Touch SMAOS-L Smart Occupancy Sensor Instruction Manual

May 15, 2024
Touch

INSTALLATION INSTRUCTIONS
**TOUCHÉ LIGHTING CONTROLS

SMART OCCUPANCY SENSOR
PART # SMAOS-L/H
**

FRONT OF OCCUPANCY SENSOR

BACK OF OCCUPANCY SENSOR

NOTE: LABELED INPUT AND OUTPUT PORTS ARE FOR CABLE IDENTIFICATION ONLY – PORTS ARE ELECTRICALLY IDENTICAL & CAN BE INTERCHANGED.

RECESSED MOUNTING

Touch SMAOS-L Smart Occupancy Sensor - RECESSED
MOUNTING

4 SQUARE WITH MUD RING MOUNTING

SYMBOLS AS SHOWN
ON SUBMITTAL AND
CONSTRUCTION
DOCUMENTS

NOTES

  1. PIR FRESNEL LENS AND LED INDICATOR (SEE CONNECTIVITY PAGE FOR LED INDICATION)
  2. SMART PORTS – MINIMUM CAT 5 CABLE – DO NOT CONNECT TO BRANCH PORTS
  3. 3-1/2″ DIAMETER OPENING. 3-5/8″ HOLE SAW FOR 3″ CONDUIT IS ALLOWED
  4. MOUNTING SPRINGS
  5. STANDARD 4 SQUARE BOX
  6. CIRCLE MUD RING FOR 4 SQUARE BOX
  7. HEXAGONAL ELECTRICAL BOX
  8. SNAP RING REQUIRED FOR MOUNTING TO HEXAGONAL ELECTRICAL BOX (SOLD SEPARATELY)

HEXAGONAL ELECTRICAL BOX MOUNTING

Touch SMAOS-L Smart Occupancy Sensor - BOX MOUNTING

SMART OCCUPANCY SENSOR CONNECTIVITY

CABLE TYPES

LINE ID| DESCRIPTION| TYPE| NOTES
Touch SMAOS-L Smart Occupancy Sensor - icon 3| SMART| CAT 5 (MIN)| TOTAL SMARTNET LENGTH NOT TO EXCEED 400′

Touch SMAOS-L Smart Occupancy Sensor - SENSOR
CONNECTIVITY

LED INDICATION

LED COLOR| DESCRIPTION| SENSES OCCUPANCY| RECOMMENDATION(S)
| BLUE| INDICATION MEANING| NONE
| GREEN| SENSOR IS FORCED VACANT| NONE
BLINK| BLINKING GREEN| SENSOR HAS POWER BUT  IS NOT
COMMUNICATING WITH  CONTROLLER| CHECK PATCH CABLE
| RED| CONNECTED TO BRANCH PORT| CONNECT TO SMARTNET
| OFF| NO POWER| CHECK PATCH CABLE

Touché Lighting Controls (a Product of ESI Ventures)
A: 2085 Humphrey Street, Fort Wayne, IN 46803
W: ToucheControls.com