat exchanger cores requires the removal of the cooler
lid/exhaust transition. Ensure any additional ducting is readily removable
and/or lightweight.
· Where an installation requires extended exhaust ducts, the increase in
static load should not exceed 20 Pa (0.08 in wg).
ILL2428-A
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 13
INSTALLATION
SUPERCOOL COOLERS
The CW-H Supercool coolers are fitted with Chillcel pads, providing additional
Direct Evaporative Cooling (DEC).
They can be configured in two ways;
MODEL CW-H15S CW-H15S Plus
PERFORMANCE
Supply Airflow Rate
External Static Pressure
1100 L/s 3960 m3/h 2330 CFM 1600 L/s 5760 m3/h 3390 CFM
120 Pa
0.52 in.w.g. 80 Pa
0.32 in.w.g.
To correctly configure this cooler, ensure the following steps are followed
during the installation and commissioning process;
STEP 1 – EXHAUST CAPS
MODEL CW-H15S CW-H15S Plus
FIT EXHAUST CAPS? NO YES
This CW-H cooler has been supplied with 2x Exhaust Caps (P/N 637999), shipped loose under other exhaust components.
ILL3663-A
For CW-H15S PLUS ONLY slide an EXHAUST CAP over the back of each EXHAUST
GRILLE. The EXHAUST CAP covers the top portion of the EXHAUST GRILLE and is
designed to optimise the CW-H15S PLUS performance.
STEP 2 – SET CORRECT DEVICE TYPE
MODEL CW-H15S CW-H15S Plus
CHANGE DEVICE TYPE? YES
NO – FACTORY DEFAULT SETTING IS CORRECT
For CW-H15S ONLY access the SETUP menu on the PLC to change DEVICE TYPE.
Push and hold the RIGHT button until the password screen is displayed.
LOGIN
Enter Password
7378
ILL3664-A
Use the navigation LEFT/ RIGHT and UP/DOWN buttons to enter password “7378”
and push OK to display the SETUP screen.
ILL3665-A
SETUP DEVICE TYPE COMMUNICATION SERVICE SETTINGS
Use the navigation UP/DOWN buttons to move the cursor to DEVICE TYPE and push OK
DEVICE TYPE
PRODUCT FAMILY
MODEL
CW-H CW-H15S
VOLTAGE 380-480V/3PH
ILL3666-C
Push OK to activate the MODEL field. Use the navigation UP/DOWN buttons to
select CW-H15S.
Push OK to save the setting.
ILL3667-B
Push and hold the LEFT button to return to the previous menu. Repeat until the
display returns to the “CONTROL” menu.
ILL2431-A
FIT EXHAUST CAPS TO BACK OF EXHAUST GRILLE
ILL3668-A
STEP 3 – SET SUPPLY AIR PLENUM PRESSURE
MODEL CW-H15S CW-H15S Plus
PLENUM PRESSURE 175 Pa (0.70 in.w.g.) 210 Pa (0.84 in.w.g.)
All CW-H coolers require the supply air plenum pressure to be correctly set. Follow the detailed instructions set out in the Commissioning section of this manual.
14 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
ELECTRICAL REQUIREMENTS
ELECTRICAL SUPPLY INSTALLATION
INSTALLATION OF THE COOLER MUST CONFORM TO LOCAL ELECTRICAL RULES, REGULATIONS
AND STANDARDS.
It is a requirement of Seeley International that all coolers be wired with a
dedicated circuit and circuit breaker/fuse at the distribution board.
A mains isolation switch, with all pole disconnection, shall be furnished by
the contractor and installed adjacent to the cooler.
IMPORTANT! There are specific models for regional voltages and frequencies
which are not interchangeable. Specifically, the fan motor(s), transformer(s)
and pump(s) may be unique to the voltage/frequency of supply.
See the cooler rating label for the correct electrical data. Before connecting
the device, make sure the power supply matches the cooler voltage and
frequency.
Electrical Supply Specification (50Hz Option):
380-415V / 50 Hz / 3N~ / 4.9A (FLA)
Electrical Supply Specification (60Hz Options):
440-480V / 60 Hz / 3~ / 9A (FLA) 11.5A (MCA) 15A (MOPD)
200-240V / 60 Hz / 3~ / 11A (FLA) 14.5A (MCA) 20A (MOPD)
200-240V / 60 Hz / 1~ / 8A (FLA) 10.5A (MCA) 15A (MOPD)
Mains power terminals are provided inside the electrical cabinet with glands
provided for cable entry.
MOTOR LOCKED-ROTOR PROTECTION
Due to the built-in motor locked-rotor protection, the starting current (LRA)
is equal to or less than the nominal current (FLA).
HIGH LEAKAGE CURRENT
IMPORTANT! High leakage current. Earth connection essential before connecting
supply.
The cooler utilises a fan motor with a built in inverter drive. To comply with
EMC regulations these drives adopt EMC filters that connect to the motor earth
terminals. The normal filter leakage current to earth may accumulate to a
total leakage current in excess of 10mA. For asymmetrical power systems or if
a phase fails, the leakage current can increase to a multiple of the nominal
value.
To comply with regulations and to prevent electric shock this leakage current
must be properly addressed.
In particular, the earth terminal at the mains power point of connection must
be properly connected and earthed. Power must not be applied until this is
correctly completed.
RESIDUAL CURRENT CIRCUIT BREAKER (RCCB)
The cooler utilises a fan motor with a built-in variable speed drive (VSD). If
local electrical standards require the use of a residual current circuit
breaker (RCCB), only AC/DC-sensitive residual current devices (type B) are
permissible. If incorrectly selected and/or sized, pulsed charging currents
from the capacitors in the integrated EMC filter can lead to the instant
tripping of RCCB when the cooler power supply is switched on.
FIRE TERMINALS
A pair of terminals labelled “FIRE” are provided for integration with a
building fire management system.
These terminals provide power to the cooler controls and are supplied with a
bridge.
To use with a building management system, remove the bridge and connect the
terminals through a NORMALLY CLOSED relay which opens in a fire event.
Interrupting power to the PLC will immediately stop all cooler components,
including fans.
24VDC POWER SUPPLY
The cooler is provided with a 24VDC switch mode power supply for use with
internal components and optional sensor accessories. The maximum power
available for external components is 30W.
TRANSFORMER TAPPINGS
440-480V / 3~ coolers ONLY are fitted with a transformer to power the cooler
electronics. By default the input voltage jumper is set for 480V. If the power
supply has a different phase-to-phase voltage, reposition the jumper as per
the table below.
380-415V control box shown FIRE
TERMINALS
3~ MAINS TERMINALS
PHASE TO PHASE PRIMARY VOLTAGE
380V 400V 415V 440V 460V 480V
JUMPER BETWEEN
31 – 38 32 – 38 31 – 37 32 – 37 32 – 36 33 – 36
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 15
WATER REQUIREMENTS
WATER SUPPLY INSTALLATION
The cooler requires a permanent water supply to be connected. A built-in Inlet
Solenoid Valve, controlled by the water management system, allows water into
the cooler when required.
INSTALLATION OF THE WATER SUPPLY MUST CONFORM TO LOCAL PLUMBING RULES,
REGULATIONS AND STANDARDS.
The following specifications for water supply are required:
Water Connections: ½” BSP (Aus/Eur), ½” NPT (USA) male connection supplied
suitable for a compression fitting.
Water Supply: 100kPa (15psi) – 800 kPa (115psi) 10L/min (2.6 gal/min) MINIMUM
20L/min (5.3 gal/min) RECOMMENDED
Water Supply Temperature: 40°C (105°F) MAXIMUM
Water Supply Salinity: 100 to 1150S/cm
WATER SUPPLY FILTRATION
The Installer must provide an inlet water filter in the water supply line,
external to the cooler, to prevent any debris from entering and damaging
cooler components.
Important! Flush the water pipe to remove any contaminants (swarf, filings or
dirt) before final fitting. Contaminants can lodge in the inlet solenoid
valve, preventing it from functioning correctly.
The cooler’s water management system is designed to use water that is suitable
to be classified as potable’ and fit for human consumption. If alternative water (including rain water) is to be used that contains unusually high or low levels of salinity, hardness, acidity or chemical contaminants, then additional filtration or treatment systems should be employed to render the water
potable’.
WATER HAMMER
Not all installation pipeworks are the same, and some may require additional
prevention against water hammer. If water hammer is a problem, it is the
responsibility of the Installer to fit an appropriate water hammer arresting
device external to the cooler.
DO NOT OVERTIGHTEN
OR CROSSTHREAD
COMPRESSION FITTINGS
ONTO THE PLASTIC WATER INLET NIPPLE.
ACCESS COVER FOR DRAIN VALVE
CONNECTION
REAR VIEW
WATER CONNECTION 1/2″ MALE NIPPLE
(Water connection may require an adaptor to suit local pipe sizes)
200mm
660mm (26″)
ILL1940-B
WATER SUPPLY PRESSURE REGULATION
The Installer must provide a pressure regulator in the water supply line adjacent to the cooler to regulate water supply pressures between 100kPa (15 PSI) and 800kPa (115 PSI).
Important! Water pressures which are lower than 100kPa (15 PSI) will prevent the inlet solenoid valve from opening.
Important! Water pressures which are higher than 1200 kPa (175 PSI) and/or
water temperatures which are higher than 40ºC (105ºF) risk inlet solenoid
valve failure.
Water pipes installed on the outside of a building, or any other exposed
location, shall have adequate insulation to protect against freezing in the
winter and solar radiation heating in the summer.
If a non-return valve is installed in the water supply line, it is recommended that a suitable pressure relief valve is also installed between the cooler and the non-return valve to limit the pressure rise associated with the heating effects of ambient temperature and solar radiation.
WATER SUPPLY ISOLATION
The Installer must provide a manual 1/4 turn ball type shut off valve (do not
use a stop cock) in the water supply line adjacent to the cooler, subject to
local plumbing regulations. This allows the water supply to be isolated
whenever work needs to be done on the cooler.
In areas where temperatures can cause water supply pipes to freeze, a drain
down facility should be provided during the installation. This drain down
facility must be activated prior to freezing conditions to avoid possible
damage to the cooler components.
16 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
WATER REQUIREMENTS
WATER DRAIN INSTALLATION
The cooler requires a permanent water drain to be connected. A built-in drain
valve, controlled by the water management system, releases water from the
cooler when required. INSTALLATION OF THE WATER DRAIN MUST CONFORM TO LOCAL
PLUMBING STANDARDS. Drain Connections: The cooler installation kit contains
components to configure the drain valve discharge to one of the following
options: – Down or Rear Discharge – 1.5″ (40mm) BSP Male or 1.5″ Flexible
Coupling. Drain Rate: 15 L/min (4 gal/min) Important! Water drained from the
drain valve is high in salinity and must be carried away to a suitable
discharge point on the building or property. Never drain the water directly
onto the roof
ILL2442-E
ILL2443
The removable access panel should be re-assembled after drain line
installation. Important! Drainage systems with long pipe runs, multiple entry
points, and/or incorporating traps shall use a tundish or similar device to
create a 25mm (1″) air-gap between the bottom of the drain valve and the
drainage system.
ILL3938
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 17
COOLER CONTROL COMPONENTS
FAN SPEED MANAGEMENT SYSTEM
The cooler fan is driven by an electronically commutated DC motor with
integrated variable speed drives (VSD) that allows for 0-10Vdc speed control.
The fan speed is controlled by the inputs from the Primary Control Method
(e.g. Multi-Magic Wall Controller). Depending upon the control type, speed
control is either continuously variable or in 10 discrete speed steps (Speed
1-10).
If, when commanded to start, the fan start delay option is enabled, the fan
will remain off until the delay timer has expired. Upon starting, the fan will
initially run at a fixed slow speed for 30 seconds before increasing to the
requested speed.
If pre-wet is enabled, the supply fans will remain at the fixed slow speed
until the pre-wet cycle is complete.
WATER MANAGEMENT SYSTEM
The cooler contains multiple parts to supply, distribute and manage the water
needed for the heat exchangers.
Water Inlet Solenoid Valve
The inlet solenoid valve allows water into the water reservoir. It is open
during the following phases.
· Initial Tank Fill Trigger: Entering IEC or DEC mode.
· IEC Tank Fill Trigger: Indirect Watering Cycle = TANK FILL.
· DEC Only Tank Fill Trigger: Low Probe = WET.
Once open, the inlet solenoid valve will remain open until the water high
probe has detected water for at least 5 seconds.
If the water drain valve is open, the inlet solenoid valve will remain closed.
Indirect Pump Control (IEC Watering Cycle)
The indirect pumps move water from the reservoir to the 3 indirect heat
exchangers.
The indirect heat exchangers do not require continuous watering and the pump
runs on the following cycle
· Tank Level OK – Water filled to high probe and waiting for next IEC pump
cycle to start.
· Indirect Pump Running (60 seconds).
· Core Drain – IEC pump stopped and excess water is draining back to the
reservoir (1 minute 30 seconds)
· Tank Fill – IEC pump stopped and inlet solenoid valve open and re-filling to
high probe (6 minutes 30 seconds)
Total IEC pump on time = 1 minute
Total IEC pump off time = 8 minutes
Direct Pump Control (Supercool coolers only)
The direct pump moves water from the reservoir to the Chillcel® media. When
running in DEC mode the direct pump runs continuously. Excess water from the
Chillcel® media drains back to the reservoir.
Water Salinity Control
As water evaporates from the heat exchangers, the salinity of the remaining
water naturally increases.
The water management system uses the 3-pin water probe to measure water
conductivity as a proxy for salinity. The probe can sense conductivity down to
9 µS (about 4ppm) .
Water conductivity is updated every time water reaches the high probe and,
when it exceeds the upper set point, a salinity drain cycle will start.
Chlorinator Control
The chlorinator is a pair of specially treated plates. When energised and
submerged in water, electrical current flows between them generating chlorine
which is known to kill bacteria in water supplies.
The chlorinator is active when the cooler is in IEC mode, AND the water level
is above the bottom probe AND the water conductivity is >1500 µs/cm.
If the water conductivity remain <1500µs/cm for 24 hours a clean tank drain
cycle will start.
Water Tank (Reservoir) Drain Valve
The drain valve will automatically open when power is first applied to the
cooler. It will close again when IEC or DEC mode is enabled.
During a salinity drain cycle, the drain valve opens until the water level
falls below the low probe, then the drain valve closes immediately, and inlet
solenoid valve opens to refill the reservoir with fresh water.
During a clean water drain cycle, the drain valve remains open for 10 minutes,
after which the inlet solenoid valve opens to refill the reservoir with fresh
water.
The drain valve will open if it has been 3 days since IEC or DEC mode was last
run.
18 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
COOLER CONTROL COMPONENTS
CONTROL COMPONENTS
Cooler logic and controls are handled by a PLC in conjunction with a Water Manager PCBA, both located in the controls enclosure.
PLC
WATER MANAGER PCBA
INPUT AND OUTPUT TERMINALS
A series of input and output terminals are located on the door of the controls
enclosure.
See MULTI-MAGIC CONTROLS for terminal functions.
ILL3940
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 19
MULTI-MAGIC CONTROLS
MULTI-MAGIC PLC
10
CONTROL SCREEN
This screen allows the user to select the cooler’s primary input control
method, including controlling the cooler manually from the PLC via Local Mode.
6
1
7
2
8
3
9
4
5
ILL3622-A
Item Description
Item Description
UP moves cursor up to next
1
variable or increase value in 6 Green LED Power Status
edit mode
DOWN moves cursor down to
Red LED Fault Status.
2
next variable or decrease value 7 Number of flashes indicates
in edit mode
fault code
3
RIGHT opens the next page
8 Yellow LED
4
LEFT opens the previous page
9
Green LED Flashes if wall control/MODBUS primary is connected
5
OK (ENTER) select/edit value
10
USB Type A for USB memory stick
For all PLC screens:
· Use the navigation UP/DOWN buttons to scroll through the options
· Push the OK button to edit the option. · Use the UP/DOWN buttons to change
the value of the option. · Push the OK button again to confirm the selection
and exit
edit mode.
Item Description
ILL3624
Item Description
Primary Input Control Method;
LOCAL 1 WALL = Multi-Magic Wall Controller
BMS = Low Voltage BMS Modbus BACnet
4 PLC Software Revision
Cool Mode
Vent = Fan only.
Indirect = Fan & Indirect Evaporative
2 Cooling Direct = Fan & Direct Evaporative
5
Message Bar. Shows current cooler status.
Cooling*
Supercool = Fan & Indirect & Direct Evaporative Cooling*
Fan Speed
If Control Method = Local; Sets Fan Speed 0-10
3
Otherwise display 0-100% (BMS / MODBUS)
or display 0-10 (Wall Controller / BACnet)
Fault.
6 Displays if a fault condition is active.
*NOTE. Direct Cool Mode and Supercool Mode are available for Supercool enabled coolers only.
IMPORTANT! The cooler can only accept control inputs from the one primary
control method selected on the CONTROLS screen, however control outputs are
available to be read across all methods.
For example, when Wall Controller is selected, the cooler will only accept
inputs (e.g. Fan Speed) from a Multi-Magic Wall Controller, whereas outputs
(e.g. Drain Valve status) can be read by a 3rd party Modbus device.
Use the navigation LEFT/RIGHT buttons to switch between the “CONTROL”,
“MONITOR”, “SENSORS” and “HISTORY” screens.
To return to the previous menu screen long press the LEFT button
20 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
MULTI-MAGIC CONTROLS
MONITOR SCREENS
These screens allows the user to see the status of the cooler components.
SENSOR SCREENS
These screens allow the user to configure up to four 0-10Vdc input channels,
labelled S1 to S4, for use with optional sensor accessories.
Item Description
Item Description
ILL3623
Displays status of the
1
Inlet Water Solenoid Valve. Image shows running water
into tank when valve is open.
Displays the tank water level.
Image empty when water not detected at low probe.
2 Image half full when water detected at low probe only.
Image full when water detected at both low and high probes.
Displays status of the
3
Drain Valve. Image shows water emptying from tank when
valve is open.
Displays the status of the pumps.
4 Image shows flowing water when the Indirect Pump (IEC) and/or Direct Pump
(DEC) is running.
Item Description
Displays water salinity level 1 (µS/cm) measured by 3 pin
probe.
Displays status of the
Chlorinator. ON/OFF 2
OK
FAULT
Item Description
ILL3870
3
Water Manager PCBA Software Revision
4
Displays PWM of the Chlorinator 0…100%
Tag
Description
ILL3710-C
Ambient Air Sensor
AMBNT-T Temperature, 0-10V, -40…+70C or -40…+158F
AMBNT-H Relative Humidity, 0-10V, 0…100% rh
Room Air Sensor
ROOM-T Temperature, 0-10V, 0…+50C or +32…+122F
ROOM-H Relative Humidity, 0-10V, 0…100% rh
Supply Air Duct Sensor
SPLY-T
Temperature, 0-10V, 0…+50C or +32…+122F
SPLY-H
Relative Humidity, 0-10V, 0…100% rh
Differential Air Pressure Sensor
PRESSURE Pressure, 0-10V, 0….+500Pa or 0….+2.00″wg
Temperature and Relative Humidity sensors require two input
channels. When configuring the first channel for Temperature, the second
channel is automatically configured for Relative Humidity.
Pressure sensors require only one input channel.
Installing sensor accessories does not automatically activate additional sensor functionality. Customers require a control method (e.g. Multi-Magic Wall Controller or 3rd Party Building Management System) to use the measured values as required.
See separate Installation Instructions for each type of sensor for example functions.
HISTORY SCREENS
These screens allow the user to view time stamped records of the coolers fault
code history and water drain history Each history can be reset by selecting
the CLEAR button.
Item Description
Item Description
ILL3931
Displays the status of the fan motors. 1 0-10Vdc analogue output from the PLC to the supply fan (SF)
CW-H Supply Fan (SF) Status
2
OK
FAULT
ILL3930
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 21
MULTI-MAGIC CONTROLS
CONTROL METHOD OPTION 1 (WALL)
MULTI-MAGIC WALL CONTROLLER (WALL)
SETTING DEVICE NODE ADDRESS (WALL)
When using the Multi-Magic Wall Controller, each cooler on the RS-485 network
requires a unique Node Address.
Push and hold the RIGHT button until the password screen is displayed.
ILL3872
The Multi-Magic Wall Controller, (supplied separately) can control up to a
maximum of 15 MultiMagic coolers acting as a Primary Controller over a Modbus
RS-485 network. It incorporates sensors to automatically regulate local zone
temperature and relative humidity. Ensure “WALL” is selected on the CONTROL
screen.
Refer to the RS-485 wiring rules section in this manual for communication
cable installation instructions and refer to installation literature provided
with the Multi-Magic Wall Controller for additional setup instructions.
Use the LEFT/RIGHT and UP/DOWN buttons to enter password “7378” and push OK to
display the SETUP screen.
Use the UP/DOWN buttons to select COMMUNICATION and push OK.
Use the UP/DOWN buttons to select NODE ADDRESS. Push OK to activate the field.
Use the UP/DOWN buttons to set a unique value for each cooler and push OK.
Note: Baud Rate must be 38400 Parity must be NULL
Use the UP/DOWN buttons to select SAVE. Push OK to activate the field. AFTER
CHANGING NODE ADDRESS, CYCLE POWER TO COOLER TO SAVE CHANGE.
22 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
Once set, the cooler NODE ADDRESS will appear on the CONTROLS page.
ILL3665
MULTI-MAGIC CONTROLS
CONTROL METHOD OPTION 2 (MODBUS)
3rd PARTY MODBUS RS-485 PRIMARY CONTROL
COMMUNICATION SETUP (MODBUS)
All secondary devices (coolers) on the Modbus RS-485 network requires a unique
Node Address and communication setting which match the 3rd Party Primary
Controller.
Push and hold the RIGHT button until the password screen is displayed.
ILL3743
The basic functions of cooler can be controlled via a 3rd Party Modbus RS-485
Primary Controller.
Ensure “MOBUS” is selected on the CONTROL screen.
Modbus control registers are available for.
· Vent Mode
· IEC Cool Mode
· DEC Cool Mode
· Fan Speed (0-100%)
· Fault Code Reset
· Manual Drain
Note: DEC Cool Mode only operates on Supercool coolers
Additional read only registers are available for monitoring the status of the
connected coolers. See Appendix C for the full register list.
Refer to the RS-485 wiring rules section in this manual for communication
cable installation instructions
Use the LEFT/RIGHT and UP/DOWN buttons to enter password “7378” and push OK to
display the SETUP screen.
Use the UP/DOWN buttons to select COMMUNICATION and push OK.
Use the UP/DOWN buttons to and push OK to activate the available fields. Set a
unique NODE ADDRESS for each cooler. Set BAUD RATE and PARITY values to match
the Primary Modbus Controller.
Once finished select SAVE. Push OK AFTER CHANGING COMMUNICATION SETTINGS,
CYCLE POWER TO COOLER TO SAVE CHANGE.
Once set, the cooler NODE ADDRESS will appear on the CONTROLS page.
ILL3904
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 23
MULTI-MAGIC CONTROLS
CONTROL METHOD OPTION 3 (BACNET)
3rd PARTY BACnet MS/TP or BACnet IP PRIMARY CONTROL
BACNET MS/TP COMMUNICATION SETUP
With BACnet MS/TP selected
Press RIGHT button.
ILL3905
The basic functions of cooler can be controlled via BACnet using either BACnet
MS/TP or BACnet IP protocols. Ensure “BACNET” is selected on the CONTROL
screen. BACnet control objects are available for. · Cooler ON/OFF · Vent Mode
· IEC Cool Mode · DEC Cool Mode (Supercool only) · Fan Speed (0-10) · Fault
Code Reset · Manual Drain Additional monitoring objects are available for the
status of the connected coolers. See Appendix D for the full object list.
BACNET PROTOCOL SELECTION Push and hold the RIGHT button until the password
screen is displayed.
Use the UP/DOWN buttons to and push OK to activate the available fields. Set a
unique NODE ADDRESS for each cooler. Set BAUD RATE and PARITY values to match
the BACnet Controller.
Once finished, select SAVE. Push OK AFTER CHANGING COMMUNICATION SETTINGS,
CYCLE POWER TO COOLER TO SAVE CHANGE.
Once set, the cooler NODE ADDRESS will appear on the CONTROLS page.
Use the LEFT/RIGHT and UP/DOWN buttons to enter password “7378” and push OK to
display the SETUP screen.
Use the UP/DOWN buttons to select COMMUNICATION and push OK.
Use the LEFT/RIGHT and UP/DOWN buttons to 1. Select either BACnet MS/TP or
BACnet IP 2. Set the NAME to Cooler 1, Cooler 2, Cooler 3 etc.
ILL3907
BACNET IP COMMUNICATION SETUP
With BACnet IP selected
Press RIGHT button.
Use the UP/DOWN buttons to and push OK to activate the available fields. Set a
unique Ethernet IP ADDRESS for each cooler. Set GATEWAY and NETMASK ADDRESS to
match the BACnet Controller.
ILL3906
Note. Only one BACnet protocol may be active at a time.
24 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
ILL3908-A
MULTI-MAGIC CONTROLS
RS-485 NETWORK SETUP
The Multi-Magic Wall Controller, 3rd Party MODBUS and BACnet MS/TP control
options all use the RS-485 serial protocol.
RS-485 CABLE SPECIFICATIONS
The Installer must supply communication cable between the primary controller
and connected coolers to the following specification.
· Suitable for RS-485 applications · Minimum 1 twisted pair (TP) and a third
conductor · Copper conductors · 0.5 mm2 / AWG 20 · Braided shield with drain
wire · Characteristic impedance 120 · Nominal capacity between conductors 89
pF/m · Nominal capacity between conductors and shielding 161pF/m Note: Non-
shielded cables are not protected against electromagnetic interference which
can cause signal degradation.
RS-485 TERMINATING RESISTORS
Daisy-chained RS-485 networks require two 120 terminating resistors, one at
the start and one at the end of the communication chain.
Attach a 120 terminating resistor between the “+” and “-” terminals on the
Primary Controller (e.g. Wall Controller)
Attach a 120 terminating resistor between the “+” and “-” terminals on the
last cooler on the network.
Do not fit a 120 terminating resistor to coolers installed between the Primary
Controller and the last cooler.
RS-485 CABLE CONNECTIONS
The RS-485 serial terminals are located on the inside of the control enclosure
door.
Use the twisted pair for the +’ and
-` signal terminals.
Use the 3rd conductor for the signal GND terminals.
Attach the braided shield / drain wire to the EARTH point at one end only.
ILL3677-B
See Appendix A for an example wiring schematic.
ILL3888-A
RJ45 ETHERNET SETUP
The BACnet IP (BCN) control option uses the RJ45 ethernet port, located on top
of the Multi-Magic PLC.
MODBUS RS-485 Terminal Details Type Stripping Length Cable Termination 2x Conductors Cross Section (Flexible)
ILL3705-B
Push-In 8 mm – 10 mm / 5/16″ – 3/8″ Ferrule with plastic sleeve 0.5 mm2 / 20
AWG
ETHERNET CABLE SPECIFICATIONS
The Installer must supply ethernet cable between the primary controller and
connected coolers to the following specification. · Cat 5, 5e, 6 or 6e
shielded
ETHERNET CABLE WIRING RULES
· Maximum single cable length between devices is 100m. · Each cooler has a
single RJ45 ethernet port, so an ethernet
switch or router is required
RS-485 CABLE WIRING RULES
The following rules must be applied when setting up a RS-485 network:
· Communication wiring must be kept separate from AC power wiring.
· Always route communication cables at least 300mm (12″) away from high
voltage cables and high-power machines.
· Crossover high power cables at right angles. · Maximum cable length from
Wall Controller / Primary to first
cooler is 100m (330ft). · Maximum cable length between each cooler is 100m
(330ft). · Coolers must be connected in daisy-chain style, not star or
multi-drop..
ILL3909-A
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 25
MULTI-MAGIC CONTROLS
CONTROL METHOD OPTION 4 (BMS)
LOW VOLTAGE BUILDING MANAGEMENT SYSTEM
ILL3681
The basic functions of cooler can be controlled via a low voltage Building
Management System and the series of terminals located on the control enclosure
door. Ensure “BMS” is selected on the CONTROL screen.
BMS CONTROL INPUTS
The cooler operating mode is set via the IEC, DEC and SPD input terminals with the following logic.
PRIMARY CONTROL COOLER FUNCTION METHOD
BMS OFF
IEC
DEC SPD (Vdc)
TERMINAL TERMINAL TERMINAL
FALSE
FALSE
0
BMS VENT
FALSE
FALSE
1.3
BMS INDIRECT COOL ONLY
TRUE
FALSE
1.3
BMS DIRECT COOL ONLY*
FALSE
TRUE
1.3
BMS BMS BMS W/C
INDIRECT & DIRECT COOL CLEAR FAULT
TRUE FALSE
MANUAL DRAIN VENT FIXED LOW SPEED
FALSE TRUE
TRUE FALSE FALSE FALSE
1.3
0.9 – 1.3 for 10 seconds 0.5 – 0.9 for 10 seconds
N/A
W/C VENT FIXED HIGH SPEED FALSE
TRUE
N/A
*Note: DEC Cool Mode only operates on Supercool coolers
Warning: The BMS IEC and DEC input terminals are nonisolated dry contacts. Do
not apply an external power supply, instead use a switch to connect the input
terminal to the BMS GND terminal.
BMS FAN SPEED INPUT
The cooler fan speed is set by applying an analogue 0-10Vdc signal to the Fan
Speed Input terminal, with the following logic;
ID FAULT FAULT
TYPE
DIGITAL OUTPUT DRY CONTACT
FUNCTION
Fault Output. Configurable NC or NO. See Settings
BMS GND GROUND
BMS SPD BMS IEC BMS DEC
ANALOGUE INPUT 0-10Vdc DIGITAL INPUT DRY CONTACT DIGITAL INPUT DRY CONTACT
Fan Speed Input
Cooler Operating Mode. See Logic Table
BMS FAULT OUTPUT
The fault output is a pair of dry contact terminals which can be used to
switch an external power supply.
Maximum Voltage: 250 Vac Maximum Current: 3A Minimum Switching Capacity: 100mA
/ 5Vdc
The fault output can be configured to be Normally Open (close in Fault state)
or Normally Closed (open in Fault state). See the Commissioning Section for
instructions on how to set.
The output is available for use in all Primary Control Methods, not just BMS.
For example, a Wall Controller can be used for local zone control, with the
fault signal monitored by a central building management system.
BMS FAN SPEED
OFF 1 2 3 4 5 6 7 8 9 10
MINIMUM VOLTAGE
Vdc 0.00 1.30 1.80 2.70 3.60 4.50 5.40 6.30 7.20 8.10 9.00
MAXIMUM VOLTAGE
Vdc 1.29 1.79 2.69 3.59 4.49 5.39 6.29 7.19 8.09 8.99 10.00
BMS CABLING REQUIREMENTS
To avoid signal degradation use shielded, properly grounded cables for all
analogue and digital inputs and outputs. Route input and output cables
separately from high voltage power cables. Interconnection wiring shall be
separated by reinforced insulation to any live parts.
BMS Terminal Details Type Stripping Length Cable Termination 2x Conductors Cross Section (Flexible)
Push-In 8 mm – 10 mm / 5/16″ – 3/8″ Ferrule with plastic sleeve 0.5 mm2 / 20 AWG
See Appendix B for an example BMS wiring schematic.
26 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
MULTI-MAGIC CONTROLS
CONTROL METHOD OPTION 5 (LOCAL)
PLC LOCAL CONTROL
MANUAL DRAIN
All control modes provide an option to complete a manual tank drain.
When triggered, the drain valve will open and stay open for at least 10
minutes.
During this period, all pumps will stop and the inlet solenoid valve will
remain closed, however the fan will continue to run at the requested speed.
Once triggered, it is not possible to close the drain valve again until the 10
minutes as elapsed.
After 10 minutes the cooler will resume running in requested operating mode.
ILL3682
The basic functions of cooler can be manually controlled from the CONTROL
screen. This mode is recommended for initial setup and servicing only.
Ensure “LOCAL” is selected on the CONTROL screen.
Select the required COOL-MODE
· Vent = Fan only. · Indirect = Fan & Indirect Evaporative Cooling · Direct =
Fan & Direct Evaporative Cooling · Supercool = Fan & Indirect & Direct
Evaporative Cooling.
For all modes, set the SPEED between 0 and 10 to run the fan.
*Note: Direct and Supercool Mode only operates on Supercool coolers.
ILL3910
To start a Manual Drain select the button under the tank icon on the MONITOR-
TANK screen.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 27
MULTI-MAGIC CONTROLS
CHANGING COOLER SETTINGS
Push and hold the RIGHT button until the password screen is displayed.
Use the navigation LEFT/ RIGHT and UP/DOWN buttons to enter password “7378”
and push OK to display the SETUP screen.
Use the navigation UP/DOWN buttons to move the cursor to SETTINGS and push OK.
PRE-WET
Upon cooler start-up, Pre-Wet first ensures the water tank is full and then
runs an extra 6-minute start up pump cycle to saturate the heat exchanger
cores.
During this Pre-Wet phase, the supply fan will be restricted to Speed 1
regardless of controller input.
Pre-Wet ensures only cooled air is delivered, at the expense of a longer start
up time.
The Pre-Wet sequence will run again if the pumps have not run in the last 30
minutes.
FAN START DELAY & RUN OUTPUT RELAY
The Fan Start Delay can be a positive or negative timer.
If a positive timer is selected, the fan run output relay changes state but
the fan does not start until the timer has expired.
For example, this can be used to open or close 3rd party dampers before the
cooler fans start.
FAINECSPEED INPUT
Use the navigation LEFT/ RIGHT buttons to move between Pages 1, 2 and 3.
Use the navigation UP/DOWN buttons to move the cursor to the required setting.
Push OK to activate the field.
Use the navigation UP/DOWN buttons to set a unique value. Push OK to save the
setting
Long press LEFT to return to the previous screen.
SETTING
ILL3678
VALUES
LANGUAGE
English (Default) Spanish Italian French Portuguese
PRE-WET
Enabled Disabled (Default)
SALINITY DRAIN SET POINT
4275 uS/cm (Default) 2305 uS/cm
Normally Open (Default) BMS FAULT STATE OUTPUT LOGIC
Normally Closed
SENSOR UNITS
Metric (Default) Imperial
DATE TIME FAN START DELAY FAN RUN OUTPUT LOGIC BMS LOCK SPEED
Set for use with Fault Codes and Drain History
0s (Default) -120s, -90s, -60s, -30s +30s, +60s, +90s, +120s Normally Open
(Default) Normally Closed
HIGH: 0-10 (Default 0) LOW: 0-10 (Default 0)
28 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
RELAY OUTPUT USER SELECTABLE N/C or N/O
USER SELECTABLE +30s, +60s, +90s, +120s
FAN RUN
If a negative timer is selected, the fans start when requested, but the fan
run output relay does not change state until the timer has expired. For
example, this can be used to ensure internal building pressure is maintained
before opening 3rd party relief vents.
FAIENC SPEED INPUT
FAN RUN
USER SELECTABLE -30s, -60s, -90s, -120s
RELAY OUTPUT USER SELECTABLE N/C or N/O
The fan run output is a pair of dry contact terminals which can be used to
switch an external power supply. Maximum Voltage: 250 Vac Maximum Current: 3A
Minimum Switching Capacity: 100mA / 5Vdc The fan run output can be configured
to be Normally Open (close in when fan runs) or Normally Closed (open when fan
runs). The output is available for use in all Primary Control Methods,
MULTI-MAGIC CONTROLS
BMS LOCK SPEED
BMS Lock is a special mode for use with a Multi-Magic Wall Controller.
When Wall Controller is selected as the Primary Control Method, use the BMS
IEC or DEC input terminals on any connected cooler to remotely lockout the
Wall Controller.
When applied, no cooler control from the Wall Controller is possible and the
cooler can be configured to either shutdown or run in VENT mode at one of two
different fixed speeds
For example, if low speed is set to 3 and high speed is set to 8.
LOW SPEED HIGH SPEED
SETTING
SETTING
(0-10)
(0-10)
0
0
0
0
0
0
3
8
3
8
IEC TERMINAL
FALSE TRUE TRUE FALSE TRUE
DEC TERMINAL
TRUE FALSE TRUE TRUE FALSE
COOLER FUNCTION
SHUTDOWN SHUTDOWN SHUTDOWN VENT SPEED 3 VENT SPEED 8
This feature may be useful when Building Managers wish to remotely shutdown coolers during certain hours, enable overnight building purges or when Climate Wizard products are used as blowers for in line heaters during the winter season.
For groups of coolers running from a single Wall Controller
· Each cooler can be set to run at different BMS Lock Speeds.
· The IEC and/or DEC input can be applied to any single cooler in the group
and all coolers will enter BMS Lock Mode.
MESSAGE BAR CONTENTS
ILL3936
The MESSAGE BAR contains useful information about the current cooler state.
The MESSAGE BAR will cycle through all active messages.
MESSAGE STANDBY VENT MODE TANK INITIAL FILL PRE-WET FS LIMITED FAN START DELAY
INDIRECT PUMP RUNNING
CORE DRAIN TANK FILL-IEC TANK LEVEL OK TANK FILL-DEC DIRECT PUMP RUNNING
SALINITY DRAIN CLEAN WATER DRAIN TANK DRAIN REMOTE SHUTDOWN BMS LOCK HIGH
SPEED BMS LOCK LOW SPEED
DESCRIPTION
Cooler is ON but no control input active.
Fan is running but no cooling stage is on.
Inlet Water Solenoid is on and water is entering the tank. Pumps will not
start until the tank is full.
Pre-Wet is enabled. The pumps are running for an extra 6 minutes whilst the
fan speed is limited.
Fan start delay is enabled. Fans will start after the delay timer has expired.
IEC COOL MODE IEC pump is running. Pump cycles ON for 60 seconds and OFF for
100 seconds.
IEC COOL MODE IEC pump have just turned OFF and water is returning back to
tank.
IEC COOL MODE Inlet Water Solenoid is on and water is entering the tank.
IEC COOL MODE Tank is full, waiting for IEC pumps to start.
DEC COOL MODE Inlet Water Solenoid is on and water is entering the tank.
DEC COOL MODE DEC pump is running. Pump runs continuously.
Tank water has reached the maximum salinity level and a partial tank drain and
fill cycle is in progress.
The chlorinator has not run for 24 hours and a complete tank drain and fill
cycle is in progress.
3-day tank drain delay or manual drain triggered.
Multi-Magic Wall Controller has been locked by a BMS input. Refer to Wall
Controller manual.
Multi-Magic Wall Controller has been locked by a BMS input to VENT Mode Refer
to Wall Controller manual.
Multi-Magic Wall Controller has been locked by a BMS input to VENT Mode Refer
to Wall Controller manual.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 29
MULTI-MAGIC CONTROLS
WATER MANAGER LED STATES
FAULT CODE DISPLAY
Active Fault Codes will cause the FAULT button to appear on the CONTROLS page.
Selecting the FAULT button will open the ACTIVE FAULTS page, listing all the
current active faults.
Select the INFO button to display a QR code.
Scanning the QR Code will direct users to the Seeley Service Technical Support
website.
TRI-COLOUR RED LED LED
OPERATION PHASE
LED
INITIAL BOOT UP.
RED
FIRST 30-45 SECONDS AFTER POWER UP
TRI-COLOUR
NORMAL RUNNING
RED TRI-COLOUR
ILL3686-A
STATE ON FLASHING GREEN ON ON AMBER
ILL3653
Select the RESET button to reset each active fault. Cycle the cooler power to
reset all active faults.
All faults are added to the FAULT CODE HISTORY screen.
On all screens, long press the LEFT button to return to the CONTROL page.
Note: Both PCBA LEDs are continuously ON once communication between the PLC and PCBA has been established.
30 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
MULTI-MAGIC CONTROLS
FAULT CODE DESCRIPTIONS
All faults below shut the cooler down unless stated. Fault codes labelled as Running Faults will allow the cooler to continue to run, however performance may be reduced.
FAULT CODE Fault Code 1 Fault Code 2
Fault Code 3
Fault Code 4
Fault Code 5
FAULT DESCRIPTION
SUGGESTED REMEDY
PLC PCBA COMMUNICATION FAILURE
Cooler PLC has lost communication with PCBA fitted inside control box for at
least 1 minute.
Check LED status on PCBA. Check communication wiring between PLC and PCBA Replace PCBA
FAILURE TO DETECT WATER AT LOW PROBE No water at low probe 20 minutes after solenoid valve opening.
Check water supply on. Check solenoid valve open. Check drain valve closed. Check water management probe position relative to drain valve overflow. Clean water management probe.
FAILURE TO DETECT WATER AT HIGH PROBE No water at high probe 30 minutes after water detected at low probe.
Check water supply on. Check solenoid valve open. Check water management probe position relative to drain valve overflow. Clean water management probe. Check water supply pressure sufficient to maintain tank capacity.
FAILURE TO CLEAR LOW PROBE DURING DRAIN Water still detected at low probe 20 minutes after drain opened.
Check drain valve open. Check drain pipework not blocked. Check solenoid valve closed. Clean water management probe.
WATER DETECTED AT HIGH PROBE BUT NOT LOW PROBE Clean water management probe. Water still detected at high probe 30 minutes after water not detected at low probe.
Fault Code 7 SUPPLY MOTOR ERROR Motor has been in fault state for at least 1
minute.
Fault Code 10 CHLORINATOR FAULT Chlorinator has reached end of life or is
experiencing a short circuit. Running Fault
Fault Code 11 ROOM AIR SENSOR FAULT Temperature or Relative Humidity input
value has been 0V or 10V for at least 10 minutes. Running Fault
Check Motor Power Cable connections. Check Motor Communications Cable
connections. Check MONITOR screen to identify which motor is in fault.
Check cooler PLC flashing LEDs for fault type. Check no debris between
chlorinator plates. Replace Chlorinator
Check Sensor values at PLC cooler screen “SENSORS” menu Check Sensor wiring If
no Sensor fitted, check Sensor has not been accidentally enabled on Wall
Controller and/or PLC
Fault Code 12 AMBIENT AIR SENSOR FAULT Temperature or Relative Humidity input
value has been 0V or 10V for at least 10 minutes. Running Fault
Fault Code 14 DUCT AIR SENSOR FAULT Temperature or Relative Humidity input
value has been 0V or 10V for at least 10 minutes. Running Fault
Fault Code 15 PRESSURE SENSOR FAULT Pressure input value has been 0V or 10V
for at least 10 minutes. Running Fault.
Check Sensor values at PLC cooler screen “SENSORS” menu Check Sensor wiring If
no Sensor fitted, check Sensor has not been accidentally enabled on Wall
Controller and/or PLC
Check Sensor values at PLC cooler screen “SENSORS” menu Check Sensor wiring If
no Sensor fitted, check Sensor has not been accidentally enabled the PLC.
Check Sensor values at PLC cooler screen “SENSORS” menu Check Sensor wiring If
no Sensor fitted, check Sensor has not been accidentally enabled the PLC.
Fault Code 16 COMMUNICATION FAILURE PLC has lost communication with Wall Controller for at least 5 minutes.
Ensure cooler is powered up.
Check communication cable connections including 120 Modbus terminating
resistors.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 31
COMMISSIONING
Owner Name: ………………………………………………………………….. Address: …………………………………………………………………………. ………………………………………………………………………………………… Dealer: …………………………………………………….. Date Installed: …………………………………………..
Telephone: ………………………………………………..
Installer: …………………………………………………… Model No: ………………………………………………… Serial No:
………………………………………………….
INSTALLATION CHECKLIST
This checklist only covers the key points to be observed during installation.
Always refer to the relevant sections of the installation manual for full
details.
COOLER LOCATION
The cooler is adequately supported, secure and level. The cooler is installed
in a position that allows adequate access for future maintenance and servicing
activities.
INTAKE AIR
The cooler will always receive a plentiful supply of fresh air. Inlet air
filters installed correct way round. Observe airflow direction arrow on filter
frame
SUPPLY AIR DUCTWORK
Vibration absorbing flexible connections are used for all duct connections to
the cooler All building penetrations are correctly flashed and sealed. If
flexible ducts are used, they are fully extended, hung correctly, with no
kinks, tight bends, or squashed segments. All duct joints are fully sealed
with no air leaks.
EXHAUST AIR
The cooler’s exhaust air is not likely to cause corrosion or damage to other
nearby items. The cooler’s exhaust air is not likely to re-circulate into the
air intake of the cooler. Exhaust caps fitted (CW-H15S PLUS only) If exhaust
air ductwork is fitted, the static pressure drop does not exceed 20Pa (0.08 in
wg).
ELECTRICAL SUPPLY
The electrical power supply installation adheres to all local and national
regulations The electrical power supply is wired back to the distribution
board on its own separate circuit. A mains isolation switch, with all pole
disconnection, has been installed adjacent to the cooler. The owner has been
instructed how they can electrically isolate the unit in case of an emergency.
Phase to Phase voltage has been measured and is within specification.
WATER SUPPLY
The water supply installation adheres to all local and national regulations
with no leaks at any fittings or valves. The water supply pipes were flushed
of any foreign materials before connection to the cooler was made. The water
is filtered as required. Static water pressure to each cooler always remains
between 100kPa (15psi) and 800 kPa (115psi) throughout the day. Opening and
closing the inlet water solenoid valve does not cause water hammer. Water flow
rates to each cooler always remains between 10L/min (2.6 gal/min) and 20L/min
(5.3 gal/min) throughout the day. An isolation valve has been installed
adjacent to the cooler. The owner has been instructed on how to isolate the
water supply to the cooler in case of emergency.
WATER DRAIN
The water drain installation adheres to all local and national regulations
with no leaks at any fittings or valves. Drain water pipes/hoses are free from
any restrictions (kinks) or blockages. The drain water does not discharge onto
the roof surface.
Signed by Installer: ………………………………………………………..
32 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
Commissioning Technician: …………………………………………….
COMMISSIONING
SETUP MENU ACCESS
Push and hold the RIGHT button until the password screen is displayed.
TEST MENU
Use the navigation LEFT/ RIGHT and UP/DOWN buttons to enter password “7378” and push OK to display the SETUP screen.
ILL3678
MULTI-MAGIC DEVICE TYPE
Prior to running the cooler for the first time, check the device type in the
PLC SETUP menu matches the cooler rating label.
Record the details
Product Family.
ILL3885-A
…………………………………………..
Model
…………………………………………..
Voltage
…………………………………………..
IMPORTANT: CW-H Supercool coolers are sold as one part
number, but can be configured in one of two ways, CW-H15S or CW-H15S PLUS.
Refer to the specifying consultants/
builders schedule of works or specification to confirm which configuration is
to be used.
TIME & DATE
To assist with fault code and drain history logs, set the time and date in the PLC SETTING menu.
Use the navigation LEFT/RIGHT and UP/DOWN buttons to set the Time, Date and Day.
Select SAVE to commit values to memory.
ILL3887-A
To assist with commissioning, each component on the cooler can be controlled
individually via the SERVICE – TEST MENU on the cooler PLC. Set TEST to ON to
control components. Use the LEFT/RIGHT buttons to access 2 pages
WATER MANAGEMENT SYSTEM CHECKS
Turn inlet water solenoid valve ON. Confirm water enters reservoir. Wait until
Tank Low Level (Tk Lo) probe changes state. Confirm Water Salinity reading is
greater than 100 uS/cm. Confirm Chlorinator is fully submerged at low water
level. Wait until Tank High Level (Tk Hi) probe changes state. Turn inlet
water solenoid valve OFF.
HEAT EXCHANGER FLUSH
To reduce the probability of unusual odours, foaming or water pull off, it is
recommended to flush new heat exchangers with fresh water and then drain the
reservoir. Turn Direct Pump (DRPump) ON (Supercool Coolers only) Confirm
Direct Pump starts. Run for 5 minutes to flush the Direct Heat Exchangers Turn
Direct Pump (DRPump) OFF
Turn Indirect Pumps (IDPump) ON Confirm both Indirect Pumps start. Run for 5
minutes to flush the Indirect Heat Exchangers Turn Indirect Pumps (IDPump) OFF
Set Drain to OPEN Confirm the drain valve opens Confirm water fully drains
from the reservoir.
SUPPLY FAN CHECKS
Set Supply Fan (SpFAN) to ON Set Speed initially to 1 and then progressively
increase to 10. Check for unusual or excessive sound output at various fan
speeds. Check for excessive vibration and/or rattle sounds.
ILL3937
Signed by Installer: ………………………………………………………..
Commissioning Technician: …………………………………………….
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 33
COMMISSIONING
AIR FLOW BALANCING
In order for the cooler to produce cool air it is mandatory that some of the
inlet air is forced to return through the indirect heat exchanger cores and be
exhausted to atmosphere. Therefore only a proportion of the total inlet air is
delivered into the cooled zone.
THIS PROPORTION IS CRITICAL TO ACHIEVING SATISFACTORY PERFORMANCE.
The supply air transition is equipped with a damper that can be adjusted to
‘balance’ the proportion of supply and exhaust air streams. Damper position is
controlled through a lever with locking screw located underneath the supply
air transition. The damper will need to be adjusted during commissioning
depending on the external static pressure of the duct system.
To balance the air flow.
1. Ensure all side panels and air filters are in place
2. Connect all external supply and exhaust ductwork.
a. Stand-alone Cooling: Fully open all supply air outlets in the entire
ductwork system.
b. Pre-Cooling: Ensure all main Air Conditioning plant fans are running at
full speed – consult with Building Manager and/or Air Conditioning contractor.
3. Using the cooler’s PLC, start the Climate Wizard in LOCAL and IEC modes at
Speed 10.
ILL3884-A
ILL2447-A
There is a hole in the right hand side of the supply air transition suitable
for manometer tubes for measuring pressure.
NOTE! Pressure measuring should be carried out using an accurate instrument,
either electronic or “inclined tube manometer”. DO NOT GUESS.
4. Wait approximately 5 minutes, to allow the cooler to complete the first water fill and the pumps to start.
5. Adjust the supply air transition damper until the pressure in the transition stabilises as follows:
a.CW-H10:
200 Pa (0.80 in wg static)
b.CW-H15:
175 Pa (0.70 in wg static)
c.CW-H15S: 175 Pa (0.70 in wg static)
d.CW-H15S Plus: 210 Pa (0.84 in wg static)
6. For multiple CW-H coolers connected to the same supply duct, it may be necessary to re-check and adjust the supply air transition pressures of all coolers after each cooler is set.
7. For stand-alone cooling, balance all customer’s supply air outlets in your usual manner. After balancing, check and adjust the CW-H damper back to the above values.
8. Lock the damper in its final position and record the final value
Supply Transition Pressure = …………………………..
Signed by Installer: ………………………………………………………..
Commissioning Technician: ……………………………………………
34 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
COMMISSIONING
MULTI-MAGIC COOLER SETTINGS
To aid future servicing it is recommended to record the PLC setting here.
SETTING PRIMARY CONTROL METHOD
LANGUAGE PRE-WET SALINITY DRAIN SET-POINT BMS FAULT OUTPUT LOGIC SENSOR UNITS
FAN START DELAY
FAN RUN OUTPUT LOGIC BMS LOCK SPEED (0-10)
VALUES Local (LCL) Wall Controller (W/C) Low Voltage BMS (BMS) High Level Modbus (MBS) BACnet (BCN) English (Default) Spanish Italian French Portuguese Enabled Disabled (Default) 4275 uS/cm (Default) 2305 uS/cm Normally Open (Default) Normally Closed Metric (Default) Imperial 0s (Default) -120s -90s -60s -30s +30s +60s +90s +120s Normally Open (Default) Normally Closed HIGH = LOW =
MULTI-MAGIC RS-485 SETTINGS
If used, record the PLC settings for Wall Controller, Modbus and BACnet MS/TP communication here.
SETTING
VALUES
NAME*
Default = Cooler 1 Actual =
Default = 1 Unique NODE ADDRESS (1…99)
Actual =
9600
19200
BAUD RATE
38400 (Default) 57000
76800
115200
NULL (Default)
PARITY
ODD
EVEN
120 TERMINATING RESISTORS
Wall Controller / Primary Last Cooler
- Applicable to BACNet MS/TP only
MULTI-MAGIC IP SETTINGS
If used, record the PLC settings BACnet IP communication here.
SETTING IP ADDRESS GATEWAY SUBNET MASK BACNET IP PORT
VALUES Default = 192.168.10.51
Actual = Default = 192.168.10.1
Actual = Default = 255.255.255.0
Actual = Default = 47808 (0xBAC0)
Actual =
CUSTOMER HANDOVER CHECKLIST
Run the cooler for at least 20 minutes in IEC and DEC mode at Speed 10 and
confirm,
Leaving temperatures are sufficiently cooler than ambient temperatures.
No unusual odours No visible water leaks. No excess water is draining from
overflow
Finally, confirm that
All the installation rubbish has been removed Any property damage reported
and/or repaired. The customer has been given a copy of the cooler manual
which includes Operation, Maintenance & Warranty details.
Signed by Installer: ………………………………………………………..
Commissioning Technician: ……………………………………………
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 35
MAINTENANCE SCHEDULE
MAINTENANCE FREQUENCY
Maintenance of an indirect evaporative cooler is essential in maintaining
proper performance and reliability.
All maintenance must be done by competent, qualified, licensed technicians, in
accordance with National and/or Local Regulations.
The frequency of service is largely dependent on the conditions under which
the cooler is operated. External factors, such as air and water quality, can
affect the serviceable life of the cooler and its components. In particular,
installations using hard water, usually defined as greater than 200mg/L, will
experience greater scaling problems requiring a more frequent cleaning regime.
Similarly, the amount and type of use can also have a significant impact. The
guidelines listed below are intended to provide help in formulating a proper
service regime. Local, and in some cases, individual factors should be taken
into account when deciding on the frequency of visits.
HEALTH REGULATIONS. In some regions, regulations require that evaporative air
coolers be serviced at specific intervals. Ensure all maintenance is done in
accordance with any local and national regulations.
TYPE OF INSTALLATION
MAINTENANCE SCHEDULE SERVICING FREQUENCY
AIR FILTERS
CHLORINATOR
COMMERCIAL / INDUSTRIAL INSTALLATIONS (Seasonal use)
COMMERCIAL / INDUSTRIAL INSTALLATIONS (All year use)
Maintenance Schedule servicing must be a minimum of twice a year, typically immediately before and after the summer season.
Air filters should be cleaned every month of operation and replaced every
year.
Chlorinators should be cleaned during each service and replaced every 4 years.
Maintenance Schedule servicing must be performed every 3 months.
Air filters should be cleaned every month and replaced every year.
Chlorinators must be cleaned during each service and replaced every 2 years.
While installation is not covered by warranty (e.g. duct work, roof
penetrations, electrical and water connections etc.), these items should be
checked as they can affect the performance (and/or safety) of the cooler. For
this reason, they are included in the Maintenance Schedule.
For access to Technical/Installation/Service Information register online at
www.seeleyinternational.com/service
WINTER OPERATION AND SHUTDOWN
Climate Wizard coolers cannot be used in any cooling mode (INDIRECT, DIRECT or
SUPERCOOL) in freezing conditions. In particular the inlet water solenoid
valve, pumps, and drain valve are likely to fail in such conditions.
It is recommended that, to prevent damage to cooler components, the following
tasks are completed before the start of the winter season.
1. Drain and clean the reservoir. 2. Drain down and isolate the water supply.
3. Isolate the power.
For installations requiring continuous operation through the winter, it is
possible to run the cooler in VENT mode down to -20oC (-4oF), however
customers must ensure the controls are not accidently set to any cooling mode
in these conditions.
36 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
MAINTENANCE SCHEDULE
MAINTENANCE CHECKLIST
DEFINITIONS
Clean – To wash and remove all dirt, grit or debris. Check/Inspect – To
visually inspect the item for correct operation, fitment and functionality.
Test – To turn the item on and off and confirm correct function. Replace – To
remove the existing item and replace with a specified genuine replacement
part. Note! It is important that only new Seeley International factory
authorised replacement parts be used in this cooler. Failure to do so may void
warranty, cause improper cooler performance, and unsafe operation.
SERVICE NO.
1
2
3
4
5
6
7
8
9
10
11
12
EXTERNAL INSPECTION
Check/Inspect the following parts for general deterioration, leaks, damage, corrosion, missing components, secure connections, and function.
Cooler Body
Supply Air Duct
Support Frames / Curb
Vibration Isolation
Roof Flashing
Isolation Switch
Circuit Breakers/Fuses
Power Cables
Communication Cables
Water Supply Pipe
Water Supply Strainer/Filter
Water Isolation Valve
Drain Hose Remove & Clean the following components.
Air Filters*
INTERNAL WATER DISTRIBUTION Check/Inspect the following for general condition, damage and secure connections.
Water Distribution Hoses Remove & Clean the following components
Pump Strainers
Water Probe Pins
Chlorinator Cell*
Tank Surfaces Test the following components
Water Probe Resistance Remove & Clean the following components
HEAT EXCHANGERS
Indirect Spreaders
Check/Inspect the following for general condition and damage. Supply Fan Blades Supply Motor Mounts Test the following. Supply Motor Spins Freely
FAN & MOTORS
- Air Filters and Chlorinators require replacement based on usage. Refer to frequency of service guidelines.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 37
MAINTENANCE SCHEDULE
SERVICE NO.
1
2
3
4
5
6
7
8
9
10
11
12
Test the following components service screen.
FUNCTIONAL TEST
Inlet Solenoid Valve 3-Pin Water Probe Drain Valve Indirect Pump Direct Pump Supply Fan Speed Control Check/Inspect the following whilst running at full speed.
No excessive noise No excessive vibration No water leaks Correct internal water levels
38 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
MAINTENANCE INSTRUCTIONS
COOLER CONTROL
Liaise with the Building Manager prior to starting a service. To avoid any
unintended cooler operation from commands received by remote controller, it is
recommended that the cooler is set to LOCAL control before performing any
maintenance.
ILL3682
To assist with maintenance and fault finding, each component of the cooler can
be controlled individually via the TEST MENU on the cooler PLC.
Push and hold the RIGHT button until the password screen is displayed.
QUARTERLY INSPECTION PROCEDURES
1. Drain the cooler reservoir by initiating a manual drain 2. Isolate and
lockout the power supply to the cooler. 3. Turn off the water supply. 4.
Remove the service access panels from both sides of the
cooler. 5. Clean the Pump Strainers & Impellers 6. Clean the Chlorinator
Blades 7. Clean the Water Management Probe 8. Clean the Water Reservoir 9.
Clean or Replace the Inlet Air Filters 10. Inspect the entirety of the cooler
body and external
components for general deterioration, leaks, damage, corrosion, and loose or
missing fasteners. 11. Re-fit the service access panel to both sides of the
cooler. Apply a liberal coat of anti-seize paste to the screw threads prior to
fitment. 12. Turn on the power and water supply. 13. Complete the cooler
commissioning sequence
SIDE VIEW – LHS
Cores Water Distribution Spreaders Reservoir access
Use the LEFT/RIGHT and UP/DOWN buttons to enter password “7378” and push OK to
display the SETUP screen.
Use the UP/DOWN buttons to move the cursor to SERVICE and push OK.
Water Inlet Solenoid Chlorinator Pumps
SIDE VIEW – RHS
Cores Water Distribution Spreaders Reservoir access
Use the UP/DOWN buttons to move the cursor to TEST MENU and push OK.
REAR VIEW
Core Access Panel
Pump Access Panel
Pump Access Panel
Core Access Panel
ILL1954-B
Water Management Probe Drain Valve Pumps
ILL2448-A
Set TEST = ON Use the UP/DOWN buttons to move the cursor between component and
push OK to change state.
Use the LEFT/RIGHT buttons to switch between different Test Menu screens.
Push and hold the LEFT button to return to the previous menu. Repeat until the
display returns to ILL3913 the “CONTROL” menu.
IMPORTANT: UPON COMPLETION OF SERVICE ENSURE PLC CONTROL IS SET BACK TO
ORIGINAL SETTING (WALL CONTROLLER, MODBUS, BMS, OR BACNET)
Drain Connection Access Panel
ILL3683-A
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 39
MAINTENANCE INSTRUCTIONS
INDIRECT & DIRECT PUMPS
Quantities and locations of pumps for each model are shown below.
WATER INLET SOLENOID VALVE
SOLENOID VALVE MAINTENANCE No regular maintenance of the solenoid valve is
required.
Cores Water Distribution Spreaders Reservoir access
CW-H10 = 1, CW-H15 = 1, CW-H15S = 1, CW-H15S Plus = 1
CW-H10 = 1 CW-H15 = 1 CW-H15S = 2 CW-H15S Plus = 2
Water Inlet Solenoid Chlorinator Pumps
Pump Access Panel
Core Access Panel
PUMP JUNCTION BOX
(UNDER LID)
ILL2450-B
PUMP MAINTENANCE
Cleaning Pump Strainers & Impellers
1. Cut the cable tie securing the pump leads and remove the 2 screws securing the pump bracket to the wall of the cooler.
2. Disconnect the plumbing hose from the spigot at the pump base.
3. Remove the pump assembly from the cooler cabinet.
4. To remove pump from the strainer, press the release button on the strainer, twist the pump body clock-wise with button depressed and lift the pump body out of the strainer base. Note the orientation prior to removal.
5. Inspect and clean the pump strainer and impellor housing. Remove any solids or residues from the strainer slots or around the impellor with a soft brush.
6. Re-assemble in the reverse order, use a new cable tie to tidy and secure all the cables again.
Note! When removing or unplugging pumps, take care to ensure they are replaced correctly.
· The pump body must be seated flush in outlet housing otherwise it will not
pump sufficient water.
· Check the integrity of the hoses and their connection to the pump spigots.
SOLENOID VALVE REPLACEMENT
ILL1954-B
1. Turn off the water supply.
2. Remove the breather hose from and unclip the solenoid cover (B).
3. Remove the outlet hose from the bottom of the solenoid valve.
4. Undo and remove the water inlet nipple (D) from the old solenoid.
5. Fit the new solenoid to the bracket (C) with a new water inlet nipple (D) and o-rings (E) and (F).
6. Unplug the old solenoid lead from the main PCBA, (refer to the wiring diagram on the control box door for the plug point location), remove the lead from the cable gland at the base of the control box and pull through the rubber gland mounted below the control box. Use the old cable to pull the new cable to the opposite side of the cooler. Plug the new solenoid into the PCBA.
7. Re-attach the outlet hose, ensuring there is a 10mm (3/8″) gap between the top of the hose and the top of the slot in the solenoid – this is to prevent a vacuum being created (refer diagram below).
8. Re-fit the breather hose and solenoid cover (B).
A
SOLENOID VALVE, NYMET BRAND, 12VDC, 1000KPA
B
SOLENOID COVER
C
SOLENOID COVER BRACKET
B
D
FITTING1/2″ BSP
E
O’RING 19MM ID
F
O’RING 25MM ID
G
RIVET 1/8″ (X4)
H
BLANKING GROMMET 12MM (NOT SHOWN)
I
PRESSURE HOSE 300MM (NOT SHOWN)
OUTLET HOSE
PUMP REPLACEMENT
ILL1956-A
Pumps are wired in parallel via a junction box located below the cooler lid back panel.
Trace the pump cable back to the pump junction box to identify the correct cable gland and terminal junctions.
Replicate the pump basket orientation with the pump being removed.
Unscrew the 2 screws securing the pump to the bracket and refit to the new pump.
10MM GAP
D EF
O’RING ORIENTATION 19mm
A G
25mm
C
ILL2454-A
40 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
MAINTENANCE INSTRUCTIONS
CHLORINATOR
SIDE VIEW – LHS
WATER MANAGEMENT PROBE
SIDE VIEW – RHS
Water Inlet Solenoid Chlorinator Pumps
Access Panel
Access Panel
Water Management Probe Drain Valve Pumps
ILL1954-B
CHLORINATOR MAINTENANCE
The chlorinator is fitted to a bracket located underneath the water inlet
solenoid valve. The chlorinator and bracket can be removed together. To
remove, detach the water hose and unscrew the bracket from the cooler body.
It is normal for the chlorinator cell blades to be covered in white deposits.
1. Remove any excess solids gently, using a soft brush, prior to immersion
2. Wash or hose the chlorinator cell in clean water (hot water if possible).
3. Immerse the chlorinator cell in a plastic container with 5% phosphoric
acid solution for at least 10 minutes. Be sure to clean the inner surfaces of
the chlorinator cell blades
4. Rinse with fresh water & reassemble chlorinator. Ensure chlorinator
spacing clip is in place.
IMPORTANT – ENSURE THE CHLORINATOR AND 4-WAY DISTRIBUTOR SIT PARALLEL TO THE
BRACKET AS SHOWN.
ILL2448-A
WATER MANAGEMENT PROBE MAINTENANCE
1. Open the pump access panel. Cut the cable tie securing the probe lead to
the pump hose.
2. Unclip the probe from the bracket, pull the lead through the opening in
the bracket and pull the probe out from the enclosure (there is sufficient
lead length to clear the pump enclosure). Remove the small plastic shrouds
from the first and third pins.
3. Clean the pins by wiping the contact surfaces with a soft cloth – do NOT
use abrasives.
4. Check the probe pin resistances using a multi-meter (refer figure and
wiring diagram – you’ll need to unplug the probe lead from the main PCB to do
this).
Clean the water level probes by wiping the contact surfaces with a soft cloth.
Pin 1
Pin 2
Pin 3
Pin shrouds shown in dotted line for clarity
0.00W
+ –
ILL2451-A
CHLORINATOR REPLACEMENT
Unplug the chlorinator lead from the main PCBA, (refer to the wiring diagram
on the control box door for the plug point location), remove the cable from
the cable gland at the base of the control box and pull through the rubber
gland mounted below the control box. Use the old cable to pull the new cable
to the opposite side of the cooler.
PIN 4 (EMPTY) PIN 3 (BROWN) PIN 2 (BLACK) PIN 1 (BLUE)
ILL2452-A
Resistance should be 0-5 ohms. A reading of 5 ohms or greater indicates a faulty probe. Check for shorts between pins: There should be an open circuit.
5. Refit the shrouds over pins 1 & 3. Refit the probe to the bracket, making
sure the clip is fully engaged and square
(the clip makes a “click” sound when properly engaged).
WATER MANAGEMENT PROBE REPLACEMENT
1. Unclip the probe from the mounting bracket, unplug the probe lead from the
main PCB, remove the lead from the cable gland at the base of the control box,
pull the lead through the rubber gland mounted below the control box from the
access panel opening.
2. Refit the assembly. Use a new cable tie to tidy and secure all the cables
again and re-assemble.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 41
MAINTENANCE INSTRUCTIONS
DRAIN VALVE
SIDE VIEW – RHS
Access Panel
Water Management Probe Drain Valve Pumps
DRAIN VALVE MAINTENANCE
ILL2448-A
No regular maintenance of the drain valve is required; however it is sometimes necessary to remove the drain valve fully during tank flushing.
DRAIN VALVE REPLACEMENT
1. Unplug the drain valve lead from the main PCBA, (refer to the wiring diagram on the control box door for the plug point location), remove the lead from the cable gland at the base of the control box and pull through the rubber gland mounted below the control box.
2. Remove any drain fittings from the bottom of the Drain Valve.
3. Undo the drain valve nut on the bottom of the reservoir and lift the drain valve out of the cooler.
4. Before replacing, ensure the sealing surface of the reservoir and the o-ring is free of any derbis. This is important to prevent leaks.
5. Make sure that the O-Ring (2) and Retainer (3) is fitted to the drain
valve thread before replacing the valve back into
the reservoir. Screw the nut (4) up tightly by hand through
the drain valve access panel. Do not overtighten the nut.
6. Re-fit the drain fittings to the bottom of the Drain Valve.
7. Run the new drain valve cable through to the control box and connect to
the PCBA.
1
INLET AIR FILTERS
The inlet air filters should be replaced as soon as the airflow through the
filters is restricted by dust or contaminants. The frequency of changing the
inlet air filters is dependent on the air quality at the site
Replacement inlet air filters are available from SI Service Agents and Climate
Wizard Distributors. If alternative air filters are supplied, they should be
to EN779 G4 or ASHRAE 52.2 MERV8 standards as a minimum.
To access the Inlet Air Filters, the centre front panel of the Air Filter
Cowling must be removed by releasing x4 quarter-turn fasteners.
QUARTER TURN LOCKS IN ALL 4 CORNERS OF THE DOOR PANEL
ILL3619-A
Lift and slide out the 2x retaining brackets holding the filters in place.
OTHER BRACKET OBSCURED IN THIS
VIEW
Slide up to remove
1. = DRAIN VALVE ASSY 2. = O RING (Inside) 3. = RETAINER (Inside) 4. = NUT
(Outside) 5. = DRAIN ELBOW (Outside) 6. = FLEXIBLE DRAIN ADAPTOR (Outside)
2 3
TANK FLOOR 4
6 5
DRAIN VALVE ACCESS PANEL
ILL3620-A
The Inlet Air Filters slide in and out of the Air Filter Frame. When fitting,
use the air flow direction sticker on the side of the filter to ensure the
correct orientation. Ensure the 2x retaining brackets are re-fitted.
WATER RESERVOIR (TANK)
Flushing of the water reservoir is best achieved with the pumps/chlorinator
and water management probe removed. In instances of large amounts of solid
debris, it is also recommended to remove the drain valve.
Use a water hose or low-pressure cleaner to flush all debris down the
reservoir drain. After flushing wipe the bottom of the reservoir thoroughly
using a wet cloth or brush.
NUT/ORING ELBOW
ADAPTOR
ILL2453-C
42 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
MAINTENANCE INSTRUCTIONS
INDIRECT HEAT EXCHANGERS
The indirect heat exchanger cores do not require any maintenance other than
visual inspection, which can be completed without removal from the cooler.
However it is recommended that, after 7 years of operation and for each
subsequent year of operation, all indirect heat exchangers are removed for a
detailed inspection.
During a full inspection, check the following areas.
· Air intake face and dry channels are clear of dirt, debris and calcium build
up.
· Glue seams are fully sealed, with no splits greater than 10cm. · Wet channel
air-entry slots are not bridged by calcium build
up.
TOP VIEW
7. The cores can now be slid out from either side of the cooler through the access panel openings. Take care to ensure the cores are not damaged during removal. They can be heavy and fragile when wet. Grasp the cores around the top section to ensure no delamination of the core occurs while moving them.
CORE AND SPREADER ASSEMBLIES (LID REMOVED)
1. Power OFF, water OFF.
ILL2450-B
2. Disconnect and remove any fixed ducting from the exhaust outlet of the cooler (if fitted).
3. Remove the exhaust transition/lid assembly from the cooler.
ILL2457-A
8. To re-assemble, position the cores into the cooler starting at the centre.
For all cores the front of the core must face the cooled air outlet of the
cooler as below.
REAR Side View
FRONT
ILL2462-A
4. Open the core access panels on either side of the cooler.
5. Remove the metal core clamp strips
6. Disconnect the spreader assembly from the rubber core extrusions and
remove the water spreader assemblies. They can be placed aside onto the lid of
the cooler cabinet while still remaining connected to the plumbing system.
PATTERN CHANGES
FRONT
RUBBER SEAL EXTRUSION TOP VIEW PATTERN CHANGES
FRONT
Top View
FRONT
REAR
ILL2456-A
ILL2458-A
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 43
MAINTENANCE INSTRUCTIONS
9. Locate the water spreader assembly front flange into the extrusion at top
front of the cores.
DIRECT HEAT EXCHANGERS (CHILLCEL)
(CW-H15S, H15S Plus ONLY)
1. Remove the lid / exhaust assembly.
2. Remove the indirect heat exchangers to expose the 3 Chillcel pads located
in the cooler supply air outlet transition.
3. Remove the Chillcel cover plate.
4. Slide the Chillcell out from underneath the water spreader assembly.
ILL2459-A
10. Check the cores fit snugly and squarely across the width of the core
platform and are firmly butted together. Check for a uniform gap at either
side of the cooler between the side walls and the core. The core access door
has a seal to take up any resultant gap.
ILL3939
5. To re-assemble, first note the Chillcel has a small header block; this is
the top of the pad and must be positioned under the water spreader for the pad
to function correctly.
6. Ensure the re-fitted Chillcel sits upright against the water spreaders and
tightly against each other.
ILL2460-A
11. Ensure a good seal between the cores and the access door when closing.
When re-securing the access doors, start from the bottom screws and work up.
12. Refit the core clamp strips clamping over the extrusion located at the
top of the cores.
ELECTRICAL ENCLOSURE
The cooler electrical controls enclosure is manufactured from steel coated in
a thermosetting epoxy polyester powder paint. Care should be taken to avoid
causing deep scratches, dents or cleaning using an abrasive brush. Wipe clean
with sponges and clean water.
Any local areas of corrosion or cracked paint can be treated by applying a
heavy duty, zinc-rich, anti-corrosive coating, often called “Zinc Rich Primer”
or “Cold Galv”. First ensure the surface is free from dust, dirt, grease, oil,
rust, scale and other contaminants and then follow the coating manufacturer’s
application instructions.
ILL2461-A
13. Refit the exhaust transition/lid assembly to the cooler.
14. Refit any fixed ducting to the exhaust outlet of the cooler.
15. Turn water and power back on to the cooler.
44 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
MAINTENANCE INSTRUCTIONS
TROUBLESHOOTING
PROBLEM
POSSIBLE CAUSE
Cooler in fault.
Cooler fails to start/ not running.
No power to cooler. Wall control in 7-day program mode.
Cooler not receiving commands. Cooler running in vent mode. Incorrect wall control temperature setpoint.
Inadequate cooling.
DEC stage not operating (Supercool coolers only.)
Plenum pressures too low. Clogged or dirty inlet air filters Clogged or dirty
heat exchanger cores. Water pump failure.
Pumps run but insufficient water in tank.
Pumps run but no water circulation or heat exchanger cores lack water
Inadequate exhaust from building. Under-sized ducts. Under-sized cooler. High ambient humidity.
Excessive humidity. Noisy cooler. Unpleasant odour.
External water leaks.
Inadequate exhaust from building.
Reduce DEC usage (Supercool coolers only.) Fan out of balance due to dirt,
etc. Air duct noise New heat exchanger cores. Cooler located near source of
unpleasant odour. Algae in reservoir water. Cores remain wet after shutdown.
Loose water hose connections. Blocked or undersized drains.
Excessive amounts of water from drain hose.
Water carryover in supply airstream.
Water carryover in exhaust airstream.
Clogged or dirty heat exchanger cores. New heat exchanger cores. Heat exchanger cores not fitted correctly into plenum. Plenum pressures too high External static pressure too high.
Core seals/spreaders moved during transport.
SUGGESTED REMEDY
Clear active faults. Check wall controller fault code log. Check tri-colour
LED for fault code.
Check circuit breaker. Consult with building manager.
Adjust setpoint and/or timer settings. Switch to manual mode to check fan
operation.
Set to PLC control method to W/C, MBS or BMS as required, see Multi-Magic
Control Schemes
Turn to cool mode.
Adjust wall control setpoint. Move wall control to more appropriate location.
Check controller humidity setpoint is not too high. Check cooler device type
is set correctly (CW-H15S or CW-H15S Plus)
See Commissioning section for Air Flow Balancing
Clean or replace air filters. Clean or replace cores.
Check all pumps are operating.
Clean or replace water probe. Check water management probe position relative
to drain valve overflow Check cooler is level.
Clean pump strainer. Check water distribution system for possible obstruction
in hoses. Check for blockages in the spreaders feeding the core assemblies.
Make sure there is adequate provision for exhausting air from building (open
windows and doors).
Carry out cooling load design to determine correct size unit, ducting and
outlets required. Discuss with building manager.
On days during summer when ambient humidity is high the cooler will not reduce
the temperature as much as on drier days. There is no remedy.
Make sure there is adequate provision for exhausting air from building (open
windows and doors).
Discuss with building manager Adjust controls program.
Clean the fan.
Increase size of ducts. Increase size of room registers/grilles
See Commissioning Section for Cooling Core Flush
Remove source of odour or relocate cooler.
Drain reservoir, clean thoroughly with strong cleansing agent, refill. Run
cooler on VENT mode after cooling cycle to dry heat exchanger cores out.
Check and tighten connections.
Check and clean drain lines.
Check drain valve seal. Check water management probe position relative to
drain valve overflow. Check cooler is level.
Clean or replace cores.
See Commissioning section for Cooling Core Flush
Check for air gaps around water spreaders and between cores.
See Commissioning section for Air Flow Balancing
Increase size of ducts. Increase size of room registers/grilles.
Check spreader assemblies securely clamped to top of cores and gaps between
cores covered up. Check core doors correctly sealing against sides of cores.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 45
WARRANTY TERMS (AUSTRALIA)
HOW TO REGISTER YOUR PRODUCT WARRANTY (Australia only) Please register your
warranty online by visiting seeleyinternational.com and selecting COMMERCIAL
section on the top right hand side of the screen. Then follow these steps:
Step 1 Select REGISTER FOR WARRANTY Step 2 Enter your product serial number
and “SUBMIT” Step 3 Enter the required information and “SUBMIT”
Alternatively, go to www.seeleyinternational.com/commercial/register-a
-product-for-warranty which will take you directly to the product warranty
registration page.
Important Note: You need to have the following information to complete your registration: · your unit model and size
· serial number
· date your system was installed
· name of the dealer/installer you purchased it from
Please complete this section. You will also need to retain your purchase receipt, and proof of any warranty period extension.
Brand:
Model:
Serial No:
Customer Name: _____
Installation Address: __
Date of Installation: ___
Installer / Dealer: ____
As with any product that has moving parts or is subject to wear and tear, it
is VERY IMPORTANT that you maintain your Climate Wizard and have it regularly
serviced. It is a condition of warranty cover for your Climate Wizard that you
comply with all of the maintenance and service requirements set out in the
Owner’s Manual. Compliance with these requirements will prolong the life of
your Climate Wizard. Further, it is also a condition of warranty cover that
each item in the Maintenance Schedule in the Owner’s Manual is performed with
the frequency indicated, by a qualified, licensed technician, and that the
Maintenance Schedule is properly filled out (i.e. names, signature, date, and
action taken) when the item is completed.
ANY FAILURE TO CARRY OUT THE REQUIRED MAINTENANCE AND SERVICING REQUIREMENTS,
AND ANY FAILURE TO PROPERLY FILL OUT THE MAINTENANCE SCHEDULE, WILL VOID YOUR
WARRANTY.
46 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
WARRANTY
Warranty Details (Australia only)
In this warranty:
We or us means Seeley International Pty Ltd (Seeley) ABN 23 054 687 035, and our contact details are set out at the end of this warranty;
You means you, the original end-user purchaser of the Goods;
Supplier means the authorised distributor or retailer of the Goods that sold you the Goods in Australia;
Goods means the product, unit, appliance or equipment which was accompanied by this warranty and purchased in Australia; and
Relevant Warranty Period means the various warranty periods as described in clause 1 below, as appropriate.
Our Goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the Goods repaired or replaced if the Goods fail to be of acceptable quality and the failure does not amount to a major failure.
In addition to any rights and remedies that You may have under the Australian Consumer Law or any other law, subject to the terms of this warranty, We provide the following warranty:
1. If during the first one (1) year from the date of purchase, the Goods upon
examination prove defective by reason of improper workmanship or material, We
will repair or replace at our option, the Goods or any part thereof without
charge for either parts or
labour during normal working hours.
2. The warranty granted under clause 1 applies to all components which form part of the original air cooler, but does not cover:
a. fair or normal wear and tear;
b. damage, loss or claims caused by, resulting from, or arising out of any utilities that service or are connected to the
Goods. This includes but it is not limited to electrical surges, and inadequacies, failure, or other problems in or with
any electricity, power, or water supply to the Goods;
c. after the first year: the replacement, supply, or servicing of consumable items (including without limitation washers,
seals, and drive belts);
d. despite clause 2.c. above, the air filters;
e. installation (including without limitation ductwork, fittings, and other related installation components) which is excluded
and.
f.
batteries (including damage caused by leaking or faulty batteries), cracking or breaking of display screens in
controllers, physical damage caused by the user or third parties, and accidental breakage.
3. Seeley also warrants the Fan Motor for the first three (3) years from the
date of the Goods purchase, if upon examination prove defective by reason of
improper workmanship or material, We will repair or replace at our option, the
Fan Motors or any part
thereof without charge for parts, during normal working hours.
4. During the period to which any expressed warranty applies, all defective part(s) shall be replaced or repaired (at the discretion of Seeley) without charge for either parts or labour, during normal working hours. Should we deem in our absolute discretion to replace the Goods pursuant to clause 1, we may substitute any similar good even if it is not on our current price/equipment list. Further, Goods presented for repair may be replaced by refurbished goods of the same type rather than being repaired. Refurbished parts may be used to repair the Goods.
5. We are under no obligation to repair or replace the Goods or Parts under clause 1 above if (i) the Goods have not been installed and commissioned in accordance with the Installation Instructions (ii) the Goods have not been installed and commissioned properly or competently, (iii) the Goods have not been operated, serviced and maintained in accordance with the instructions provided in the Owner’s Manual, or (iv) any such service or maintenance has not been properly or competently performed. The addition of any third party device or the removal or the alteration of any Seeley component or damage due to the misuse of the unit or faulty installation or commissioning will void this warranty. Further, it is a condition of warranty cover that each item in the Maintenance Schedule in the Owner’s Manual (if it was published with such a Schedule) is performed with the frequency indicated, by a qualified, licensed technician, and that the Maintenance Schedule is properly filled out (i.e. names, signature, date, and action taken) when the item is completed. Any failure to carry out the required maintenance and servicing requirements, and any failure to properly fill out a Maintenance Schedule in the Owner’s Manual, will void your warranty.
6. As far as the law permits, We will not be liable for any consequential loss suffered through, or resulting from, the non-operation, or ineffective operation of the air cooler. The warranties granted under clause 1 do not cover damage to the air cooler or other loss resulting from acts of God.
7. No other person, company or corporation is authorised to offer, or give on
our behalf, any other warranty. The benefits conferred are in favour of You
and any person deriving title to the air cooler whilst in its original place
of installation. Nothing in
this warranty shall be construed as affecting any rights You may have under
all the relevant laws, or Commonwealth or State Legislation which give You
rights which cannot be modified or excluded by agreement.
8. In order to claim under the warranties granted under clause 1 You must:
a.
either:
contact us within the Relevant Warranty Period on: 1300 650 644; or
log a warranty claim on our website (website address below) within the Relevant Warranty Period; and
b.
make available for inspection by the service agent who will come to the location of the Goods or send to us at
the address below within the Relevant Warranty Period: (i) the legible and unmodified original proof of purchase, which clearly
indicates the name and address of the original retailer, the date and place of purchase, the product name or other product
serial number, (ii) all of your records of all service and maintenance carried out to the Goods, plus the Maintenance Schedule
in the Owner’s Manual (if it was published with such a Schedule) (iii) a copy of the completed Warranty Information page in this
warranty, and (iv) if an extended warranty period was provided by us for the Goods, then the relevant document provided by us
confirming that extended warranty period. If you choose to send the documents described in (i) to (iv) to us, then they must be
accompanied by a covering letter which states your name and address and daytime telephone number, the address at which
the Goods are installed, and the model and serial number of the Goods.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 47
WARRANTY TERMS (AUSTRALIA)
9. The warranty granted in clause 1 covers the costs of parts and labour but
you will be responsible for:
a. the cost of travel incurred for a Seeley International service agent to get
to and from the location of the Goods if the location of the Goods is either:
(i) outside the metropolitan areas of the capital cities; or (ii) more than 35
kilometers from an authorised Seeley International branch or service
representative; and
b. any costs for additional labour or equipment associated with gaining
acceptable and safe service access to the Goods installed in restricted, high
or unsafe locations, and or the removal and replacement of any barrier, walls,
roofs, floors, fences etc.; and
c. any costs incurred by the Seeley International service agent in gaining
access to the Goods which is necessary to comply with any safety or workplace
safety requirements and/or any other relevant regulations. For the avoidance
of doubt, the reference to any costs incurred also includes the cost of any
necessary site inductions.
10. We are not responsible in any way for any failure and/or inadequate
performance of the Goods which arises from or is connected to the use in the
Goods of non-genuine spare parts. We strongly recommend that only spare parts
supplied or approved by us are used in the Goods.
11. We are not responsible for the installation of the Goods and expressly
disclaim all liability resulting from incorrect installations or installations
that do not conform to local electrical codes, local plumbing codes,
Occupational Health and Safety requirements, and by laws which are legislated
or in effect at the time of installation.
12. This warranty is only valid and enforceable in Australia.
Note: It is important that the safety and privacy of our service technicians
is protected at all times. Accordingly, We and our Seeley International
service agents reserve the right to refuse service if (i) safety and
accessibility to the unit cannot be guaranteed or (ii) the owner of the unit,
occupant of the site where the Goods are located, or any other third party
seeks to take photographs, or make a video or audio recording, of the service
technician(s) while they are on the site or carrying out service to the unit.
If a service technician attends the site but subsequently leaves for any of
these reasons then a service charge will be made for the call which charge
shall be a debt immediately due and payable by the person or entity that has
made the claim under this Warranty.
Note: We and our service agents reserve the right to refuse service unless
safety and accessibility to the unit can be guaranteed.
Note: If a service call reveals no warranty fault found with the Goods, a
charge will be made for the call.
Our liability under this warranty is limited to the extent permitted by law.
That is, to the extent that it is fair and reasonable, if the Goods are not of
a kind ordinarily acquired for personal, domestic or household use or
consumption, your remedies associated with any failure or defect of the
Product will be limited to:
a. the replacement of the Goods or the supply of equivalent goods; b. the
repair of the Goods; c. the payment of the cost of replacing the Goods or of
acquiring equivalent goods; d. the payment of the cost of having the Goods
repaired
and subject to the terms and conditions included in this warranty.
SERVICE DEPARTMENT
Seeley International Pty Ltd
112 O’Sullivan Beach Road
Lonsdale, South Australia 5160
Customer service centre 1300 650 644
Website: www.seeleyinternational.com
FOR SERVICE Service call Booking
To book a Service on your Seeley International product Online visit
www.seeleyinternational.com and selecting COMMERCIAL section on the top right
hand side of the screen. Then follow these steps:
Step 1 Select “SUPPORT” and “BOOK A SERVICE”. Step 2 On the “FIND A SERVICE
AGENT” page, enter your POSTCODE and select a category (“COMMERCIAL – CLIMATE
WIZARD”), select the “SEARCH” button. Step 3 On the “RESULTS” page, select the
“BRAND” of your cooler. Step 4 Choose “SELECT” for your preferred agent from
the list provided. Step 5 Select “BOOK A SERVICE” and complete the required
steps and fields. or Phone 1300 650 644 to be directed to your closest
authorised Service Agent.
PRIVACY NOTICE
Seeley International Pty Ltd ABN 23 054 687 035 will use the personal
information you provide us with to provide warranty support for the product
you have purchased and to inform you about other products and services. If you
choose not to supply us with the information requested, we may be unable to
provide you with warranty support. We may also disclose your information to
third parties, such as related entities; retailers, distributors, service
agents and contractors who are affiliated with us; or marketing or market
research companies. If you would prefer not to receive direct marketing
communications from us, please follow the instructions to “unsubscribe” which
will be included in the direct marketing communications we send you, or
contact our Privacy Officer using the details set out below. While we do not
currently transfer personal information to overseas recipients or store
personal information overseas, if we transfer your information to third
parties who do so, we will take reasonable steps to ensure that the overseas
recipients do not breach the Australian Privacy Principles. By registering
your warranty, you consent to having your personal information used in this
way. Please read our Privacy Policy on our website www.seeleyinternational.com
for further explanation of how we collect, use, hold and disclose personal
information, and how you may access and seek correction of your information.
It also sets out how you may complain about a breach of the Australian Privacy
Principles, and how we will deal with your complaint. You may contact us at:
Privacy Officer, Seeley International Pty Ltd, 112 O’Sullivan Beach Road,
Lonsdale, South Australia 5160.
48 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 49
WARRANTY TERMS (USA)
LIMITED WARRANTY DETAILS (USA only) In this warranty: We or Us means Convair
Cooler Corporation doing business as Seeley International Americas (“SIA”),
and our contact details are set out at the end of this warranty; You and
Purchaser means the original end-user purchaser of the Goods; Supplier means
the authorized distributor or retailer which sold you the Goods; Goods means
the CW3, CW-H, or CW80 model of the Climate Wizard cooler which was
accompanied by this warranty and is intended for industrial and commercial use
and not for personal, residential, or household use. There is no warranty on
the Goods for personal, residential, or household use; and Relevant Warranty
Period means the warranty period described in “Express Limited Warranty”
below. Do not use cooler cleaners, cooler treatment, or other additives to
your cooler. The use of any of these products will void your warranty and may
impair the performance of your cooler.
ELIGIBILITY: THE COOLER MUST BE REGISTERED WITHIN 45 DAYS OF INSTALLATION AT:
www.seeleyinternational.com/americaswarranty
SIA SHALL HAVE NO LIABILITY RELATED TO THE CLIMATE WIZARD COOLER OTHER THAN
FOR BREACH OF THE EXPRESS WARRANTY STATED HEREIN, AND YOU RELEASE AND
DISCHARGE US FROM ALL OTHER CLAIMS, WHETHER IN CONTRACT OR TORT, BY STATUTE OR
COMMON LAW, AND YOU FURTHER AGREE TO INDEMNIFY AND HOLD US HARMLESS FROM ALL
OTHER CLAIMS (INCLUDING BUT NOT LIMITED TO CLAIMS ALLEGING PRODUCT LIABILITY,
STRICT LIABILITY, DECEPTIVE TRADE PRACTICES, BODILY INJURY, AND/OR PROPERTY
DAMAGE) TO THE MAXIMUM EXTENT PERMISSIBLE UNDER LAW). THE EXPRESS WARRANTY
PROVIDED HEREIN BY SIA IS THE SOLE AND EXCLUSIVE WARRANTY AND IS IN LIEU OF
ALL OTHER WARRANTIES, WHETHER EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO
THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, WHICH ARE HEREBY DISCLAIMED. EXCEPT FOR THE EXPRESS LIMITED
WARRANTIES HEREIN, THE CLIMATE WIZARD COOLER IS SOLD “AS IS, WHERE IS.” NO
OTHER PERSON OR ENTITY IS AUTHORIZED TO OFFER, OR GIVE YOU, ON OUR BEHALF, ANY
OTHER WARRANTY.
EXPRESS LIMITED WARRANTY TERM: SUBJECT TO THE CONDITIONS AND EXCEPTIONS STATED
HEREIN, SIA warrants the CLIMATE WIZARD COOLER sold by SIA as follows: 1. SIA
warrants the Cooler cabinet only (base, top, side panels) against corrosion
due to normal operation for 1 year. 2. SIA warrants the structural integrity
of all plastic components against defects in materials or workmanship for 1
year. 3. SIA warrants, for 1 year, the original factory-installed water pumps,
motors, Chlorinator, Water Solenoid, Water Probe, Drain
Valve and controls against all defects in material and workmanship. 4. SIA
warrants the factory installed cooler pads (cores) against de-lamination due
to manufacturing defects for 1 year.
REPLACEMENT OF AIR FILTERS AND/OR COOLER PADS DUE TO NORMAL WEAR AND TEAR IS A
COMMON MAINTENANCE FUNCTION AND IS NOT COVERED BY THIS WARRANTY. 5. All labor
costs incurred for installation, removal, or re-installation are the
purchaser’s responsibility. 6. All shipping costs for replacement parts are
the purchaser’s responsibility.
EXPRESS LIMITED WARRANTY COMMENCEMENT: Warranty coverage begins on the
installation date. The installation date is either: (1) The date that the
Cooler was originally commissioned (commissioning being the process that
occurs on, or shortly after, the Cooler is installed whereby the installer
checks the installation of the Cooler, and makes any final adjustments, before
hand-over to the purchaser). The date the Cooler was commissioned must be
provided to Seeley at the time of warranty registration; or (2) If the date
the Cooler was originally commissioned cannot be verified by Seeley, the
installation date shall be deemed to be the date on the purchaser’s invoice
for the purchase of the Cooler. However, if the Cooler is not installed within
90 days of the date on the purchaser’s invoice for the purchase of the Cooler,
then the warranty coverage commences on the date that is 90 days from the date
on the purchaser’s invoice. THE DATE ON THE PURCHASER’S INVOICE FOR THE
PURCHASE OF THE COOLER MUST BE GENUINE. A NONGENUINE DATE WILL NOT BE ACCEPTED
BY SIA. LIMITED REMEDIES: THE EXPRESS REMEDIES PROVIDED HEREIN ARE THE SOLE
AND EXCLUSIVE REMEDIES FOR ALL CLAIMS RELATED TO THE CLIMATE WIZARD, AND ARE
IN LIEU OF ALL OTHER REMEDIES, WHICH ARE HEREBY DISCLAIMED BY SIA AND WAIVED
BY YOU TO THE FULLEST EXTENT PERMISSIBLE BY LAW (INCLUDING BUT NOT LIMITED TO
WAIVER OF ALL DECEPTIVE TRADE PRACTICES STATUTES).
50 | CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I
WARRANTY TERMS (USA)
EXPRESS LIMITED REMEDIES:
SUBJECT TO THE CONDITIONS AND EXCEPTIONS STATED HEREIN, your remedies for any claim related to the CLIMATE WIZARD COOLER are limited to the following:
1. For breach of the foregoing Express Limited Warranty, if a claim is timely made within the applicable Relevant Warranty Period, THE SOLE AND EXCLUSIVE REMEDY SHALL BE, AT THE OPTION OF SIA AND AT SIA’S COST, TO REPAIR/ REPLACE THE DEFECTIVE PART, REPLACE THE COOLER, OR REFUND THE PURCHASE PRICE PAID for the Climate Wizard cooler (any such refund excluding price paid by end-user for delivery, installation, service, repairs and/or maintenance). If SIA elects to replace or repair either parts or coolers, SIA may, in its discretion, use refurbished parts or coolers in making the replacement or repairs, and may, in its discretion, substitute similar SIA authorized parts or coolers instead of the identical warranted part or cooler, even if such parts or coolers are not on its current price/equipment list. You shall have no recourse for breach of the Express Limited Warranty if written notice of claim is not received by SIA within the applicable Relevant Warranty Period, in which case your claim shall be deemed time-barred for all purposes.
2. EXCLUSIONS FROM EXPRESS LIMITED WARRANTY. The EXPRESS LIMITED WARRANTY excludes coverage for and SIA disclaims (and you hold harmless from and indemnify SIA against) any and all liability to or for:
a. anyone other than You or any person directly deriving title to the Climate Wizard cooler from You whilst in its original
place of installation; (i.e. this Express Limited Warranty is assignable by You only to the person or entity who directly
acquires or buys from you your business and/or property, but the assignee has no further right of assignment); and
b. normal wear and tear; and
c. the cooler’s cooling performance, efficiency, water, and electricity consumption, all of which may vary widely
depending upon the environment in which the cooler is installed and operates, the area, composition and insulation of
the interior structure which it is intended to cool, and how it is used; and
d. damage, loss or claims caused by, resulting from, or arising out of any utilities, including, but not limited to, electrical
surges, and inadequacies, interruptions, failure, or other problems in or with electricity, power, or clean water supply to
the cooler; and
e. damage, loss or claims caused by, resulting from, or arising out of installation, servicing, maintenance, or repair that is
not performed in accordance with SIA’s written instructions; and
f.
the replacement, supply, or servicing of consumable items (including, without limitation, washers, seals, bearings,
drive belts, float valves, plumbing components, cooler pads); and
g. calcification of the cooler pads, since calcification may be affected by minerals in the water supplied to the cooler and
in the ambient air; and
h. installation or re-installation of the cooler (including without limitation related ductwork, fittings, and other installation
components) which is the responsibility of your Supplier and/or installer; and
i.
acts of God or nature, e.g., fire, flood, tornado, power outage, lightning, dust storm; or acts of theft or vandalism; or
any intentional act which impairs the utility of or damages the cooler; and
j.
all costs of labour and travel incurred in connection with repairing or replacing a defective part or the cooler; and
k. any costs incurred by Us in connection with a warranty claim which We determine is not a valid claim covered by the
Express Limited Warranty; and
l.
personal, residential, or household use of the Climate Wizard cooler.
LOSS OF EXPRESS LIMITED WARRANTY: THE EXPRESS LIMITED WARRANTY SHALL BE NULL AND VOID, ALL LIABILITY FOR BREACH OF SUCH WARRANTIES OR OTHERWISE SHALL BE DEEMED DISCLAIMED, AND YOU SHALL WAIVE ALL RIGHTS AND REMEDIES OF ANY KIND FOR ANY ALLEGED DEFECT IN THE CLIMATE WIZARD COOLER, IF:
a. the Climate Wizard cooler has not been installed and commissioned, in accordance with the instructions in the
Owner’s Manual, by a qualified, licensed, properly trained technician; OR
b. the Climate Wizard cooler has not been operated by you, and/or serviced and/or maintained by a qualified, licensed
technician, in accordance with the instructions provided in the Owner’s Manual; OR
c. you fail to maintain and present with any notice of claim the up-to-date Maintenance Schedule (if same is contained
in the Owner Manual) showing all work performed on the cooler from installation, the date of each work item, a
description of the work performed, and the name, signature and contact details of the qualified, licensed technician
who performed the work; OR
d. any installation, commissioning, service or maintenance has not been properly or competently performed in
accordance with applicable electrical, plumbing, building and safety codes and regulations; OR
e. use of any replacement parts or spare parts not authorized by SIA; OR
f.
addition of any third party device to (except where such addition is required by the installation instructions and
complies with those instructions), or the removal, modification, or alteration of, the Climate Wizard cooler or any SIA
component thereof; OR
g. the Climate Wizard cooler has been moved from the original place of installation (whether at the same premises or to
different premises).
EVEN IF THE EXCLUSIVE CONTRACTUAL REMEDY (OF REPAIR, REPLACEMENT, OR REFUND OF THE PURCHASE PRICE) PROVIDED HEREIN FAILS OF ITS ESSENTIAL PURPOSE, SIA SHALL NOT BE LIABLE TO YOU FOR ANY CONSEQUENTIAL, INCIDENTAL, INDIRECT, PUNITIVE, EXEMPLARY, OR SPECIAL DAMAGES, INCLUDING, WITHOUT LIMITATION, LOST REVENUES, DOWNTIME, LOSS OF USE, SUBSTITUTE EQUIPMENT, GOODWILL, DAMAGE TO OR REPLACEMENT OF YOUR OTHER EQUIPMENT AND PROPERTY. IN NO EVENT SHALL OUR LIABILITY EXCEED THE PURCHASE PRICE PAID FOR THE GOODS.
CW-H INSTALLATION, OPERATION & MAINTENANCE MANUAL 859749-I | 51
WARRANTY TERMS (USA)
CONDITIONS TO WARRANTY CLAIM: Failure to comply with the following conditions shall waive your warranty claim and release and discharge Us from any liability for same.
1. NOTICE.
In order to make a claim hereunder, You must send to the original Supplier of the cooler, or a cooler
contractor authorized by Us, or Us, written notice of the claim made, describing the breach claimed with particularity, stating
the date you first learned of it, with your name, address and daytime telephone number, the address at which the Goods are
installed, and the model and serial number of the Goods, by mail or (if to Us, then you may also do this through our website
(see details below)), and the written notice (or claim lodged through our website) must be received within the Relevant Warranty
Period:
· If by mail to Us, then to:
Convair Cooler Corporation dba Seeley International (Americas) 1002 South 56th Avenue Suite 101 Phoenix, Arizona 85043 United States of America; or
· If to Us through our website, then at:
www.seeleyinternational.com/americaswarranty
2. PROOF OF PURCHASE AND SERVICE RECORDS. You shall, in our discretion, within the Relevant Warranty Period, either send to us at the address below, or make available for inspection by the authorized person or company who repairs or replaces the defective part or cooler: (i) the legible and unmodified original proof of purchase, which clearly indicates the name and address of the original retailer, the date and place of purchase, the product name or other product serial number, and show you as the original end-user customer for the Goods, (ii) all of your records of installation, service and maintenance carried out to the Goods, plus the up-to-date Maintenance Schedule (if same exists) in the Owner’s Manual, and (iii) your name and contact details.
3. SAFE ACCESS TO THE GOODS. You shall provide Us, or the authorized person
or company that repairs or replaces the
defective part or cooler, safe access to your premises and the specific
location on your premises where the Goods are installed so that We and/or that
authorized person or company may safely access and inspect the Goods and, if a
breach of warranty is
confirmed, make repairs or replace parts, whichever remedy We elect in our
discretion.
DISPUTE RESOLUTION.
4. GOVERNING LAW. This Limited Warranty and all disputes arising from or
related to the Climate Wizard cooler sold herewith
shall be governed by the Federal Arbitration Act and the laws of the State of
Denver, excluding its conflicts of law rules and excluding application of the
U.N. Convention on Contracts for the International Sale of Goods.
5. FORUM. All disputes arising from or related to this L
References
- Seeley International - World Leading Air Conditioners
- Seeley International - World Leading Air Conditioners
- Register a Product for Warranty - Americas - Seeley International
- Register a Product for Warranty - Seeley International
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>