EMERSON STFE Series Surge Protective Devices Instruction Manual

June 4, 2024
Emerson

Nest of Lamp Tables
Instruction Manual

Safety Information

Important Information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER
DANGER
indicates a hazardous situation that, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.

Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Appleton Grp LLC d/b/a Appleton  Group for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, NOM-029-STPS, or CSA Z462.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside the equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors, and covers before turning on the power to this equipment.
  • This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
  • Do not supply more than 24VDC / 24VAC and no more than a current of 2A.
  • Confirm that the Surge Protective Device voltage rating on the module or nameplate label is not less than the operating voltage.
  • This equipment must be installed inside an enclosure and located so, as to prevent accidental contact with terminals during maintenance or servicing.
  • Do not install in areas with excessive dust, corrosive vapors, flammable materials, or explosive atmospheres.
    Failure to follow these instructions will result in death or serious injury.

WARNING: This product can expose you to chemicals including DINP, which is known to the State of California to cause cancer, and DIDP which is known to the  State of California to cause birth defects or other reproductive harm. For more information go to: www.P65Warnings.ca.gov.

NOTICE
LOSS OF SURGE SUPPRESSION

  • Make certain that Surge Protective Device is disconnected from the circuit it is protecting before conducting high-potential insulation testing.

Failure to follow these instructions can result in equipment damage.

Introduction

The STFE Series combines rugged, high-energy transient protection with the original Active Tracking® Filter technology to provide protection against the full spectrum of voltage transients and surges.
Proper installation is required for maximum system performance. To ensure a quality installation, the installer should read the entire manual and follow all instructions before and during the installation.
These instructions do not replace national or local electrical codes. Check applicable electrical codes to ensure compliance. Installation of the STFE Series should only be performed by qualified personnel.

Preinstallation

Location Considerations
Environment: The unit is designed for indoor operation in ambient temperatures of -40ºC (-40ºF) to +60ºC (+140ºF) with a relative humidity of 0% to 95% (noncondensing).
Supplemental Enclosures: All units provided with terminal blocks must be installed inside an enclosure and located so as to prevent accidental contact with terminals during maintenance and service.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • This equipment must be installed inside an enclosure and located so, as to prevent accidental contact with terminals during maintenance or servicing.
  • Do not install in areas with excessive dust, corrosive vapors, flammable materials, or explosive atmospheres.
    Failure to follow these instructions will result in death or serious injury.

Electrical Connections
All electrical connections must be installed by a licensed electrician. All wiring must comply with the National Electrical Code® (NEC® ) and applicable local codes.

Voltage, Current, and Power Configurations
Maximum Current Capability: The total current draw that a unit may continuously handle is provided in the Voltage, Current, and Power Configurations table below.

NOTICE
LOSS OF SURGE SUPPRESSION

  • Overloading the unit can cause permanent damage.
    Failure to follow these instructions can result in equipment damage.

Nominal Voltage: The nominal operating voltage for each model is provided in the Voltage, Current and
Power Configurations table below.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Confirm that the Surge Protective Device voltage rating on the module or nameplate label is not less than the operating voltage.

Failure to follow these instructions will result in death or serious injury.

Grounding

Input and output ground terminals must be connected for proper operation. Grounding is not only required for safety, but also for equipment performance. Incorrect grounding can reduce or impede the operation of the unit.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
    Failure to follow these instructions will result in death or serious injury.

Voltage, Current, and Power Configurations

Catalog Number| Load Current| Wire Size Range
(AWG)| Required
Torque (lb-in.)| Fuse/Circuit Breaker Ampacity
Suggest| Max
Single-Phase Models (120 VAC)
STFE03010N| 3.0A| 14 – 10| 4.4 lb-in. (0.50 N • m)| 3.0A| 3.75A
STFE05010N| 5. OA| 12 – 10| 5.0A| 6.25A
STFE10010N| 10.0 A| 14 – 12| 4.0 lb-in. (0.45 N • m)| 10.0 A| 12.5A
STFE20010N| 20.0 A| 12 only| 20.0 A| 25.0 A
Single-Phase Models (240 VAC)
STFE030241| 3.0 A| 14 – 10| 4.4 lb-in. (0.50 N • m)| 3.0A| 3.75A
STFE050241| 5.OA| 12 – 10| 5.0A| 6.25A
STFE100241| 10.0 A| 14 – 12| 4.0 lb-in. (0.45 N • m)| 10.0A| 12.5A
STFE20024L| 20.0 A| 12 only| 20.0 A| 25.0 A

Installation

  • For units provided with a ground connection, a green (with or without one or more yellow stripes) insulated grounding conductor identical in size, insulation material, and thickness to the grounded and ungrounded conductors must be installed (ref. NEC Table 250-95) and referenced back to acceptable building ground.
  • Attachment plugs, receptacles, etc. in the vicinity of the STFE Series must be of grounding type, with the grounding conductors connected to acceptable building ground.
  • Terminals, lugs, and connectors used in installation must be suitable for the material of the conductors.
    Conductors of dissimilar metals shall not be intermixed in a terminal or splicing.

Connection Diagram

Dansk Nest of Lamp Tables - Figure 1

Description Catalog Number
STFE2000 ON STFEXXX24L
Input Voltage 120 V (0-150 VRMS)
Line Frequency 47-63 Hz
Response Time <0.5 ns normal mode: < 5 ns common mode
Enclosure Fully enclosed metal housing
Connection!Mounting Type DIN rail mount
Status Indication Green LED -or, Form C contact. 5 A@ 125 VAC or 5 A@ 100 VDC
Weight 1.0 lb. (0.45 kg)
Dimensions H x W x 0 4.88 x 2.56 x 4.33in. (124 x 65 x 110mm)
Operating Temperature -40°C to +50°C at full load: derate linearly to 60% at

+70°C
Operating Humidity| 0% to 95% Non-condensing
Peak Surge Current Capability
Per Phase| 30,000 A
line to Neutral| 20,000 A
Line to Ground| 10,000 A
Neutral to Ground| 10,000 A
Load Surge Current Rating| 10 ms| 5 x Nominal
1 s| 3 x Nominal
10 s| 2 x Nominal
Nominal Discharge Current Rating| 3 kA
Short Circuit Current Rating (SCCR)| 51th
Maximum Continuous Operating Voltage (MCOV)| 150V1.-N.L-G. N-G| 320 L-L
Frequent Response
Normal Mode (forward-reverse)| 100 kHz to 50 MHz| -90 dB Max
Common Mode (forward-reverse)| 5 kHz to 50 MHz| -60 dB Max
Transient Reduction (IEEE C62.41).
‘All Voltage configurations are single phase. 2 wire + ground| Typical Category A Ringwave (6 kV. 200 A, 100 kHz) <60 V peak
Typical Category 8 Ringwave (6 kV, 500 A, 100 kHz) < 100 V peak
Standards Certifications| cRUus: UL 1449, CSA 22.2 No. 269, UL 1283, CSA 22.2 No. 8 (recognized component), CE
Warranty| 5-year limited warranty

Dimensional Drawings

Dansk Nest of Lamp Tables - Figure 2

System Design

Dansk Nest of Lamp Tables - Figure 3

Technical Support

Website: www.solahd.com
Technical Support E-Mail: solahd.technicalservices@emerson.com
Toll-Free: 1-800-377-4384
USA: 1-847-268-6651

Warranty

Please refer to the “Terms & Conditions of Sale” document.
While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility and disclaims all liability for damages resulting from the use of this information or for any errors or omissions.

The Emerson logo is a trademark and service mark of Emerson Electric Co.
Appleton Grp LLC d/b/a Appleton Group. SolaHD is a registered trademark of Appleton Grp LLC.
Active Tracking (and The Active Tracking Filter) trademarks owned by ASCO Power Technologies, L.P.
All other marks are the property of their respective owners. © 2020 Emerson Electric Co. All rights reserved.

United States
(Headquarters)
Appleton Grp LLC
9377 W. Higgins Road
Rosemont, IL 60018
United States
T +1 800 621 1506
Australia Sales Office
Bayswater, Victoria
T +61 3 9721 0348
Korea Sales Office
Seoul
T +82 2 3483 1555| Europe
ATX SAS
Espace Industriel Nord
35, rue André DurouchezCS 98017
80084 Amiens Cedex 2
France
T +33 3 2254 1390
China Sales Office
Shanghai
T +86 21 3338 7000| Canada
EGS Electrical Group Canada
Ltd.
99 Union Street
Elmira ON, N3B 3L7
Canada
T +1 888 765 2226
Middle East Sales Office
Dammam, Saudi Arabia
T +966 13 510 3702| Asia Pacific
EGS Private Ltd.
Block 4008, Ang Mo KioAve 10,

04-16 TechPlace 1,

Singapore 569625
T +65 6556 1100
Chile Sales Office
Las Condes
T +56 2928 4819| Latin America
EGS Comercializadora
Mexico S de RL de CV
Calle 10 N°145 Piso 3
Col. San Pedro de los Pinos
Del. Álvaro Obregon
Ciudad de México. 01180
T +52 55 5809 5049
India Sales Office
Chennai
T +91 44 3919 7300
---|---|---|---|---


References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals