Touch SMAOS-L Smart Occupancy Sensor Instruction Manual
- May 15, 2024
- Touch
Table of Contents
INSTALLATION INSTRUCTIONS
**TOUCHÉ LIGHTING CONTROLS
SMART OCCUPANCY SENSOR
PART # SMAOS-L/H
**
FRONT OF OCCUPANCY SENSOR
BACK OF OCCUPANCY SENSOR
NOTE: LABELED INPUT AND OUTPUT PORTS ARE FOR CABLE IDENTIFICATION ONLY – PORTS ARE ELECTRICALLY IDENTICAL & CAN BE INTERCHANGED.
RECESSED MOUNTING
4 SQUARE WITH MUD RING MOUNTING
SYMBOLS AS SHOWN
ON SUBMITTAL AND
CONSTRUCTION
DOCUMENTS
NOTES
- PIR FRESNEL LENS AND LED INDICATOR (SEE CONNECTIVITY PAGE FOR LED INDICATION)
- SMART PORTS – MINIMUM CAT 5 CABLE – DO NOT CONNECT TO BRANCH PORTS
- 3-1/2″ DIAMETER OPENING. 3-5/8″ HOLE SAW FOR 3″ CONDUIT IS ALLOWED
- MOUNTING SPRINGS
- STANDARD 4 SQUARE BOX
- CIRCLE MUD RING FOR 4 SQUARE BOX
- HEXAGONAL ELECTRICAL BOX
- SNAP RING REQUIRED FOR MOUNTING TO HEXAGONAL ELECTRICAL BOX (SOLD SEPARATELY)
HEXAGONAL ELECTRICAL BOX MOUNTING
SMART OCCUPANCY SENSOR CONNECTIVITY
CABLE TYPES
LINE ID| DESCRIPTION| TYPE| NOTES
|
SMART| CAT 5 (MIN)| TOTAL SMARTNET LENGTH NOT TO EXCEED 400′
LED INDICATION
LED COLOR| DESCRIPTION| SENSES OCCUPANCY|
RECOMMENDATION(S)
| BLUE| INDICATION MEANING| NONE
| GREEN| SENSOR IS FORCED VACANT| NONE
BLINK| BLINKING GREEN| SENSOR HAS POWER BUT IS NOT
COMMUNICATING WITH CONTROLLER| CHECK PATCH CABLE
| RED| CONNECTED TO BRANCH PORT| CONNECT TO SMARTNET
| OFF| NO POWER| CHECK PATCH CABLE
Touché Lighting Controls (a Product of ESI Ventures)
A: 2085 Humphrey Street, Fort Wayne, IN 46803
W: ToucheControls.com
Read User Manual Online (PDF format)