Honeywell Farenhyt Series Internal Amplifier Installation Guide

May 15, 2024
Honeywell

Honeywell Farenhyt Series Internal Amplifier

INSTALLATION GUIDE

ECS-INT50W
Internal Amplifier
Product Installation Document

1. Description

The ECS-INT50W Internal Amplifier is used to amplify the audio message for distribution throughout the facility for the Emergency Communication System. The ECS-INT50W Internal Amplifier can fit inside the IFP-300ECS or IFP-2000ECS cabinets. It can also be adapted to fit into the IFP-2100ECS cabinet with the ECS-AMPMT mounting kit (sold separately).

1.1 Compatibility
The ECS-INT50W is compatible with the following Honeywell Farenhyt Series FACPs. For more information, refer to the FACP Installation Manual or the ECS Series Manual (PN:151455).

  • IFP-2100ECS
  • IFP-300ECS
  • IFP-2000ECS
  • IFP-1000ECS
  • IFP-100ECS

1.2 Specifications

  • Standby Current: 52mA
  • ECS-INT50W only Alarm Current @ 25V: 275mA; @ 70V: 310mA
  • Full Alarm load current @ 25V: 2840mA; @ 70V: 2900mA

2. Board Layout

Board Layout

3. Installation

NOTE: Installation and wiring of this device must be done in accordance with NFPA 72 and local ordinances.

To mount the ECS-INT50W, refer to the following steps.
1. Remove AC power and disconnect backup batteries from the main control panel.
2. To mount the ECS-INT50W inside the FACP cabinet below the main board (above the batteries), align the board with the mounting holes and secure the board to the enclosure with the eight supplied screws.

When mounting the ECS-INT50W in the ECS cabinet that contains an ECS-NVCM, it is necessary to mount the ECS-INT50W on the right side of the control board. To do this, you will need the ECS-AMPMT mounting kit (ordered separately).

1. Mount the ECS-AMPMT plate into the cabinet using the six supplied screws. Orient with “Top” side up. See Figure 2 below.

2. Secure the ECS-INT50W onto the six PEM studs on the mounting plate with six supplied screws. Ensure the side with only one terminal block is at the top of the ECS-AMPMT. See the figure below.

Mount

4. Wiring

4.1 FACP Wiring
See Figure 3 to properly wire the ECS-INT50W to the FACP. The Internal Amplifier must be powered by a NAC programmed as Constant Auxiliary Power. Refer to the FACP Installation Manual.

Wiring

4.2 VBUS Wiring
The VBUS is an analog voice bus that carries the recorded voice messages from the ECS-VCM or ECS-NVCM to the ECS-INT50W amplifiers, or the voice messages generated from a system microphone to the ECS-INT50W.
The maximum resistance on the VBUS is 20W.
Connect the VBUS from the ECS-VCM or ECS-NVCM to the ECS-INT50W amplifiers as shown in Figure 4.

VBUS Wiring

5. Setting the Device Address

Use the onboard DIP switches to select an ID number for the ECS-INT50W. Refer to Figure 5 to see how to set the DIP switches for the desired ID number. Once the ID number is set, add the ECS-INT50W to the system through panel programming. Note that Address 0 is an invalid number and cannot be used.

NOTE: The ECS-INT50W is powered by a NAC on the FACP or by an auxiliary power supply. It will not be found using JumpStart AutoProgramming.

ON/OFF

6. Speaker Wiring

Each ECS-INT50W supplies one circuit for speaker connection. The speaker circuit can be supervised and wired for Class B or Class A. The speaker circuit is capable of 50 watts of power at 25 Vrms or 70.7 Vrms. Refer to the Farenhyt Device Compatibility Document P/N LS10167-003FH for compatible speakers.

Speaker Wiring

NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20% voltage drop on the last speaker is allowed.

Figure 6 illustrates how to wire speakers to the control panel using Class B or Class A supervision.

Speaker Configurations

Specifications

  • Product Name: FarenhytTM ECS-INT50W Internal Amplifier
  • Compatibility: Compatible with IFP-300ECS, IFP-2000ECS, and IFP2100ECS (with ECS-AMPMT mounting kit)

FAQ

Q: Can the ECS-INT50W be used with all types of control panels?

A: The ECS-INT50W is compatible with IFP-300ECS, IFP-2000ECS, and IFP2100ECS (with ECS-AMPMT mounting kit).

Q: What is the maximum resistance on the VBUS for the ECS-INT50W?

A: The maximum resistance on the VBUS is 20 ohms.

Honeywell Fire Solutions
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.farenhyt.com

LS10119-001SK-E | D | 02/22
©2022 Honeywell International Inc.