UTICA BOILERS AT Series Electric Hot Water Boiler
Product Information
Specifications
- Product: Utica Boilers Electric Hot Water Boiler AT Boiler
- Manufacturer: ECR International Inc.
- Construction: Cast Iron heat exchanger, Incoloy sheath heating elements
- Control System: PCB integral controller with LCD display
- Electrical: 208/240 Vac, 1 ph, 60 Hz
- Warranty: 20 years on Primary heat exchanger, one year on parts
FAQ
- What is the warranty period for the Utica Boilers Electric Hot Water Boiler?
- The warranty is 20 years on the Primary heat exchanger and one year on parts.
- What is the construction material of the boiler heat exchanger?
- The boiler heat exchanger is constructed of Cast Iron.
General Requirements
- Provide and Install Boiler(s) in accordance with the plan drawings, written specifications and contract documents.
- All work shall be performed in a neat workmanship like manner compliant with all local code authorities.
Submittal
- Product Data: Submit manufacturer’s technical product data, including rated capacities of selected model, weight, installation, start-up instructions, and furnished accessory information.
- Shop Drawings: Submit manufacturer’s assembly drawings indicating dimensions, connection locations, and clearance requirements.
- Wiring Diagrams: Submit manufacturer’s electrical requirements for the boiler including ladder type wiring diagrams for interlock and control wiring.
Boiler Requirements
- Boiler shall include a one-piece heat exchanger to provide hot water for comfort heating zones and domestic hot water heating at the stated rate.
- Boiler shall be a wall hung type boiler.
- Boiler shall be factory tested.
- Refer to all local codes and jurisdictional requirements for installation of field supplied wiring and anti-scald valve(s).
Acceptable Manufacturers
- Equivalent units and manufacturers must meet all performance criteria for all options and will be considered upon prior approval.
Certifications & Listings
- Boiler shall be certified by CSA in accordance with CSA C22.2 No. 165 and UL-834.
- Registered with Massachusetts Board, National Board BPVI.
- Boiler shall be constructed in accordance with the American Society of Mechanical Engineers (ASME)
- Boiler shall have an ASME H stamp that is applied to the heat exchanger. Each heat exchanger shall be independently reviewed by an ASME authorized inspector. The boiler heat exchanger shall be rated for a maximum allowable working pressure of 30 psig. The boiler shall be equipped with a 30 psig relief valve.
System Requirements And Construction
System Requirements
- Central heat hydronic system pressure shall be no more than 30 psig and no less than 7.25 psig.
- Domestic hot water hydronic system pressure shall be no more than 30 psig.
Construction
- Boiler heat exchanger shall be constructed of Cast Iron.
- Boiler heating element circuit breakers shall be two-pole rated 40 A.
- Electric heating elements shall be CSA listed and constructed of an Incoloy sheath.
- Electronic control bord shall be cULus listed.
Control System And Electrical Connections
Control System
- Control system shall be PCB integral controller with an LCD digital display.
- Control will sense supply water temperature and stage additional heating elements on or off to meet the heating demand.
- Control will sense and display supply water temperature and indicate when boiler is in central heating or domestic water mode.
- Control displays error codes and diagnostic information.
Electrical Connections
- Supply voltage 208/240 Vac, 1 ph, 60 Hz.
- Boiler shall have a low voltage terminal strip with clearly marked connections.
Quality Assurance
Warranty
- Boiler shall be supplied with written Manufacturer’s Standard Warranty. Warranty is 20 years on Primary heat exchanger, one year on parts.
- Factory testing – boiler shall be factory tested.
Boiler Manuals
- The boiler shall be provided with a complete set of instructions as follows:
- Installation, Operation and Maintenance Manual (IOM) with Application Guide and repair parts list
Contacts
- 2201 Dwyer Avenue, Utica, NY 13501
- Tel. 800 325 5479
- www.ecrinternational.com
Manufactured by:
- ECR International Inc.
- 2201 Dwyer Avenue, Utica, NY 13501
- Tel. 800 253 7900
PN 615000607 REV. A [01/13/2023]
All specifications subject to change without notice.
©2023 ECR International, Inc.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>