Honeywell IDP-PHOTO Photoelectric Smoke Detector
Product Information
Specifications
- Brand: Farenhyt
- Compatibility: Honeywell Farenhyt FACPs (fire control alarm panels)
- Supported Devices: IDP, SK, or SD SLC devices
Product Usage Instructions
-
Compatible IDP SLC Devices
The Farenhyt Series supports various IDP SLC devices for use with control panels like IFP-2000(ECS), IFP-1000(ECS), IFP-100(ECS), and IFP-50. Refer to the installation documentation provided with each device for detailed instructions. It’s important not to mix different types of SLC devices on the control panel. -
Compatible IDP SLC Devices Current Draw
Refer to Table 2 for a list of compatible IDP SLC devices and their respective current draw. Always consult the FACP installation manual for additional information on these devices. -
Compatible SK SLC Devices
Table 3 lists additional SK SLC devices compatible with the control panels. Make sure to follow the device installation instructions provided with each device for proper usage. Avoid mixing different types of SLC devices on the control panel.
FAQ (Frequently Asked Questions)
- Q: Can I mix different types of SLC devices on the control panel?
A: No, it is not recommended to mix different types of SLCdevices on the control panel. The control panel supports the use of either IDP, SK, or SD SLC devices separately.
This supplement provides information on additional devices that are listed for use with the Honeywell Farenhyt FACPs (fire control alarm panels). Additional information is available in the installation documentation provided with the FACP.
Compatible IDP SLC Devices
Table 1 lists additionally available IDP SLC devices for use with the IFP-2000(ECS), IFP-1000(ECS), IFP-100(ECS), and IFP-50 control panels. Refer to the device installation instructions packaged with the device for more information.
NOTE:
The FACP supports the use of either IDP, SK, or SD SLC devices. Do not mix SLC
device types on the control panel.
Part Numbers | Model Name/Description | Install Sheet PN |
---|---|---|
IDP-PHOTO | Photoelectric smoke detector |
I56-3611
IDP-PHOTO-T| Photoelectric smoke detector with thermal (135°F)
IDP-ACCLIMATE| Multi-criteria photoelectric smoke detector with thermal
(135°F)
IDP-PHOTOR| Photoelectric replacement smoke detector with remote test
capability in DNR| I56-3569
IDP-BEAM| Reflected beam smoke detector without test feature| I56-2735
IDP-BEAM-T| Reflected beam smoke detector with test feature
OSI-RI-FH| Intelligent Beam Detector – Flashscan| E56-6585
DNR/DNRW| Duct smoke detector housing, non-relay (photo sold separately)|
I56-3051
IDP-HEAT| Fixed temperature thermal detector (135°F)|
I56-3608
IDP-HEAT-ROR| Rate-of-rise thermal detector with 135° fixed temperature
IDP-HEAT-HT| Fixed high-temperature thermal detector (190°F)
IDP-PULL-SA| Addressable single-action pull station| I56-3606
IDP-PULL-DA| Addressable dual-action pull station| I56-3605
IDP-ISO| Fault isolator module| I56-2729
ISO-6| Six Fault isolator module| I56-4096
IDP-MONITOR| Monitor module| I56-3603
IDP-MINIMON| Mini monitor module| I56-2726
IDP-MONITOR-2| Dual input monitor module| I56-2730
IDP-MONITOR-10| 10 input monitor module| I56-2731
IDP-RELAY| Relay module| I56-2729
IDP-RELAY-6| Six-circuit relay module| I56-2729
IDP-RELAYMON-2| Multi-module with 2 relay outputs & 2 monitor inputs| I56-3734
IDP-ZONE| Zone interface module| I56-3602
IDP-ZONE-6| Six-zone interface module| I56-2733
IDP-CONTROL| Supervised control module| I56-3600
IDP-CONTROL-6| Six-circuit supervised control module| I56-2734
IDP-FIRE-CO| Multi-Criteria Carbon Monoxide and Smoke Detector| I56-3946
IDP-FIRE-CO-W| Multi-Criteria Carbon Monoxide and Smoke Detector| I56-6603
IDP-PTIR-W / IV*| Multi-Criteria Photoelectric, Thermal, and Infrared Multi-
Criteria Detector| I56-6619
B200S-WH / IV| Intelligent Sounder base.| I56-3387
B200SR-WH / IV| Intelligent Sounder base| I56-3392
B210LP| 6″ Plug-in Detector base| I56-3739/I56-0595
B300-6 / -IV| 6” Plug-in Detector Base| I56-6566
B224BI-WH / -IV| 6″ isolator base| I56-0725
B224RB-WH / -IV| 6″ relay base| I56-3737
B200SR-LF-WH / -IV| Low-Frequency Sounder Base| I56-4152
B200S-LF-WH / -IV| Low-Frequency Sounder Base| I56-4151
B501| 4″ Plug-in Detector Base| I56-0357
B501-WHITE / -IV / -BL| 4” Plug-in Detector Base| I56-3738
IDP-PHOTO-W / -IV| Photoelectric smoke detector| I56-6531
Table 1 IDP SLC Devices
Part Numbers | Model Name/Description | Install Sheet PN |
---|---|---|
IDP-PHOTO-R-W / -IV | Photoelectric replacement smoke detector with remote test | |
capability in DNR | I56-6532 | |
IDP-PHOTO-T-W / -IV | Photoelectric smoke detector with thermal (135°F) |
I56-6534
IDP-HEAT-W / -IV| Fixed temperature thermal detector (135°F)| I56-6533
IDP-HEAT-ROR-W / -IV| Rate-of-rise thermal detector with 135° fixed
temperature| I56-6533
IDP-HEAT-HT-W / -IV| Fixed high-temperature thermal detector (190°F)| I56-6533
Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White
Table 1 IDP SLC Devices
- Listed for use in Open Area Protection Applications per UL 268 7th Edition requirements
Compatible IDP SLC Devices Current Draw
Refer to Table 2 for additional compatible IDP SLC devices. Refer to the FACP Installation manual for additional information.
Device| # of Devices| Current per Device| Standby Current|
Alarm Current
---|---|---|---|---
SLC Accessories
B200SR / -IV / -WH Sounder Base
| | Aux Power| Standby:| 0.5mA| mA|
Alarm:| 35mA| | mA
SLC| Standby| 3mA| mA|
B200S / -IV / -WH intelligent Sounder Base
| Aux Power| Standby:| 0.5mA| mA|
Alarm: (high vol)| 35mA| | mA
SLC| Standby| 0.3mA| mA|
B200SR-LF / -IV / -WH Low Frequency Sounder Base| | Aux Power| Standby:| 1mA|
mA|
Alarm:| 125mA| | mA
B200S-LF/ -IV / -WH Low Frequency Sounder Base
| Aux Power| Standby| 0.55mA| mA|
Alarm (high vol)| 140mA| | mA
SLC| Standby| 0.30mA| mA|
B224RB / -IV / -WH Relay Base| Standby/Alarm:| 0.5mA| mA| mA
SLC Isolator Devices
IDP-ISO Isolator Module| | Standby/Alarm:| 0.45mA| mA| mA
ISO-6 6-Fault Isolator Module| Standby: (per circuit)| 0.45mA| mA|
Alarm: (per circuit)| 17mA| | mA
B224BI / -IV / -WH Isolator Base| Standby/Alarm:| 0.5mA| mA| mA
Color Guide: -WH = White, -IV = Ivory
Table 2 Current Draw Worksheet for IDP SLC Devices
Compatible SK SLC Devices
Table 3 lists additional available SK SLC devices that can be used with the IFP-2000(ECS), IFP-1000(ECS), IFP-100(ECS), and IFP-50 control pan-els. Refer to the device installation instructions packaged with the device for more information.
NOTE:
The control panel supports the use of either IDP, SK, or SD SLC devices. Do
not mix of SLC device types on the control panel.
Part Numbers | Model Name/Description | Install Sheet PN |
---|---|---|
SK-PHOTO | Photoelectric smoke detector |
I56-3426
SK-PHOTO-T| Photoelectric smoke detector with thermal (135°F)
SK-PHOTO-R| Photoelectric detector with remote test capability
SK-ACCLIMATE| Multi-criteria photoelectric smoke detector with thermal (135°F)
SK-BEAM| Reflected beam smoke detector without test feature| I56-3433
SK-BEAM-T| Reflected beam smoke detector with test feature
OSI-RI-SK| Intelligent Beam Detector – Flashscan| E56-6587
SK-DUCT| Photoelectric duct smoke detector with extended airspeed range|
I56-3432
SK-DUCT-W| Duct Smoke Detector| I56-6628
SK-HEAT| Fixed temperature thermal detector (135°F)|
I56-3429
SK-HEAT-ROR| Rate-of-rise thermal detector with 135° fixed temperature
SK-HEAT-HT| Fixed high-temperature thermal detector (190°F)
SK-PULL-SA| Addressable single-action pull station| I56-3446
SK-PULL-DA| Addressable dual-action pull station| I56-3447
Table 3 SK SLC Devices
Part Numbers | Model Name/Description | Install Sheet PN |
---|---|---|
SK-ISO | Fault isolator module | I56-3445 |
SK-MONITOR | Monitor module | I56-3442 |
SK-MINIMON | Mini monitor module | I56-3444 |
SK-MONITOR-2 | Dual input monitor module | I56-3435 |
SK-MON-10 | 10 input monitor module | I56-3443 |
SK-RELAY | Addressable relay module | I56-3438 |
SK-RELAY-6 | Six relay control module | I56-3439 |
SK-RELAYMON-2 | Dual relay/monitor module | I56-3735 |
SK-ZONE | Addressable zone interface module | I56-3440 |
SK-ZONE-6 | Six-zone interface module | I56-3441 |
SK-CONTROL | Supervised control module | I56-3436 |
SK-CONTROL-6 | Six-circuit supervised control module | I56-3437 |
SK-FIRE-CO | Multi-Criteria Carbon Monoxide and Smoke Detector | I56-3945 |
SK-FIRE-CO-W / IV* | Multi-Criteria Carbon Monoxide and Smoke Detector |
I56-6602
SK-PTIR-W*| Multi-Criteria Photo, Thermal, and Infrared Detector| I56-6618
B200S-WH / IV| Intelligent sounder base.| I56-4151
B200SR-WH / IV| Intelligent sounder base| I56-4152
B210LP| 6″ Plug-in Detector base| I56-3739/I56-0595
B224BI-WH / IV| 6″ isolator base| I56-0725
B224RB-WH / IV| 6″ relay base| I56-3737
B200SR-LF-WH / IV| Low-Frequency Sounder Base| I56-0357
B200S-LF-WH / IV| Low-Frequency Sounder Base| I56-4152
B501| 4″ Plug-in Detector Base| I56-0357
B501-WHITE / IV / BL| 4” Plug-in Detector Base| I56-3738
SK-PHOTO-W| Photoelectric smoke detector| I56-6527
SK-PHOTO-R-W| Photoelectric detector with remote test capability, for use with
DNR duct smoke detector| I56-6528
SK-PHOTO-T-W| Photoelectric smoke detector with thermal (135°F)| I56-6530
SK-HEAT-W| Fixed temperature thermal detector (135°F)| I56-6529
SK-HEAT-ROR-W| Rate-of-rise thermal detector with 135° fixed temperature|
I56-6529
SK-HEAT-HT-W| Fixed high-temperature thermal detector (190°F)| I56-6529
Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White
Table 3 SK SLC Devices
Compatible SK SLC Device Current Draw
Refer to Table 4 for additional compatible SK SLC devices. Refer to the FACP Installation manual for additional information.
Device| # of Devices| Current per Device| Standby Current|
Alarm Current
---|---|---|---|---
SLC Modules
B200SR / -IV / -WH Sounder Base| | Aux Power| Standby:| 0.5mA| mA|
Alarm:| 35mA| | mA
SLC| Standby| 0.3mA| mA|
B200S / -IV / -WH intelligent Sounder Base| Aux Power| Standby:| 0.5mA| mA|
Alarm: (high vol)| 35mA| | mA
SLC| Standby| 0.3mA| mA|
B200SR-LF / -IV / -WH Low Frequency Sounder Base| Aux Power| Standby:| 1mA|
mA|
Alarm:| 125mA| | mA
B200S-LF/ -IV / -WH Low Frequency Sounder Base
| Aux Power| Standby| 0.55mA| mA|
Alarm (high vol)| 140 mA| | mA
SLC| Standby| 0.30mA| mA|
B300-6 / -IV Low Profile Mounting Base
| Aux Power| Standby:| 0.5mA| mA|
Alarm:| 35mA| |
SLC| Standby| 0.3mA| mA|
B224RB / -IV / -WH Relay Base| Standby/Alarm:| 0.5 mA| mA| mA
SLC Isolator Devices
Table 4 Current Draw Worksheet for SK SLC Devices
Device| # of Devices| Current per Device| Standby Current|
Alarm Current
---|---|---|---|---
SK-ISO (Isolator Module)| | Standby/Alarm:
0.45mA| mA| mA
B224BI-WH / -IV Isolator Base| Standby/Alarm:
0.5mA| mA| mA
Color Guide: -WH = White, -IV = Ivory
Table 4 Current Draw Worksheet for SK SLC Devices
Compatible System Sensor Devices
Table 5 lists additional available System Sensor devices for use with the IFP-2000(ECS), IFP-1000(ECS), IFP-100(ECS), and IFP-50 control panels. Refer to the device installation instructions packaged with the device for more information.
Part Numbers | Model Name/Description | Install Sheet PN |
---|---|---|
OSI-RI-SS | Intelligent Beam Detector – CLIP | E56-6583 |
OSI-R-SS | Conventional Beam Detector | E56-6572 |
Table 5 System Sensor Devices
Compatible 520Hz Low-Frequency Bases
Refer to Appendix A in the FACP manual for additional low-frequency bases. The table below lists additional available low-frequency bases for use with the IFP-2000(ECS), IFP-1000(ECS), IFP-100(ECS), and IFP-50 control panels. Refer to the device installation instructions packaged with the device for more information.
Model Number | Description |
---|---|
B200S-LF-WH / IV | Low-Frequency Intelligent Sounder Base. White or Ivory |
B200SR-LF-WH / IV | Low-Frequency Intelligent Sounder Base. White or Ivory |
Color Guide: -IV = Ivory color, -WH = White
Table 6 Low Frequency Bases
Notification Appliances
Refer to Appendix A in the FACP manual for additional notification appliances. The table below lists additional available notification appliances for use with the IFP-2000(ECS), IFP-1000(ECS), IFP-100(ECS), and IFP-50 control panels. Refer to the device installation instructions packaged with the device for more information.
Manufacturer | Model | Audio | Visual | Description |
---|
System Sensor
| SEP-SPSWL| | | Universal Expander Plate, Amber Lens, White, ALERT
SEP-SPSWL-P| | | Universal Expander Plate, White, Plain
SEP-BBSWL| | | Universal Expander Plate Back Box Skirt, White
HWL-LF| X| | 520Hz Sounder, white
HRL-LF| X| | 520Hz Sounder, red
HGWL-LF| X| | 520Hz Sounder, white, compact
HGRL-LF| X| | 520Hz Sounder, red, compact
P2WL-LF| X| X| 520Hz Sounder Strobe, white
P2RL-LF| X| X| 520Hz Sounder Strobe, red,
HCWL-LF| X| | 520Hz Sounder, white, ceiling
HCRL-LF| X| | 520Hz Sounder, red, ceiling
PC2WL-LF| X| X| 520Hz Sounder Strobe, white
PC2RL-LF| X| X| 520Hz Sounder Strobe, red
SCWL| | X| White Ceiling Strobe 2-wire
SCWL-TILE| | X| White Ceiling Strobe 2-wire
SPCWL | X| | White Ceiling Speaker
SPCWL-TILE | X| | White Ceiling Speaker
SPSCWL | X| X| White Ceiling Speaker/Strobe
SPSCWL-TILE| X| X| White Ceiling Speaker/Strobe
Table 7 Notification Appliances
- For use with ECS Series panels only.
NOTE:
The expander plate is for vertical wall mounting only. It is for use in indoor
applications and must be mounted in the correct orientation. “UP” is indicated
on the part to designate the top of the plate.
Releasing Solenoids
Refer to the fire panel manual for approved solenoids. The table below lists additional available releasing solenoids for use with the IFP-2000(ECS), IFP-1000(ECS), IFP-100(ECS) and IFP-50 control panels. Refer to the device installation instructions packaged with the device for more information.
Manufacturer| Model| Rated Voltage, DC| Rated Current,
mA
---|---|---|---
Ceodeux Extinguisher Valves Technology S.A.| B04425146| 24 VDC| 500 mA
Parker Hannifin| 73218BN4UNLVN0C111C2| 24 VDC| 410 mA
TLX| PA0337| 24 VDC| 500 mA
Table 8 Solenoids
Power Supplies
The table below lists additional available power supplies/battery chargers for use with the IFP-2000(ECS), IFP-1000(ECS), IFP-100(ECS), and IFP-50 control panels. Refer to the device installation instructions packaged with the device for more information.
- SK-PS6
- SK-PS10
- HPF-PS6B
- HPF-PS10B
Reference Documentation
Refer to the following FACP installation manuals for more information.
Farenhyt Model Numbers | FACP Installation Manual |
---|---|
IFP-50 | 151302 |
IFP-100(ECS) | 151458 |
IFP-1000(ECS) | 151460 |
IFP-2000(ECS) | 151430-L8 |