TEB TAX 400 Axial Fan Instructions

May 15, 2024
TEB

TEB TAX 400 Axial Fan

TEB-TAX-400-Axial-Fan-product

Product Specifications:

  • Model Types: TAX 400, TAX 500, TAX 600, TAX 700, TAX 800, TAX 1000, TAX 1200, TAXG 400, TAXG 500, TAXG 600, TAXG 700, TAXG 800, TAXG 1000, TAXG 1200
  • Materials: Mild steel, 3 Phase Induction type, Aluminum alloy casting
  • Installation Height (Ceiling): Blades should be installed more than 2.3m above the floor
  • Power Range: 0.2 to 30 kW
  • Grounding: Must be properly and reliably grounded

Safety Precautions:

  • Disconnect Power: Disconnect power supply completely before inspection or maintenance.
  • Secure Installation: Install on a strong foundation and securely mount all components.
  • Authorized Access Only: Unauthorized operators or inspectors are not allowed to access the fan.
  • Proper Grounding: The product must be properly and reliably grounded to avoid electric shock.
  • Professional Installation: Electrical wiring, ducting, and installation should be done by specialists.
  • Wear Protectors: Wear protective gear like gloves and helmets during installation and maintenance.

Installation Instructions:

Installation:
For user safety, the duct should be installed twice the diameter of the fan. Install a grille or shutter at the end of the duct for safety.

Connecting Wiring:

  1. Electrical wiring must adhere to international and local standards.
  2. Proper grounding is essential to prevent electric shock.
  3. To avoid motor burn-out due to overcurrent, mount an overload protector (1.2 – 1.5 times the motor full load current).
  4. Ensure correct voltage (within 30% of rated voltage).
  5. Check for correct rotation direction of the motor.
  6. Ensure proper ventilation around the motor.
  7. Connect the power cable and Earth Wire as per instructions provided.

Fan Terminal Box:
The motor terminal box is externally connected to the fan casing for easy access during wiring.

FAQs:

  • Q: What should I do if the fan falls during installation?
    A: Ensure a secure mounting using the specified procedure to prevent any accidents or injuries.

  • Q: Can unauthorized personnel access the fan for inspection?
    A: No, only authorized operators should handle inspection and maintenance to avoid any unexpected accidents.

Installation Instructions Axial Fan

Model Type.
TAX 400 TAX 500 TAX 600 TAX 700 TAX 800 TAX 1000 TAX 1200 TAXG 400 TAXG 500 TAXG 600 TAXG 700 TAXG 800 TAXG 1000 TAXG 1200

Thank you very much for choosing “TEB” Axial Fan.

Safety Precautions

WARNING

| Disconnect power supply completely before inspection or maintenance. May cause injury or electric shocks.

  • Install to the strong foundation. Reinforce, when intensity is insufficient.
  • When installation intensity is insufficient, it may cause an unexpected accident.

Securely mount the product using the specified procedure. If the product falls, it may result in personal injuries.
Securely mount all components and parts. If they fall, it may cause an injury.
| Unauthorized operator or inspector is not allowed to access. May cause unexpected accident.
CAUTION

| This product must be properly and reliably grounded.

If the product fails or if an electricity leakage occurs in it, it may cause an electric shock.

| Electrical wiring, ducting and installation should be done by specialist.
Insufficient wiring or installation may cause unexpected accident.
Wear protectors such as gloves and helmets during installation and maintenance.
May cause injury or burn.
For this fan, precautions must be taken to avoid the back-flow of gases to the room from the open-flue
of gas or other fuel-burning appliances.
Ceiling Installation : This fan should be installed so that the blades are more than 2.3m above the floor.

Name component Part

TEB-TAX-400-Axial-Fan- \(4\)

No

| PARTS NAME| MATERIALS| REMARKS
---|---|---|---
1| Fan casing| Mild steel| –
2| Motor| 3 Phase Induction type| 0.2 to 30 kW
3| Hub| Aluminum alloy casting| –
4| Blade| Aluminum alloy casting| –
5| Terminal box| Mild steel| –
6| Mounting feet/plate| Mild steel| –
7| Flexible metallic conduit| Mild steel| Zinc galvanized
8| Cover plate| Mild steel| –
9| Packing| Rubber| –
10| Hard-lock nut| Carbon steel| –
11| Guide vane| Mild steel| For TAXG type
12| Flange| Carbon steel| –

Installation Instructions

Installation
For the safety of users should be install the duct twice the diameter of fan and should be install grille or shutter closing the end of the duct for safety.

Connecting wiring

  1. Electrical wiring must be done safety and surely in accordance with the international and local standard.

  2. This product must be properly and reliably grounded.

  3. In order to avoid motor burn-out due to over current, be sure to mount an overload protection device (such as the motor breaker) that matches the ratings on each fan. (Select a motor breaker that supports the maximum current multiplied by 1.2 to 1.5 (described in the name plate))

  4. Always install the earth leakage breaker.
    Choose the earth leakage breaker whose operating current is lower than 30 mA.

  5. Open the terminal cover and connect the power cord to the terminal block inside the terminal box.

  6. Connect the power cord shown as dotted lines in the “Wiring Diagram”.

  7. Be sure to check the rotation direction.
    (A label indicating the correct rotation direction is applied on the side of the fan casing.)

Before connect, please make preparation of the power cable as shown below.
Please prepare the power cable and the Earth Wire by the customer.
TAX 400 TAX 500 TAX 600 TAX 700 TAX 800 TAX 1000 TAX 1200
TAXG 400 TAXG 500 TAXG 600 TAXG 700 TAXG 800 TAXG 1000 TAXG 1200

Fan Terminal Box
The motor terminal box is connected to the fan casing as an outside component, therefore easily accessible for wiring.

Wiring diagram

Power cord
Supply power cord and circuit components by customer.

TEB-TAX-400-Axial-Fan- \(5\)Connected by electric technician.

TEB-TAX-400-Axial-Fan- 01 After connection
Shut the terminal cover and tighten the screws. At that time, carry out with much care against the terminal cover biting power cord.

Specifications

TEB-TAX-400-Axial-Fan- \(9\)

Model| A| B| C| E| n- d1| Weight

(kg.)

---|---|---|---|---|---|---
TAX 400 (TAXG 400)| 400| 440| 456| 300 (400)| 12- 10.5| 25 (35)

TAX 500 (TAXG 500)

|

500

|

540

|

566

|

400 (515)

|

12- 10.5

| 35 (45)
40 (50)
45 (55)
500 (615)| 65 (75)
90 (100)
600 (715)| 110 (120)

TAX 600 (TAXG 600)

|

600

|

650

|

684

|

400 (520)

|

16- 13.0

| 50 (65)
55 (70)
65 (80)
80 (95)
600 (720)| 150 (165)
700 (820)| 210 (225)

TAX 700 (TAXG 700)

|

700

|

750

|

784

|

500 (640)

|

16- 13.0

| 70 (90)
75 (95)
95 (115)
110 (130)
120 (140)

800 (940)

| 250 (270)
270 (290)
325 (345)
345 (365)

TAX 800 (TAXG 800)

|

800

|

850

| 885|

500 (660)

|

16- 13.0

| 105 (130)
125 (150)
140 (165)
155 (180)
700 (860)| 220 (245)
235 (260)
TAX 1000 (TAXG 1000)| 1,000| 1,065| 1,109| 500 (675)| 24- 13.0| 200 (240)
215 (255)
700 (875)| 290 (330)
315 (355)
395 (435)
420 (460)
TAX 1200 (TAXG 1200)| 1,200| 1,265| 1,309| 700 (900)| 24- 13.0| 350 (400)
390 (440)
460 (510)
500 (550)
800 (1000)| 560 (610)

TEB Ventilation Company Limited
www.teb.co.th

Printed in Thailand
TAX0400705-F