Schneider Electric 47952 MasterPact NW Air Circuit Breaker Instruction Manual

June 17, 2024
Schneider Electric

47952 Master Pact NW Air Circuit Breaker
Instruction ManualSchneider Electric 47952 MasterPact NW Air Circuit
Breaker Chassis accessories
Installation manual

47952 Master Pact NW Air Circuit Breaker

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - MasterPact
NW

Disclaimer

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Safety instructions

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Install safety barriers and display a danger sign.
  • Replace all devices, doors, and covers before turning on power to this equipment.
    Failure to follow these instructions will result in death or serious injury.

Precautions before carrying out any work

Draw out circuit breakerSchneider Electric 47952 MasterPact NW Air
Circuit Breaker - Drawout circuit breaker

Necessary tools

Screwdriver (Pozidrive n°2, 3 or slotted).Schneider Electric 47952
MasterPact NW Air Circuit Breaker - Necessary tools

Angled socket wrench.Schneider Electric 47952 MasterPact NW Air Circuit
Breaker - Angled socket wrench

Installation

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Basic
configuration![Schneider Electric 47952 MasterPact NW Air Circuit Breaker

Master Pact NW
Connected-disconnected carriage position switchesSchneider Electric 47952
MasterPact NW Air Circuit Breaker - MasterPact NW

Disclaimer

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Safety instructions

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Install safety barriers and display a danger sign.
  • Replace all devices, doors, and covers before turning on power to this equipment.
    Failure to follow these instructions will result in death or serious injury.

Precautions before carrying out any work
Draw out circuit breakerSchneider Electric 47952 MasterPact NW Air
Circuit Breaker - Drawout circuit breaker2

Necessary tools
Screwdriver (Pozidrive n°2, 3 or slotted).Schneider Electric 47952
MasterPact NW Air Circuit Breaker - Necessary tools2

Angled socket wrench.Schneider Electric 47952 MasterPact NW Air Circuit
Breaker - Angled socket Basic configuration

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Basic
configuration2

Other configurationsSchneider Electric 47952 MasterPact NW Air Circuit
Breaker - Other configurations

Safety shutters

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - MasterPact
NW

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Install safety barriers and display a danger sign.
  • Put back all devices, doors, and covers before turning on power to this equipment.
    Failure to follow these instructions will result in death or serious injury.

Safety instructions

WARNING: This product can expose you to chemicals including Diisononyl Phthalate (DINP), which is known to the State of Califia to cause cancer and Disobey Phthalate (DIDP) which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.

Required for Installation

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Required for
Installation

Before working on the device

Draw out circuit breakerSchneider Electric 47952 MasterPact NW Air
Circuit Breaker - Drawout circuit breaker

Remove Circuit Breaker from ChassisSchneider Electric 47952 MasterPact
NW Air Circuit Breaker - Remove Circuit Breaker from
Chassis

Master Pact NW08-40 3P/4P
Broken Shutter Removal

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Broken Shutter
Removal

Broken Shutter Removal

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Broken Shutter
Removal2

Shutters Installation

  • Install 2 shutters in the order indicated.
  • Only 2-shutter installation for Master Pact NW08-403P circuit breaker is described in detail.

Schneider Electric 47952 MasterPact NW Air Circuit Breaker -
shutters

Shutters InstallationSchneider Electric 47952 MasterPact NW Air Circuit
Breaker - Shutters InstallationSchneider Electric 47952 MasterPact NW Air
Circuit Breaker - Shutters Installation2Schneider Electric 47952 MasterPact NW
Air Circuit Breaker - Shutters Installation 1Schneider Electric 47952 MasterPact NW
Air Circuit Breaker - Shutters2

Check

WARNING
RISK OF SHUTTERS BEING JAMMED IN OPEN POSITION Release the pushbutton slowly to simulate the movement of the device in the chassis and check that the shutters are closed correctly. Failure to follow these instructions can result in death, serious injury, or equipment damage.Schneider Electric
47952 MasterPact NW Air Circuit Breaker - Shutters3

Shutter Locking

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Shutter
Locking

Broken Shutter RemovalSchneider Electric 47952 MasterPact NW Air
Circuit Breaker - Shutter Locking1Schneider Electric 47952 MasterPact NW Air
Circuit Breaker - BrokenSchneider Electric 47952 MasterPact NW Air Circuit Breaker -
MasterPact

Shutters Installation

  • Install shutters in the order indicated:
  • 6 shutters for Master Pact NW40b-63 3P circuit breakers
  • 8 shutters for Master Pact NW40b-63 4P circuit breakers.
    Only the installation of one top and one bottom shutter for Master Pact NW40b-63 circuit breaker is described in detail.

Schneider Electric 47952 MasterPact NW Air Circuit Breaker -
breakersSchneider
Electric 47952 MasterPact NW Air Circuit Breaker - Shutters
InstallationSchneider Electric 47952 MasterPact NW Air Circuit
Breaker - Shutters Installation1Schneider Electric 47952 MasterPact NW
Air Circuit Breaker - Shutters Installation2Schneider Electric 47952 MasterPact NW
Air Circuit Breaker - Shutters Installation3

Check

WARNING
RISK OF SHUTTERS BEING JAMMED IN OPEN POSITION
Release the pushbutton slowly to simulate the movement of the device in the chassis and check that the shutters are closed correctly.
Failure to follow these instructions can result in death, serious injury, or equipment damage.![Schneider Electric 47952 MasterPact NW Air Circuit Breaker

Shutter LockingSchneider Electric 47952 MasterPact NW Air Circuit
Breaker - Shutter Locking

Circuit Breaker Reinstallation

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Circuit
Breaker

Breaker mismatch protection

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Breaker
mismatch

Disclaimer

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Install safety barriers and display a danger sign.
  • Replace all devices, doors, and covers before turning on power to this equipment.
    Failure to follow these instructions will result in death or serious injury.

Before working on the device

Draw out circuit breaker Schneider Electric 47952 MasterPact NW Air Circuit
Breaker - Before working

Necessary tools
Screwdriver (Pozidrive n°2, 3 or slotted), Combination wrench.Schneider
Electric 47952 MasterPact NW Air Circuit Breaker - Necessary
tools5

Installation![Schneider Electric 47952 MasterPact NW Air Circuit Breaker

Disconnected, connected and test carriage position lockSchneider Electric
47952 MasterPact NW Air Circuit Breaker - carriage

Disclaimer

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Install safety barriers and display a danger sign.
  • Replace all devices, doors, and covers before turning on power to this equipment.
    Failure to follow these instructions will result in death or serious injury.

Before working on the device
Draw out circuit breaker
Schneider Electric 47952 MasterPact NW Air
Circuit Breaker - device

Necessary tools
Screwdriver (Pozidrive n° 2, 3 or slotted), combination wrench, tightening tool Castell 47540.Schneider Electric 47952 MasterPact NW Air Circuit
Breaker - toolsSchneider
Electric 47952 MasterPact NW Air Circuit Breaker -
tools1

Locking in disconnected position

Schneider Electric 47952 MasterPact NW Air Circuit Breaker -
position

Locking in disconnected, connected and test positions

Schneider Electric 47952 MasterPact NW Air Circuit Breaker -
disconnected

Door interlock

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Door
interlock

Disclaimer

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Install safety barriers and display a danger sign.
  • Replace all devices, doors, and covers before turning on power to this equipment. Failure to follow these instructions will result in death or serious injury.

Before working on the device
Draw out circuit breaker

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - circuit breaker
2

Screwdriver (Pozidrive n°2, 3 or slotted), Combination wrench.Schneider
Electric 47952 MasterPact NW Air Circuit Breaker -
carriage2Schneider
Electric 47952 MasterPact NW Air Circuit Breaker -
carriage3Schneider
Electric 47952 MasterPact NW Air Circuit Breaker -
carriage4

Notes

Racking interlock Schneider Electric 47952 MasterPact NW Air Circuit
Breaker - Door interlock1

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Safety instructions

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Install safety barriers and display a danger sign.
  • Replace all devices, doors, and covers before turning on power to this equipment.
    Failure to follow these instructions will result in death or serious injury.

Before working on the device
Draw out circuit breaker

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Drawout
circuitSchneider Electric 47952 MasterPact NW Air Circuit Breaker -
Drawout circuit1

Arc chamber cover

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Arc
chamber

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Install safety barriers and display a danger sign.
  • Replace all devices, doors, and covers before turning on power to this equipment. Failure to follow these instructions will result in death or serious injury.

Before working on the device
Draw out circuit breaker

Schneider Electric 47952 MasterPact NW Air Circuit Breaker - Arc
chamber1

Necessary tools
Screwdriver (Torx No. 30).Schneider Electric 47952 MasterPact NW Air
Circuit Breaker - tools2Schneider Electric 47952 MasterPact NW Air Circuit Breaker -
carriage6Schneider
Electric 47952 MasterPact NW Air Circuit Breaker -
carriage7

Notes

Schneider Electric Industries SAS
35 rue Joseph Monnier
CS 30323
F – 92506 Ruel Malmaison Cedex
www.se.com 47952
04443718AA-12
Printed on recycled paper.
Designed by: Schneider Electric
Printed by:
© 2023 Schneider Electric. All rights reserved.
Schneider Electric Limited
Stafford Park 5
Telford, TF3 3BL
United Kingdom
www.se.com/uk

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals