Safety Information

Important Information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

  • The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
  • This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation that, if not avoided, will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation that, if not avoided, could result in death or serious injury.

CAUTION
CAUTION indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.

NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.

Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Appleton Grp LLC d/b/a Appleton Group for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

Introduction

The STCDRS036 is a DIN Rail mountable, single-pair surge suppression module implementing three-stage hybrid technology. This module addresses over-voltage transients with gas tubes and silicon avalanche components. In addition, sneak currents are mitigated with resettable fuses (PTCs). The PTCs increase resistance several orders of magnitude when over-currents exceed operating limits. A normal state resumes when the over-current condition is removed. The ability to self-restore in this manner significantly increases suppressor performance and survivability.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside the equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors, and covers before turning on the power to this equipment.
  • This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
  • Confirm that the Surge Protective Device voltage rating on the module or nameplate label is not less than the operating voltage.
  • For 6-35VDC models, do not place in service on any signal line capable of continuously supplying more than 150mA.

Failure to follow these instructions will result in death or serious injury.

WARNING:
This product can expose you to chemicals including DINP, which is known to the State of California to cause cancer, and DIDP which is known to the State of California to cause birth defects or other reproductive harm. For more information go to: www.P65Warnings.ca.gov.

NOTICE

HAZARD OF MIS-INSTALLATION

  • Only install this protective device in indoor applications and on communication loop circuits that have been isolated from the public switch telephone network (PSTN).
  • Do not expose the communication loop to contact with the electric light or power conductors.
  • Install the protectors as per the applicable requirements of the National Electric Code, ANSI/NFPA 70.

Failure to follow these instructions can result in equipment damage.

Installation

  1. Turn off power prior to installing SPD.
  2. Install SPD in a suitable enclosure.
  3. Connect load wires to the output side of the SPD.
  4. Connect source wires to the input side of SPD.
  5. Do not exceed 150mA continuous current.
  6. Turn on the power and verify the operation.

General Technical Specifications 0-36VDC Models

Operating Voltage 0-36 VDC
Breakdown Voltage 43 VDC
Operating Current 0.15 A
Peak Surge Current 10 kA (8×20µs)
Max Current Ip (Occurrences) >100 (10×1000µs)
Typical Capacitance 1500pf
Nominal Series Resistance 5 Ω
Response Time < 1 nanosecond
Operating Temperature -40°C to 85°C
Weight 0.123 lbs. (0.06 kg.)
Certifications UL 497B
Limited Warranty 5 years

Dimension

EMERSON-STC-DRS-Series-Surge-Protective-Devices-fig-1

Ordering Information

MODEL APPLICATION
STCDRS036 0-36 VDC

Technical Support

Warranty

Please refer to the “Terms & Conditions of Sale” document.

While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility and disclaims all liability for damages resulting from the use of this information or for any errors or omissions.

The Emerson logo is a trademark and service mark of Emerson Electric Co. Appleton Grp LLC d/b/a Appleton Group. SolaHD is a registered trademark of Appleton Grp LLC. All other marks are the property of their respective owners. © 2020 Emerson Electric Co. All rights reserved.

United States
(Headquarters) Appleton Grp LLC 9377 W. Higgins Road Rosemont, IL 60018 United States T +1 800 621 1506.

Australia Sales Office
Bayswater, Victoria T +61 3 9721 0348.

Korea Sales Office
Seoul T +82 2 3483 1555.

Europe
ATX SAS Espace Industriel Nord 35, rue André Durouchez, CS 98017 80084 Amiens Cedex 2 France T +33 3 2254 1390.

China Sales Office Shanghai
T +86 21 3338 7000

Canada
EGS Electrical Group Canada Ltd. 99 Union Street Elmira ON, N3B 3L7 Canada T +1 888 765 2226

Middle East Sales Office
Dammam, Saudi Arabia T +966 13 510 3702.

Asia Pacific
EGS Private Ltd. Block 4008, Ang Mo Kio Ave 10, #04-16 TechPlace 1, Singapore 569625 T +65 6556 1100.

Chile Sales Office
Las Condes T +56 2928 4819.

Latin America
EGS Comercializadora Mexico S de RL de CV Calle 10 N°145 Piso 3 Col. San Pedro de los Pinos Del. Álvaro Obregon Ciudad de México. 01180 T +52 55 5809 5049

India Sales Office Chennai
T +91 44 3919 7300

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals